Peter Huber Kältemaschinenbau Unichiller 015w-H OLÉ
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 015w-H OLÉ

Peter Huber Kältemaschinenbau Unichiller 015w-H OLÉ — Recirculating chillers with Noise level 54 dB.

The Unichiller 015w-H OLÉ is a water-cooled recirculating chiller with an immersion pump and OLÉ controller, rated for -20 to 100 °C. It is the water-cooled variant of the 015 series, requiring a cooling water supply of 5–20 °C at ≥1 bar differential pressure. It serves externally closed process loops where heat is rejected to facility cooling water.

Noise level
54 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller 015w-H OLÉ Current 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 54 dB(A)
Maximum delivery flow rate 29 l/min (1 bar)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type Immersion pump
Temperature range -20...100 °C
Dimensions, Weight & Mechanical Design
Weight 63 kg
Electrical, Power & Drive Specifications
Fuse rating 16 A
Power supply 220-240V 1~ 50Hz
Interfaces, Connections & Control
Controller OLÉ
Display resolution 0, 1 K
Digital interface USB (Device), RS232 Interface
Temperature display OLED Display
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 36 l/h (cooling water 15°C, flow -20°C)
cooling water 15°C, flow -10°C: 48 l/h · cooling water 15°C, flow 0°C: 60 l/h · cooling water 15°C, flow 15°C: 68 l/h
Cooling water differential pressure 1 bar (min)
Cooling Water Pressure 6 bar (max)
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Process Limits
Externally closed loop only; no open bath

The manual restricts this chiller to externally closed applications. Designing an open tank or direct immersion circuit violates the intended hydraulic configuration and may cause pump cavitation or overflow.

Unichiller Operation Manual, Section: Function Description, p. 34
Cooling & Media
Cooling water must be 5–20 °C at ≥1 bar differential

The datasheet specifies cooling water intake between 5 °C and 20 °C and a minimum differential pressure of 1 bar. Below 1 bar the condenser may not receive adequate flow; above 20 °C cooling capacity drops and flow demand rises.

Unichiller 015w-H OLÉ Technical Data, p. 2
Cooling & Media
Plastic pump incompatible with acetone and polyglycols

The immersion pump is plastic and not resistant to acetone or polyglycols. Select an alternative heat-transfer fluid or specify a more resistant pump; otherwise pump damage and leakage can occur.

Unichiller 015w-H OLÉ Technical Data, p. 2
Mounting
50–200 cm side clearance required for maintenance

Free-standing installation requires a wall clearance of 50 to 200 cm on either side. Planning a tighter footprint will block service access to the refrigerant circuit and pump.

Unichiller Operation Manual, Section: Commissioning, p. 25
Electrical
Country-specific plug must be specified at ordering

Single/two-phase devices are delivered with a power cable and country-specific plug; the plug type must be stated on the order. Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, and not all combinations are permitted.

Unichiller 015w-H OLÉ Technical Data, p. 2
Control & I/O
Configure power-failure response before unattended operation

The OLÉ controller supports OFF/Standby, ON and Power Failure Auto restart modes. For processes that must not restart automatically after a mains interruption, select OFF/Standby; for exothermic reactions, verify that Process Safety mode is enabled so maximum cooling is released at the OT trigger.

Unichiller Operation Manual, Section: Normal Operation, p. 18–19
Maintenance
Refrigerant circuit work restricted to approved contractors

Any work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. In-house maintenance is limited to non-refrigerant tasks; plan service contracts accordingly.

Unichiller Operation Manual, Section: Maintenance, p. 17
Operation
Shut off cooling water even for overnight downtime

The cooling water supply must be closed for any downtime, including overnight. Leaving it open risks water damage and corrosion in the cooling circuit during idle periods.

Unichiller Operation Manual, Section: Commissioning, p. 28

Selection & Integration Q&A

When should I choose the water-cooled 015w-H OLÉ instead of the air-cooled 015-H OLÉ?

Choose the 015w-H OLÉ when facility cooling water (5–20 °C, ≥1 bar differential) is available and heat rejection to air is undesirable; it is quieter (54 dB(A) vs 63 dB(A)). The air-cooled 015-H OLÉ avoids cooling-water infrastructure and is preferable where water supply or drainage is unavailable.

What cooling-water supply and connections does this chiller require from the facility?

A cooling-water supply of 5–20 °C with at least 1 bar differential pressure and maximum 6 bar, connected via G1/2 male fittings. Consumption is 36–68 l/h depending on flow temperature. Pipes must be insulated if below condensation point, and electrical lines below the unit protected from liquid ingress.

What are the installation environment and duty-cycle limits for this model?

Indoor use only, 5–40 °C ambient, illuminance ≥300 lx, altitude ≤2000 m, and no ATEX zone. Maintain 50–200 cm side clearance for maintenance. Activate leveling feet/parking brakes before start-up. Shut off cooling water for any downtime, including overnight.

What maintenance and accessories are required beyond the base delivery?

Refrigerant-circuit work must be by approved contractors; no user-serviceable refrigerant tasks. The base delivery includes a power cable with country-specific plug (specify at order). The Pt100 sensor connection is a factory-fitted option only, not retrofittable. Freeze protection requires glysantine or ethylene glycol added to water.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 015w-H OLÉ Technical Data
Datasheet ·97,5 КБ ·2 pp.
View PDF