Peter Huber Kältemaschinenbau Unichiller 015w-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 015w-H

Peter Huber Kältemaschinenbau Unichiller 015w-H — Recirculating chillers with Noise level 54 dB.

The Unichiller 015w-H is a water-cooled recirculating chiller with a 1 kW cooling capacity at 0 °C and a -20…100 °C temperature range, controlled by the Pilot ONE. Its 'w' designation indicates water cooling, distinguishing it from air-cooled siblings in the 015 series. It serves externally closed process loops requiring precise temperature control with facility cooling water.

Noise level
54 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller 015w-H Current 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 54 dB(A)
Pump connection G3/4 AG male
Pump speed adjustable Yes
Pump type Immersion pump
External sensor connection Pt100
Temperature range -20...100 °C
Dimensions, Weight & Mechanical Design
Weight 57 kg
Electrical, Power & Drive Specifications
Current consumption 13 A
Fuse rating 16 A
Power supply 220-240V 1~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling capacity 1 kW (at 0 °C)
Cooling water connection G1/2 male
Cooling water consumption 36 l/h (cooling water at 15 °C, flow -20 °C)
cooling water at 15 °C, flow -10 °C: 48 l/h · cooling water at 15 °C, flow 0 °C: 60 l/h · cooling water at 15 °C, flow 15 °C: 68 l/h
Cooling water differential pressure 1 bar
Cooling Water Pressure 6 bar
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and Series Positioning

The Unichiller 015w-H is a water-cooled recirculating chiller in the Unichiller 015 series. Unlike the air-cooled Unichiller 015, 015-H, and OLÉ variants, this model uses a facility cooling water circuit for heat rejection, which reduces noise emission to 54 dB(A) compared with 63 dB(A) for the air-cooled siblings. The unit is built for externally closed applications only and is not explosion-protected, so it must not be installed in ATEX zones. The refrigerant circuit contains R-449A (GWP 1397, charge 0.25 kg, 0.3 t CO2 equivalent).

Hydraulic and Thermal Behavior

The immersion pump delivers a maximum of 29 l/min at 1 bar maximum delivery pressure, with 21 l/min available at 0.5 bar. The minimum filling capacity is 3.8 l, and the expansion vessel volume is 1.7 l. Cooling water consumption depends on the required flow temperature: 60 l/h at 0 °C, 68 l/h at 15 °C, 48 l/h at -10 °C, and 36 l/h at -20 °C, all with cooling water at 15 °C. The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, so only compatible water quality may be used. The plastic pump is not resistant to acetone or polyglycols; a more resistant pump is available at extra cost. For freeze protection below 0 °C, water should be mixed with glysantine or ethylene glycol.

Installation, Control, and Operation

The unit requires a 220-240V 1~ 50Hz supply with a maximum current of 13 A and a 16 A fuse. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed. The Pilot ONE controller provides Ethernet, USB (Host and Device), and RS232 interfaces, and supports a Pt100 external sensor. The power-failure response is configurable as OFF/Standby, ON, or Power Failure Auto. Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached, rather than switching off all poles. The unit has IP20 protection and must be installed indoors at 5…40 °C ambient temperature with at least 300 lx illuminance and up to 2000 m altitude. A wall clearance of 50 to 200 cm per side is required for maintenance. Leveling feet must be activated and parking brakes applied before startup. Cooling water supply must be shut off even for short downtimes such as overnight.

Integration & Operating Notes

Process Limits
Cooling water pressure must stay between 1 and 6 bar differential

The facility cooling water supply must provide a differential pressure of at least 1 bar and must never exceed 6 bar. Insufficient pressure prevents proper heat rejection; excessive pressure can damage the cooling water circuit. Verify the site supply before installation.

Datasheet, Technical Specifications
Mounting
Maintain 50–200 cm wall clearance per side for maintenance access

Free-standing models require a wall clearance of 50 to 200 cm on either side to allow maintenance access. The unit must be installed indoors at 5…40 °C ambient temperature with at least 300 lx illuminance and up to 2000 m altitude. Leveling feet must be unscrewed/activated and parking brakes applied before switching on.

Operation Manual, Installation
Process Limits
Plastic pump is not resistant to acetone or polyglycols

The standard plastic pump is not resistant to acetone or polyglycols (depending on the manufacturer). These media must be avoided, or a more resistant plastic pump ordered at extra cost. The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, so only suitable cooling water may be used.

Datasheet, Technical Specifications
Operation
Shut off cooling water supply even for overnight downtimes

The cooling water supply must be shut off even for short downtimes such as overnight to prevent water damage and corrosion during idle periods. Electrical lines directly below a water-cooled unit must be protected against liquid ingress from condensation.

Operation Manual, Installation

Selection & Integration Q&A

When should I choose the Unichiller 015w-H over the air-cooled Unichiller 015 or 015-H?

Choose the 015w-H when facility cooling water is available and lower noise (54 dB(A) vs 63 dB(A)) is required. Air-cooled siblings are preferable if cooling water is unavailable or if water consumption and connection costs are prohibitive.

What are the requirements for the cooling water supply and the process loop connections?

Cooling water: differential pressure 1–6 bar, intake temperature 5–20 °C, connection G1/2 male. Process loop: pump connection G3/4 AG male, max delivery pressure 1 bar, min filling volume 3.8 l. Ensure external circuit pressure drop allows at least 21 l/min at 0.5 bar.

What ambient and installation limits apply to the Unichiller 015w-H?

Install indoors at 5–40 °C ambient, max 2000 m altitude, illuminance ≥300 lx. Maintain 50–200 cm wall clearance per side. IP20 protection; protect electrical lines below unit from condensation. Not for ATEX zones. Leveling feet and parking brakes must be set before operation.

What maintenance and service items are required, and what is not included in the base delivery?

Refrigerant circuit work only by approved contractors. Cooling water must be shut off for downtimes. Base delivery excludes heat transfer fluid, freeze-protection additives (glysantine/ethylene glycol), and external Pt100 sensor. A more resistant plastic pump for acetone/polyglycols is optional at extra cost.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 015w-H Recirculating Chiller Datasheet
Datasheet ·126,5 КБ ·2 pp.