Peter Huber Kältemaschinenbau Unichiller 025w-H OLÉ
Peter Huber Kältemaschinenbau Unichiller 025w-H OLÉ — Recirculating chillers with Noise level 60 dB.
The Unichiller 025w-H OLÉ is a water-cooled recirculating chiller with an immersion pump and OLÉ controller, rated 2 kW cooling at 0 °C over a -10…100 °C range. It is the 025w-H variant of the Unichiller series, distinguished by water cooling and the OLÉ interface rather than the air-cooled 015 siblings. It serves externally closed process loops requiring sub-ambient to moderate heating duty.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller 025w-H OLÉ Current | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 60 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | Immersion pump |
| Temperature range | -10...100 °C |
| Weight | 63 kg |
| Current consumption | 15 A (max.) |
| Fuse rating | 16 A |
| Power supply | 220-240V 1~ 50Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Cooling capacity | 2 kW (at 0 °C) |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 72 л/час (at 15°C, flow -10°C) at 15°C, flow 0°C: 84 l/h · at 15°C, flow 15°C: 84 l/h |
| Cooling water differential pressure | 1 bar (min.) |
| Cooling Water Pressure | 6 bar (max.) |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- The 025w-H OLÉ is a water-cooled (w) recirculating chiller with an immersion pump (non-adjustable speed) and the OLÉ controller; it is intended for externally closed applications only.
- Within the Unichiller series, the 015 siblings are air-cooled and rated 63 dB(A); this 025w-H model is water-cooled and rated 60 dB(A), so the cooling-water circuit replaces the air-cooled condenser.
- The pump delivers 21 l/min at 0.5 bar, up to 29 l/min maximum, with 1 bar maximum delivery pressure; pump connection is G3/4 AG male.
Behavior under load and media
- Cooling capacity is 2.5 kW at 15 °C, 2 kW at 0 °C and 1.2 kW at -10 °C, so capacity must be checked against the actual process load at the target temperature.
- Cooling-water consumption is 84 l/h at 15 °C flow with 15 °C or 0 °C outlet, and 72 l/h at 15 °C flow with -10 °C outlet; minimum differential pressure is 1 bar, maximum supply pressure 6 bar at the G1/2 male connection.
- The plastic pump is not resistant to acetone or polyglycols; for freeze protection, mix water with glysantine or ethylene glycol.
Installation, control and operation
- Electrical supply is 220–240 V 1~ 50 Hz, 15 A maximum current, 16 A fuse; voltage tolerance ±5% only with simultaneous ±2% frequency tolerance, and opposite-sign deviations are not allowed.
- Interfaces are USB (Device) and RS232; the OLED display has 0.1 K resolution; power-failure response is configurable as OFF/Standby, ON, or Power Failure Auto.
- Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles.
- The unit is IP20, for indoor use only, at 5…40 °C ambient and at least 300 lx illuminance; wall clearance of 50–200 cm per side is required for maintenance.
Integration & Operating Notes
The unit is designed for externally closed applications, so the hydraulic circuit must be a sealed loop; open-tank or atmospheric operation is outside the intended use and may cause pump cavitation or overflow.
Supply water must stay between 5 °C and 20 °C inlet, with at least 1 bar differential pressure and no more than 6 bar supply pressure; insulate pipes if condensation forms, and protect electrical lines below the unit from condensate.
Voltage tolerance is ±5% only when frequency tolerance is simultaneously ±2%; a -5% voltage with +2% frequency is explicitly not allowed, so verify the site supply quality before connection to avoid compressor or electronics damage.
Before switching on, unscrew/activate the leveling feet and apply caster parking brakes so the unit cannot move; also maintain 50–200 cm wall clearance per side for maintenance access and install only indoors at ≥300 lx.
Any work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors; the refrigerant is R-449A (A1, H280) with 0.4 kg charge (0.6 t CO2 equivalent), so F-gas reporting and leak handling apply.
Close the cooling-water supply for any downtime, including overnight, to prevent water damage and corrosion in the water circuit; the circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible water quality should be used.
The power-failure response can be set to OFF/Standby, ON, or Power Failure Auto via the Pilot ONE; choose OFF/Standby where automatic restart after a mains outage would be unsafe for the process or the operator.
In Process Safety mode, reaching the overtemperature trigger value releases maximum cooling capacity instead of switching off all poles; this is relevant for exothermic processes where cutting cooling would cause runaway temperatures.
Selection & Integration Q&A
Choose the 025w-H OLÉ when a water supply is available and 2 kW at 0 °C is needed; the 015 siblings are air-cooled and rated 63 dB(A). The water-cooled 025w-H is rated 60 dB(A) and requires 1–6 bar cooling water at G1/2.
Provide 5–20 °C water at the G1/2 male connection with at least 1 bar differential pressure and no more than 6 bar supply pressure; consumption is 84 l/h at 15 °C flow (72 l/h at -10 °C outlet). Insulate pipes if condensation occurs.
Install indoors only, at 5–40 °C ambient and ≥300 lx, with 50–200 cm wall clearance per side; activate leveling feet and parking brakes before start. The unit is IP20 and not explosion-protected, so it must not be placed in an ATEX zone.
Refrigerant-circuit work must be done by approved contractors; the R-449A charge is 0.4 kg (0.6 t CO2 equivalent). For freeze protection, mix water with glysantine or ethylene glycol; the plastic pump is not resistant to acetone or polyglycols. Minimum filling is 3.8 l.