Peter Huber Kältemaschinenbau Unichiller 022w OLÉ
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 022w OLÉ

Peter Huber Kältemaschinenbau Unichiller 022w OLÉ — Recirculating chillers with Noise level 60 dB.

The Unichiller 022w OLÉ is a water-cooled recirculating chiller with an immersion pump and OLÉ controller, covering -10 to 40 °C. It is the smallest OLÉ variant in the Unichiller series, distinguished by its 60 dB(A) noise level and G3/4 pump connection. It serves externally closed cooling circuits requiring a 1–6 bar cooling water supply.

Noise level
60 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller 022w OLÉ Current 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 60 dB(A)
Maximum delivery flow rate 29 l/min (pressure pump max 1 bar)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type Immersion pump
Temperature range -10...40 °C
Dimensions, Weight & Mechanical Design
Weight 60 kg
Electrical, Power & Drive Specifications
Current consumption 6 A (max)
Fuse rating 16 A
Power supply 220-240V 1~ 50Hz
Interfaces, Connections & Control
Controller OLÉ
Display resolution 0, 1 K
Digital interface USB (Device), RS232 Interface
Temperature display OLED Display
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 77 л/час (at 15°C, flow -10°C)
at 15°C, flow 0°C: 96 l/h · at 15°C, flow 15°C: 95 l/h
Cooling water differential pressure 1 bar (min)
Cooling Water Pressure 6 bar (max)
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior and media

Installation, control and operation

Integration & Operating Notes

Process Limits
Cooling water must stay within 1–6 bar differential pressure

The cooling-water circuit requires a minimum differential pressure of 1 bar and must never exceed 6 bar; undersupply reduces cooling capacity, while overpressure can damage the internal copper/stainless/EPDM circuit. Verify the supply pressure at the unit inlet, not at the building header.

Unichiller 022w OLÉ Technical Data, Specifications
Cooling & Media
Insulate cooling-water pipes if intake drops below dew point

The unit is designed for cooling-water intake temperatures of 5–20 °C; if the intake temperature falls below the condensation point of the ambient air, the cooling-water pipes inside the unit must be insulated to prevent condensate formation and electrical hazard.

Unichiller 022w OLÉ Technical Data, Installation
Electrical
Avoid -5% voltage combined with +2% frequency

Voltage tolerance is ±5% with a simultaneous frequency tolerance of ±2%, but the combination of -5% voltage and +2% frequency is not permitted; check site power quality against this rule before commissioning, as the 16 A fuse protects the 6 A maximum current draw.

Unichiller 022w OLÉ Technical Data, Compliance
Mounting
Keep 50–200 cm clearance per side for maintenance access

Free-standing installation requires a wall clearance of 50 to 200 cm on either side to allow service access to the refrigerant circuit and pump; also confirm room volume against the 0.16 kg R-290 charge to stay below the refrigerant limit per m³ of ambient air.

Unichiller Operation Manual, Installation
Operation
Shut off cooling water even for overnight downtime

Close the cooling-water supply to the unit for any downtime, including overnight, to prevent water damage and corrosion in the cooling circuit; this is separate from the electrical power-failure response setting.

Unichiller Operation Manual, Operation
Control & I/O
Configure power-failure response before unattended runs

The OLÉ controller can be set to OFF/Standby, ON, or Power Failure Auto after a mains failure; for exothermic processes, Process Safety mode releases maximum cooling when the overtemperature trigger is reached instead of switching off all poles, so the trigger value must be set to match the process.

Unichiller Operation Manual, Operation and Safety
Maintenance
Refrigerant work only by approved contractors

Any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors; the R-290 charge of 0.16 kg and the A3 classification require qualified handling and are not user-serviceable.

Unichiller Operation Manual, Maintenance

Selection & Integration Q&A

When should I choose the 022w OLÉ instead of the 015 OLÉ or 015-H OLÉ?

Pick the 022w OLÉ for the lowest noise in the series (60 dB(A) vs 63 dB(A) on all 015 variants) and for water cooling with the OLÉ controller. The 015-H models add a heater; the 015 base models differ in cooling capacity. Confirm your heat load and required flow temperature before deciding.

What cooling-water supply and piping must be provided for this chiller?

Provide cooling water at 5–20 °C intake with 1 bar minimum differential pressure and 6 bar maximum, connected via G1/2 male fittings. Consumption is 77–96 l/h depending on flow temperature. Use water compatible with copper, stainless 1.4401, MS, PA, PPE, PTFE and EPDM to avoid corrosion.

Where can the unit be installed and what ambient conditions apply?

Indoors only, at 5–40 °C ambient, at least 300 lx illuminance and up to 2000 m altitude. It is IP20 and not explosion-protected, so no ATEX zone. Leave 50–200 cm clearance per side for maintenance and check room volume against the 0.16 kg R-290 charge.

What is not included in base delivery and what maintenance/accessories should be planned?

The Pt100 sensor connection for process temperature display is factory-fitted only and must be ordered with the unit. Matching G3/4 male pump and G1/2 male cooling-water hose couplings are not supplied. Refrigerant-circuit service requires approved contractors; plan cooling-water shutoff for every downtime.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 022w OLÉ Technical Data
Datasheet ·86,9 КБ ·2 pp.
View PDF