Peter Huber Kältemaschinenbau Unichiller 015w-H
Peter Huber Kältemaschinenbau Unichiller 015w-H — Recirculating chillers with Noise level 54 dB.
The Unichiller 015w-H is a water-cooled recirculating chiller with a 1 kW cooling capacity at 0 °C and a -20…100 °C temperature range, controlled by the Pilot ONE. Its 'w' designation indicates water cooling, distinguishing it from air-cooled siblings in the 015 series. It serves externally closed process loops requiring precise temperature control with facility cooling water.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller 015w-H Current | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 54 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | Yes |
| Pump type | Immersion pump |
| External sensor connection | Pt100 |
| Temperature range | -20...100 °C |
| Weight | 57 kg |
| Current consumption | 13 A |
| Fuse rating | 16 A |
| Power supply | 220-240V 1~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Cooling capacity | 1 kW (at 0 °C) |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 36 l/h (cooling water at 15 °C, flow -20 °C) cooling water at 15 °C, flow -10 °C: 48 l/h · cooling water at 15 °C, flow 0 °C: 60 l/h · cooling water at 15 °C, flow 15 °C: 68 l/h |
| Cooling water differential pressure | 1 bar |
| Cooling Water Pressure | 6 bar |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and Series Positioning
The Unichiller 015w-H is a water-cooled recirculating chiller in the Unichiller 015 series. Unlike the air-cooled Unichiller 015, 015-H, and OLÉ variants, this model uses a facility cooling water circuit for heat rejection, which reduces noise emission to 54 dB(A) compared with 63 dB(A) for the air-cooled siblings. The unit is built for externally closed applications only and is not explosion-protected, so it must not be installed in ATEX zones. The refrigerant circuit contains R-449A (GWP 1397, charge 0.25 kg, 0.3 t CO2 equivalent).
Hydraulic and Thermal Behavior
The immersion pump delivers a maximum of 29 l/min at 1 bar maximum delivery pressure, with 21 l/min available at 0.5 bar. The minimum filling capacity is 3.8 l, and the expansion vessel volume is 1.7 l. Cooling water consumption depends on the required flow temperature: 60 l/h at 0 °C, 68 l/h at 15 °C, 48 l/h at -10 °C, and 36 l/h at -20 °C, all with cooling water at 15 °C. The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, so only compatible water quality may be used. The plastic pump is not resistant to acetone or polyglycols; a more resistant pump is available at extra cost. For freeze protection below 0 °C, water should be mixed with glysantine or ethylene glycol.
Installation, Control, and Operation
The unit requires a 220-240V 1~ 50Hz supply with a maximum current of 13 A and a 16 A fuse. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed. The Pilot ONE controller provides Ethernet, USB (Host and Device), and RS232 interfaces, and supports a Pt100 external sensor. The power-failure response is configurable as OFF/Standby, ON, or Power Failure Auto. Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached, rather than switching off all poles. The unit has IP20 protection and must be installed indoors at 5…40 °C ambient temperature with at least 300 lx illuminance and up to 2000 m altitude. A wall clearance of 50 to 200 cm per side is required for maintenance. Leveling feet must be activated and parking brakes applied before startup. Cooling water supply must be shut off even for short downtimes such as overnight.
Integration & Operating Notes
The facility cooling water supply must provide a differential pressure of at least 1 bar and must never exceed 6 bar. Insufficient pressure prevents proper heat rejection; excessive pressure can damage the cooling water circuit. Verify the site supply before installation.
Free-standing models require a wall clearance of 50 to 200 cm on either side to allow maintenance access. The unit must be installed indoors at 5…40 °C ambient temperature with at least 300 lx illuminance and up to 2000 m altitude. Leveling feet must be unscrewed/activated and parking brakes applied before switching on.
The standard plastic pump is not resistant to acetone or polyglycols (depending on the manufacturer). These media must be avoided, or a more resistant plastic pump ordered at extra cost. The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, so only suitable cooling water may be used.
The cooling water supply must be shut off even for short downtimes such as overnight to prevent water damage and corrosion during idle periods. Electrical lines directly below a water-cooled unit must be protected against liquid ingress from condensation.
Selection & Integration Q&A
Choose the 015w-H when facility cooling water is available and lower noise (54 dB(A) vs 63 dB(A)) is required. Air-cooled siblings are preferable if cooling water is unavailable or if water consumption and connection costs are prohibitive.
Cooling water: differential pressure 1–6 bar, intake temperature 5–20 °C, connection G1/2 male. Process loop: pump connection G3/4 AG male, max delivery pressure 1 bar, min filling volume 3.8 l. Ensure external circuit pressure drop allows at least 21 l/min at 0.5 bar.
Install indoors at 5–40 °C ambient, max 2000 m altitude, illuminance ≥300 lx. Maintain 50–200 cm wall clearance per side. IP20 protection; protect electrical lines below unit from condensation. Not for ATEX zones. Leveling feet and parking brakes must be set before operation.
Refrigerant circuit work only by approved contractors. Cooling water must be shut off for downtimes. Base delivery excludes heat transfer fluid, freeze-protection additives (glysantine/ethylene glycol), and external Pt100 sensor. A more resistant plastic pump for acetone/polyglycols is optional at extra cost.