Peter Huber Kältemaschinenbau Unichiller P007
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P007

Peter Huber Kältemaschinenbau Unichiller P007 — Recirculating chillers with Noise level 58 dB.

The Unichiller P007 is a recirculating chiller with a plastic pump (type B) and Pilot ONE controller, rated -20 to 40 °C and 0.7 kW at 15 °C. Its 'P' designation targets high-pressure-drop circuits, delivering up to 25 l/min at 2.5 bar through G3/4 male connections. It serves externally closed cooling loops requiring sub-ambient control.

Noise level
58 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller P007 Current 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 58 dB(A)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
External sensor connection Pt100
Temperature range -20...40 °C
Dimensions, Weight & Mechanical Design
Weight 56 kg
Electrical, Power & Drive Specifications
Current consumption 5 A
Fuse rating 16 A
Power supply 208-240V 1~/2~ 50/60Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior under load

Installation, control and operation

Integration & Operating Notes

Process Limits
Size cooling capacity at the actual set point, not nominal

Capacity falls from 0.7 kW at 15 °C to 0.2 kW at -20 °C. A load calculated at nominal rating will be undercooled at low set points; verify the heat load against the capacity at the intended process temperature before selection.

Unichiller P007 Technical Datasheet, page 1
Process Limits
Match external circuit pressure drop to the fixed pump curve

The pump delivers 25 l/min at free flow but only 6 l/min at 2.0 bar. Because pump speed is not adjustable, a high-impedance loop will starve flow; calculate the loop pressure drop and confirm the operating point lies on the published curve.

Unichiller P007 Technical Datasheet, page 1
Cooling & Media
Avoid acetone and polyglycols with the plastic pump

The type B plastic pump is not resistant to acetone or polyglycols (depending on manufacturer). For sub-zero operation use water mixed with glysantine or ethylene glycol; incompatible fluids risk pump failure and leakage.

Unichiller P007 Technical Datasheet, page 2
Mounting
Keep 50–200 cm clearance per side and lock the casters

Free-standing installation requires 50 to 200 cm wall clearance on either side for maintenance access. Before start-up, activate parking brakes and/or unscrew leveling feet so the unit cannot move during operation.

Unichiller Operation Manual, pages 25 and 31
Mounting
R-290 charge limits the permissible room size

The refrigerant is R-290 (A3, H220), flammable. At installation, check the charge on the rating plate against the room volume so the refrigerant limit per m³ of ambient air is not exceeded; the unit must not be installed in an ATEX zone.

Unichiller P007 Technical Datasheet, page 1; Unichiller Operation Manual, pages 13 and 15
Electrical
Specify the country-specific plug at ordering

Single/two-phase units (100–240 V) are supplied with a power cable and country-specific plug that must be stated on the order. Supply tolerance is ±5% voltage with simultaneous ±2% frequency; certain combinations are not permitted.

Unichiller P007 Technical Datasheet, page 2
Control & I/O
Choose power-failure response before commissioning

The Pilot ONE can be set to OFF/Standby, ON, or Power Failure Auto after mains loss. For exothermic processes, Process Safety mode releases maximum cooling at the OT trigger rather than switching off all poles; select the behavior that matches the process risk.

Unichiller Operation Manual, pages 18–19
Maintenance
Refrigerant circuit work requires certified contractors

Any work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. Plan service access accordingly and do not attempt refrigerant-side maintenance with in-house staff.

Unichiller Operation Manual, page 17

Selection & Integration Q&A

When should I choose the P007 instead of the larger Unichiller 015 siblings?

Pick the P007 for high-pressure-drop loops and compact footprints: 0.7 kW at 15 °C, 25 l/min at 2.5 bar, 58 dB(A), 56 kg. The 015 family is larger and louder (63 dB(A)); choose it only when its higher capacity is required.

What must the external hydraulic circuit provide to mate with the P007?

G3/4 male pump connections with mating hoses rated for 2.5 bar; loop pressure drop must leave flow on the pump curve (6 l/min at 2.0 bar). Minimum filling 3.8 l plus 1.7 l expansion; use glycol-mixed water below 0 °C, never acetone or polyglycols.

What site conditions and duty limits apply to installing the P007?

Indoors only, 5–40 °C ambient, ≥300 lx, up to 2000 m altitude, IP20 dry location, 50–200 cm side clearance, casters locked. Not for ATEX zones; R-290 charge must suit the room volume. Shut off cooling water even overnight.

What is not included in base delivery and what service does the unit need?

The country-specific plug must be specified at ordering; hoses, fittings and heat-transfer fluid are not part of the base unit. Refrigerant-circuit service is restricted to approved contractors; plan access per the 50–200 cm clearance requirement.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P007 Technical Datasheet
Datasheet ·129,2 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF