Peter Huber Kältemaschinenbau Unichiller 025w
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 025w

Peter Huber Kältemaschinenbau Unichiller 025w — Recirculating chillers with Noise level 60 dB.

The Unichiller 025w is a water-cooled recirculating chiller with a 2 kW cooling capacity at 0 °C and a -10…40 °C working range, controlled by the Pilot ONE. It is the quietest of the listed Unichiller models at 60 dB(A), compared with 63 dB(A) for the 015 variants, and uses a 220–240 V 1~ 50 Hz supply. It serves externally closed process loops requiring stable cooling with G3/4 pump and G1/2 cooling-water connections.

Noise level
60 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller 025w Current 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 60 dB(A)
Pump connection G3/4 AG male
Pump speed adjustable Yes
Pump type Immersion pump
Temperature range -10...40 °C
Dimensions, Weight & Mechanical Design
Weight 59 kg
Electrical, Power & Drive Specifications
Power supply 220-240V 1~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling capacity 2 kW (at 0 °C)
Cooling water connection G1/2 male
Cooling water consumption 72 l/h (at 15°C, flow -10°C)
at 15°C, flow 0°C: 84 l/h · at 15°C, flow 15°C: 84 l/h
Cooling water differential pressure 1 bar (min.)
Cooling Water Pressure 6 bar (max.)
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

The Unichiller 025w is a water-cooled recirculating chiller built for externally closed applications only. Within the Unichiller series, it is the quietest of the listed siblings at 60 dB(A), compared with 63 dB(A) for the 015 variants. It uses an immersion pump with adjustable speed and G3/4 AG male pump connections; the cooling-water circuit connects via G1/2 male fittings. The refrigerant is R-449A (safety group A1, GHS H280) with a 0.4 kg charge corresponding to 0.6 t CO2 equivalent. The unit weighs 59 kg and is rated IP20, safety class I / NFL.

Behavior under load and media

Cooling capacity is specified as 2 kW at 0 °C. Cooling-water consumption is 84 l/h at 15 °C cooling-water inlet with 0 °C flow, 84 l/h at 15 °C with 15 °C flow, and 72 l/h at 15 °C with -10 °C flow. The cooling-water circuit requires a minimum differential pressure of 1 bar and tolerates a maximum pressure of 6 bar. The datasheet notes that as cooling-water temperature rises, cooling power drops and cooling-water flow rate may increase. The wetted cooling-water circuit includes copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible water quality may be used. The plastic pump is not resistant to acetone or polyglycols (depending on manufacturer); for freeze protection, water should be mixed with glysantine or ethylene glycol. The unit has a minimum filling capacity of 3.8 l and an expansion volume of 1.7 l.

Installation, control and operation

The Pilot ONE controller provides Ethernet, USB (Host and Device) and RS232 interfaces. Power-failure response is configurable as OFF/Standby, ON, or Power Failure Auto. Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached, rather than switching off all poles. The unit must not be installed in an ATEX zone. It is for indoor use only, at illuminance of at least 300 lx and up to 2000 m altitude. A wall clearance of 50 to 200 cm per side is required for maintenance on free-standing models. Leveling feet must be activated and parking brakes applied before startup. Cooling water supply must be shut off even for short downtimes such as overnight. Electrical lines directly below a water-cooled unit must be protected against liquid ingress. The unit is EMC classified Class A, Group 1 per EN55011. Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed. Single/two-phase devices are supplied with a power cable and country-specific plug, which must be specified when ordering.

Integration & Operating Notes

Mounting
Maintain 50–200 cm side clearance for maintenance access

Free-standing models require a wall clearance of 50 to 200 cm on either side to allow maintenance access. Plan the installation footprint accordingly, and ensure the unit is placed indoors at an illuminance of at least 300 lx and below 2000 m altitude.

Unichiller Operation Manual, Section: Installation (page 25
Electrical
Voltage and frequency tolerances are interdependent

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and combinations such as -5% voltage with +2% frequency are not allowed. Check site power quality against these limits before installation to avoid malfunction or damage.

Unichiller 025w Technical Data, page 2
Operation
Shut off cooling water even for overnight downtime

The cooling water supply must be shut off even for shorter downtimes such as overnight to prevent water damage and corrosion during idle periods. This is a mandatory operational step, not an optional measure.

Unichiller Operation Manual, Section: Operation (page 28
Safety
Process Safety mode releases max cooling on OT trigger

In Process Safety mode, the controller releases maximum cooling capacity when the overtemperature protection trigger value is reached, instead of switching off all poles. This is critical for exothermic processes where cutting cooling would cause runaway temperatures.

Unichiller Operation Manual, Section: Safety (page 18
Maintenance
Refrigerant circuit work requires certified contractors

Work on the refrigerant circuit must only be performed by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A (A1, H280) with a 0.4 kg charge; handling and service must follow applicable regulations.

Unichiller Operation Manual, Section: Maintenance (page 17

Selection & Integration Q&A

When should I choose the Unichiller 025w over the 015 siblings?

Choose the 025w when you need 2 kW cooling at 0 °C and lower noise (60 dB(A) vs 63 dB(A) for 015 variants). The 015 models are smaller-capacity siblings; select them only if their capacity meets your load. The 025w is the quietest listed model and uses a 220–240 V 1~ 50 Hz supply.

What are the requirements for the cooling water supply and connections?

The cooling water must be 5–20 °C with at least 1 bar differential pressure (max 6 bar). Connections are G1/2 male. Consumption is 84 l/h at 15 °C inlet with 0 °C flow, and 72 l/h with -10 °C flow. Insulate pipes if below condensation point.

What are the mounting and environmental limits for the Unichiller 025w?

Install indoors only, at ≥300 lx illuminance and ≤2000 m altitude. Not for ATEX zones. Maintain 50–200 cm side clearance for maintenance. Activate leveling feet and parking brakes before startup. Protect electrical lines below the unit from condensate.

What maintenance and accessories are required, and what is not included?

Refrigerant circuit work requires certified contractors. Shut off cooling water for even short downtimes. The base delivery includes a power cable with country-specific plug (must be specified). Heat transfer fluid is not included; use water with glysantine or ethylene glycol for freeze protection. Minimum filling capacity is 3.8 l.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 025w Technical Data
Datasheet ·18,4 КБ ·2 pp.
View PDF