Peter Huber Kältemaschinenbau Unichiller 025w
Peter Huber Kältemaschinenbau Unichiller 025w — Recirculating chillers with Noise level 60 dB.
The Unichiller 025w is a water-cooled recirculating chiller with a 2 kW cooling capacity at 0 °C and a -10…40 °C working range, controlled by the Pilot ONE. It is the quietest of the listed Unichiller models at 60 dB(A), compared with 63 dB(A) for the 015 variants, and uses a 220–240 V 1~ 50 Hz supply. It serves externally closed process loops requiring stable cooling with G3/4 pump and G1/2 cooling-water connections.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller 025w Current | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 60 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | Yes |
| Pump type | Immersion pump |
| Temperature range | -10...40 °C |
| Weight | 59 kg |
| Power supply | 220-240V 1~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Cooling capacity | 2 kW (at 0 °C) |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 72 l/h (at 15°C, flow -10°C) at 15°C, flow 0°C: 84 l/h · at 15°C, flow 15°C: 84 l/h |
| Cooling water differential pressure | 1 bar (min.) |
| Cooling Water Pressure | 6 bar (max.) |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
The Unichiller 025w is a water-cooled recirculating chiller built for externally closed applications only. Within the Unichiller series, it is the quietest of the listed siblings at 60 dB(A), compared with 63 dB(A) for the 015 variants. It uses an immersion pump with adjustable speed and G3/4 AG male pump connections; the cooling-water circuit connects via G1/2 male fittings. The refrigerant is R-449A (safety group A1, GHS H280) with a 0.4 kg charge corresponding to 0.6 t CO2 equivalent. The unit weighs 59 kg and is rated IP20, safety class I / NFL.
Behavior under load and media
Cooling capacity is specified as 2 kW at 0 °C. Cooling-water consumption is 84 l/h at 15 °C cooling-water inlet with 0 °C flow, 84 l/h at 15 °C with 15 °C flow, and 72 l/h at 15 °C with -10 °C flow. The cooling-water circuit requires a minimum differential pressure of 1 bar and tolerates a maximum pressure of 6 bar. The datasheet notes that as cooling-water temperature rises, cooling power drops and cooling-water flow rate may increase. The wetted cooling-water circuit includes copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible water quality may be used. The plastic pump is not resistant to acetone or polyglycols (depending on manufacturer); for freeze protection, water should be mixed with glysantine or ethylene glycol. The unit has a minimum filling capacity of 3.8 l and an expansion volume of 1.7 l.
Installation, control and operation
The Pilot ONE controller provides Ethernet, USB (Host and Device) and RS232 interfaces. Power-failure response is configurable as OFF/Standby, ON, or Power Failure Auto. Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached, rather than switching off all poles. The unit must not be installed in an ATEX zone. It is for indoor use only, at illuminance of at least 300 lx and up to 2000 m altitude. A wall clearance of 50 to 200 cm per side is required for maintenance on free-standing models. Leveling feet must be activated and parking brakes applied before startup. Cooling water supply must be shut off even for short downtimes such as overnight. Electrical lines directly below a water-cooled unit must be protected against liquid ingress. The unit is EMC classified Class A, Group 1 per EN55011. Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed. Single/two-phase devices are supplied with a power cable and country-specific plug, which must be specified when ordering.
Integration & Operating Notes
Free-standing models require a wall clearance of 50 to 200 cm on either side to allow maintenance access. Plan the installation footprint accordingly, and ensure the unit is placed indoors at an illuminance of at least 300 lx and below 2000 m altitude.
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and combinations such as -5% voltage with +2% frequency are not allowed. Check site power quality against these limits before installation to avoid malfunction or damage.
The cooling water supply must be shut off even for shorter downtimes such as overnight to prevent water damage and corrosion during idle periods. This is a mandatory operational step, not an optional measure.
In Process Safety mode, the controller releases maximum cooling capacity when the overtemperature protection trigger value is reached, instead of switching off all poles. This is critical for exothermic processes where cutting cooling would cause runaway temperatures.
Work on the refrigerant circuit must only be performed by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A (A1, H280) with a 0.4 kg charge; handling and service must follow applicable regulations.
Selection & Integration Q&A
Choose the 025w when you need 2 kW cooling at 0 °C and lower noise (60 dB(A) vs 63 dB(A) for 015 variants). The 015 models are smaller-capacity siblings; select them only if their capacity meets your load. The 025w is the quietest listed model and uses a 220–240 V 1~ 50 Hz supply.
The cooling water must be 5–20 °C with at least 1 bar differential pressure (max 6 bar). Connections are G1/2 male. Consumption is 84 l/h at 15 °C inlet with 0 °C flow, and 72 l/h with -10 °C flow. Insulate pipes if below condensation point.
Install indoors only, at ≥300 lx illuminance and ≤2000 m altitude. Not for ATEX zones. Maintain 50–200 cm side clearance for maintenance. Activate leveling feet and parking brakes before startup. Protect electrical lines below the unit from condensate.
Refrigerant circuit work requires certified contractors. Shut off cooling water for even short downtimes. The base delivery includes a power cable with country-specific plug (must be specified). Heat transfer fluid is not included; use water with glysantine or ethylene glycol for freeze protection. Minimum filling capacity is 3.8 l.