Peter Huber Kältemaschinenbau Unichiller P025w-H OLÉ
Peter Huber Kältemaschinenbau Unichiller P025w-H OLÉ — Recirculating chillers with Noise level 60 dB.
The Unichiller P025w-H OLÉ is a water-cooled recirculating chiller with a plastic pump (type B) and OLÉ controller, rated for -10...100 °C in externally closed circuits. Its 'P' designation targets high-pressure-drop loops, and the water-cooled condenser requires 5–20 °C cooling water at 1–6 bar differential. It serves as a compact process chiller for closed-loop heat removal.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P025w-H OLÉ Current | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 60 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| Temperature range | -10...100 °C |
| Weight | 67 kg |
| Fuse rating | 16 A |
| Power supply | 220-240V 1~ 50Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 72 l/h (cooling water 15 °C, flow -10 °C) cooling water 15 °C, flow 0 °C: 84 l/h · cooling water 15 °C, flow 15 °C: 84 l/h |
| Cooling water differential pressure | 1 bar (min) |
| Cooling Water Pressure | 6 bar (max) |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- Water-cooled condenser (R-449A, 0.4 kg charge, GWP 1397) with a plastic pump (type B, non-adjustable speed) and G3/4 AG male pump connection; cooling-water ports are G1/2 male.
- The 'P' in the model code marks this unit as particularly suitable for applications requiring high pressure drops, per the operation manual.
- Sibling Unichiller 015 variants are air-cooled (63 dB(A)); this P025w-H OLÉ is water-cooled and rated 60 dB(A), so it is selected where a water heat sink is available and lower noise is needed.
- OLÉ controller with OLED display, 0.1 K resolution, USB (Device) and RS232 interfaces.
Behavior and media
- Temperature range -10...100 °C; cooling-water consumption is 84 l/h at 15 °C cooling water with 0 °C flow, 72 l/h at -10 °C flow, and 84 l/h at 15 °C flow.
- Cooling power drops as cooling-water temperature rises, and the cooling-water flow rate may need to be increased accordingly (datasheet).
- The plastic pump is not resistant to acetone or polyglycols; for freeze protection use water mixed with glysantine or ethylene glycol.
- Cooling-water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM; select cooling water accordingly.
Installation, control and operation
- Power supply 220–240 V 1~ 50 Hz, max current 15.9 A, 16 A fuse; voltage tolerance ±5% with simultaneous frequency tolerance ±2%, but -5% voltage with +2% frequency is not allowed.
- IP20 protection requires a dry indoor location; electrical lines directly below the unit must be protected against liquid ingress from condensation.
- The OLÉ controller includes an autostart function for power failure; the power-failure response can be configured as OFF/Standby, ON, or Power Failure Auto via the Pilot ONE.
- Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles.
Integration & Operating Notes
The water-cooled condenser requires a cooling-water intake temperature between 5 °C and 20 °C and a differential pressure of at least 1 bar at the G1/2 male connection, with a maximum of 6 bar. Below the condensation point, cooling-water pipes must be insulated to prevent condensation.
The OLÉ controller offers OFF/Standby, ON, or Power Failure Auto response after power restoration. For processes where automatic restart is unsafe, select OFF/Standby; for continuous cooling, Power Failure Auto restarts the unit automatically.
In Process Safety mode, the controller releases maximum cooling capacity when the overtemperature trigger value is reached instead of switching off all poles. This prevents runaway temperatures in exothermic processes but requires the trigger value to be set correctly.
Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A with a charge of 0.4 kg (0.6 t CO2 equivalent), and room size must be checked against the refrigerant limit per m³.
Shut off the cooling water supply to the unit even for shorter downtimes such as overnight to prevent water damage and corrosion. Before switching on, activate parking brakes and/or unscrew leveling feet to prevent movement.
Selection & Integration Q&A
Choose the P025w-H OLÉ when you need water cooling, lower noise (60 dB(A) vs 63 dB(A)), and a 'P' pump suited to high pressure-drop loops. The 015 variants are air-cooled and may be preferred where no cooling water is available.
It requires cooling water at 5–20 °C with a differential pressure of 1–6 bar at G1/2 male connections. Consumption is 84 l/h at 15 °C cooling water and 0 °C flow, 72 l/h at -10 °C flow. Insulate pipes below the condensation point.
Install indoors only, at 5–40 °C ambient, with 50–200 cm side clearance for maintenance and at least 300 lx illuminance. IP20 requires a dry location; protect electrical lines below the unit from condensation. Not for ATEX zones.
Refrigerant circuit work must be by approved contractors. Shut off cooling water for downtimes. Base delivery excludes hoses and fittings for G1/2 and G3/4 connections; order suitable hoses and insulation separately. No specific maintenance interval is stated in the provided documents.