Peter Huber Kältemaschinenbau Unichiller P015-H OLÉ
Peter Huber Kältemaschinenbau Unichiller P015-H OLÉ — Recirculating chillers with Noise level 63 dB.
The Unichiller P015-H OLÉ is an air-cooled, single-phase recirculating chiller with a 'P' designation for high-pressure-drop process loops, rated -20 to 100 °C with cooling capacity falling from 1.5 kW at 15 °C to 0.3 kW at -20 °C. It is the OLÉ-controller variant of the 015-H platform, distinguished from the Pilot ONE siblings by its OLED/OLÉ control interface and USB/RS232 connectivity.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P015-H OLÉ Current | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 63 dB(A) (sound pressure level) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| Temperature range | -20...100 °C |
| Weight | 65 kg (net) |
| Current consumption | 15 A (max) |
| Fuse rating | 16 A |
| Power supply | 220-240V 1~ 50Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C (permissible) |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- Air-cooled refrigeration circuit using R-449A (A1, H280); no cooling-water connection is required.
- The 'P' in the model code marks this unit as particularly suitable for applications requiring high pressure drops, per the operation manual.
- Within the 015-H family, this is the OLÉ-controller version; the Unichiller 015, 015-H and 015 OLÉ siblings share the same 63 dB(A) sound pressure level but differ in controller and/or hydraulic configuration.
- Pump type B with G3/4 AG male connections; pump speed is not adjustable.
- Net weight 65 kg; IP20 protection; safety class III / FL.
Thermal behavior under load
- Operating range -20 to 100 °C, display resolution 0.1 K on the OLED display.
- Cooling capacity is strongly temperature-dependent: 1.5 kW at 15 °C, 1.0 kW at 0 °C, 0.7 kW at -10 °C and 0.3 kW at -20 °C. Low-temperature duty therefore requires careful heat-load sizing.
- Pump curve: 21 l/min at 0.5 bar, 17 l/min at 1.0 bar, 11 l/min at 1.5 bar and 6 l/min at 2.0 bar — external circuit pressure drop must be checked against this curve.
- Minimum filling capacity 3.8 l with a 1.7 l expansion tank.
Installation, control and operation
- Supply: 220–240 V 1~ 50 Hz, max. current 15 A, 16 A fuse; voltage tolerance ±5% with simultaneous frequency tolerance ±2%, not to be combined in opposite directions.
- Single-phase units ship with a power cable and country-specific plug, which must be specified at order.
- Interfaces: USB (Device) and RS232; controller OLÉ with OLED display.
- Autostart for power failure is available; the power-failure response is configurable (OFF/Standby, ON, Power Failure Auto).
- EMC classification Class A, Group 1 to EN55011 — intended for industrial environments and may cause radio interference in residential areas.
- The unit is designed for externally closed applications only and must not be installed in an ATEX zone.
Integration & Operating Notes
Cooling capacity falls to 0.3 kW at -20 °C versus 1.5 kW at 15 °C, so a process sized at mid-range temperatures will be undersized at cold set points; verify the actual heat load at the intended set point before selection.
The unit is designed only for externally closed applications, and the pump delivers 21 l/min at 0.5 bar but only 6 l/min at 2.0 bar; the process loop's pressure drop must be matched to this curve to avoid insufficient flow.
Single-phase devices are supplied with a power cable and a country-specific plug; the plug type must be stated when ordering, otherwise commissioning may be delayed by a missing or wrong connector.
The chiller is air-cooled and requires sufficient space for airflow and service access; the manual specifies a wall clearance of 50 to 200 cm per side for maintenance, indoor use only, illuminance at least 300 lx and site altitude up to 2000 m.
Parking brakes at the casters must be activated and/or leveling feet unscrewed/activated before the unit is put into operation, to prevent the unit from moving and causing crushing injuries during operation.
The unit is not explosion-protected and must not be installed or started up inside an ATEX zone; site hazardous-area classification must be checked before installation.
The power-failure response can be set to OFF/Standby, ON or Power Failure Auto via the controller; for exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles.
Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors; the refrigerant is R-449A (A1, H280), so leak and ventilation precautions apply and refrigerant charge versus room size must be checked at installation.
A drain valve (item #6839) is optional, so draining for service or fluid change requires ordering it separately; plan fluid replacement procedures accordingly.
Selection & Integration Q&A
Choose the P015-H OLÉ when the process loop has high pressure drop (the 'P' designation) and the OLÉ controller with USB/RS232 is required. The 015-H uses the Pilot ONE controller; the 015 OLÉ lacks the high-pressure-drop pump configuration.
Confirm the loop is externally closed and its pressure drop matches the pump curve (21 l/min at 0.5 bar down to 6 l/min at 2.0 bar), and provide 220–240 V 1~ 50 Hz with a 16 A fuse, respecting ±5% voltage / ±2% frequency tolerances not combined in opposite directions.
Install indoors only, 5–40 °C ambient, illuminance ≥300 lx, altitude ≤2000 m, with 50–200 cm wall clearance per side for airflow and service. Activate leveling feet/parking brakes before start-up; the unit is not ATEX-rated.
The drain valve (#6839) is optional and must be ordered separately; the country-specific plug must be specified at order. Refrigerant-circuit work requires approved contractors, and the R-449A charge versus room size must be checked at installation.