Peter Huber Kältemaschinenbau Unichiller P007-H OLÉ
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P007-H OLÉ

Peter Huber Kältemaschinenbau Unichiller P007-H OLÉ — Recirculating chillers with Noise level 58 dB.

The Unichiller P007-H OLÉ is an air-cooled, CFC/HCFC-free recirculating chiller with a plastic pump and G3/4 male connections, rated for -20 to 100 °C. Its 'P' designation targets high-pressure-drop circuits, and the OLÉ controller provides USB and RS232 interfaces. It serves externally closed cooling loops requiring sub-ambient to moderate heating duty.

Noise level
58 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller P007-H OLÉ Current 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 58 dB(A)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
Temperature range -20...100 °C
Dimensions, Weight & Mechanical Design
Weight 57 kg
Electrical, Power & Drive Specifications
Current consumption 14 A
Fuse rating 16 A
Power supply 208-240V 1~/2~ 50/60Hz
Interfaces, Connections & Control
Controller OLÉ
Display resolution 0, 1 K
Digital interface USB (Device), RS232 Interface
Temperature display OLED Display
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Behavior under load and media

Installation, connection and control

Integration & Operating Notes

Mounting
Maintain 50–200 cm side clearance and activate leveling feet

Free-standing models require a wall clearance of 50 to 200 cm on either side for maintenance access. Before switching on, the parking brakes must be activated at the casters and/or the leveling feet unscrewed/activated to prevent movement and crushing injuries.

Unichiller Operation Manual, Section on Installation
Electrical
Supply tolerances must not combine in the same direction

Voltage tolerance is ±5% and frequency tolerance ±2%, but these must not combine in the same direction. A supply outside these combined limits can damage the compressor. The unit requires a 16 A fuse and draws max 14 A at 208-240 V 1~/2~ 50/60 Hz.

Unichiller P007-H OLÉ Datasheet, page 2
Cooling & Media
Cooling capacity derates with rising ambient temperature

Cooling capacity is quoted at 20 °C room temperature and drops as ambient rises. The unit may only be operated between 5 °C and 40 °C ambient. Air-cooled condensers reject heat to the room, so adequate air flow and ventilation must be provided at the installation site.

Unichiller P007-H OLÉ Datasheet, page 2
Control & I/O
Configure power-failure response and Process Safety mode

The power-failure response can be set to OFF/Standby, ON, or Power Failure Auto via the Pilot ONE controller. For exothermic processes, Process Safety mode releases maximum cooling capacity when the OT trigger value is reached instead of switching off all poles, preventing runaway temperatures.

Unichiller Operation Manual, pages 18–19
Maintenance
Refrigerant circuit work only by approved contractors

Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A (GHS H280, GWP 1397); observe the charge amount and room size to avoid exceeding the refrigerant limit per m³ of ambient air.

Unichiller Operation Manual, page 17 and page 15
Electrical
Specify country-specific plug at order

Single and two-phase devices (100 V to 240 V) are supplied with a power cable and country-specific plug that must be specified when ordering. Missing plug specification leads to a unit that cannot be connected on site.

Unichiller P007-H OLÉ Datasheet, page 2

Selection & Integration Q&A

When should I choose the P007-H OLÉ over the Unichiller 015 variants?

Choose the P007-H OLÉ for high-pressure-drop circuits (the 'P' designation) and lower noise (58 dB(A) vs 63 dB(A) on 015 models). The 015 series offers higher capacity but is louder; select it when cooling demand exceeds the P007's 0.7 kW at 15 °C.

What are the requirements for connecting the pump to my process loop?

The pump connection is G3/4 male. Maximum tightening torques must not be exceeded and connections must be counterheld. The pump delivers max 25 l/min at 2.5 bar, falling to 6 l/min at 2.0 bar, so verify your loop's pressure drop against this curve.

What ambient and installation limits apply to the P007-H OLÉ?

Operate only between 5 °C and 40 °C ambient, indoors, at illuminance ≥300 lx and altitude ≤2000 m. Maintain 50–200 cm side clearance. Do not install in an ATEX zone. Cooling capacity derates as ambient rises above 20 °C.

What maintenance and accessories are required beyond the base unit?

Refrigerant circuit work must be by approved contractors. The power cable and country-specific plug must be specified at order. For freeze protection, glysantine or ethylene glycol is needed. Minimum filling capacity is 3.8 l; expansion tank is 1.7 l.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P007-H OLÉ Datasheet
Datasheet ·111,1 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF