Peter Huber Kältemaschinenbau Unichiller 020T
Peter Huber Kältemaschinenbau Unichiller 020T — Recirculating chillers.
The Unichiller 020T is an air-cooled, externally closed recirculating chiller rated -20 to 40 °C, with 2 kW cooling at 0 °C falling to 0.8 kW at -20 °C. It is the 020T modification of the Unichiller series, distinguished by its 25 l/min non-adjustable pump and G3/4 male connections. It serves as the cooling source for closed process loops within its capacity envelope.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller 020T Current | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Expansion volume | 2 l |
| Maximum delivery flow rate | 25 l/min (pressure pump max; also 3 bar) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Weight | 143 kg |
| Current consumption | 13 A (max) |
| Fuse rating | 16 A |
| Power supply | 230V 1~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C (permissible ambient temperature) |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
The 020T is a free-standing, air-cooled recirculating chiller with a 143 kg cabinet, IP20 protection, and a Pilot ONE controller. Within the Unichiller series it sits alongside the 015 variants (015, 015-H, 015-H OLÉ, 015 OLÉ), which share a 63 dB(A) noise figure; the 020T is the larger-capacity modification in this fact set. It is intended only for externally closed applications; open tanks are not suitable. The pump is a non-adjustable type B unit with G3/4 male connections, delivering up to 25 l/min and 5 l/min at 3 bar.
Thermal behavior and media
Cooling capacity is quoted at 20 °C room temperature: 2 kW at 0 °C and 0.8 kW at -20 °C, so low-temperature duty requires either reduced heat load or a larger unit. Capacity falls as ambient temperature rises above 20 °C. The refrigerant is R-449A (GWP 1397, charge 1.2 kg, 1.7 t CO2 equivalent). Minimum filling capacity is 2.5 l with 2 l expansion volume. The unit is classified to DIN 12876 with NFL/FL identification depending on whether the thermal fluid is combustible.
Installation, control and operation
The unit requires a 230 V 1~ 50 Hz supply, 16 A fuse, and draws up to 13 A; voltage tolerance ±5% and frequency ±2% must not be combined in opposite directions. It is Class A, Group 1 to EN55011. Interfaces include Ethernet, USB host/device, RS232, and an external Pt100 sensor connection. The Pilot ONE allows configuration of the power-failure response (OFF/Standby, ON, Power Failure Auto) and a Process Safety mode that releases maximum cooling when the overtemperature trigger is reached. Installation requires 50–200 cm wall clearance per side, indoor use at ≥300 lx and up to 2000 m altitude, and no ATEX zone. Leveling feet or parking brakes must be set before start-up.
Integration & Operating Notes
The hydraulic circuit must be externally closed. An open tank or unsealed reservoir will not match the unit's design and can cause overflow, air ingress, or incorrect expansion behavior. Verify the loop is sealed before commissioning.
Voltage tolerance is ±5% and frequency tolerance ±2%, but the datasheet forbids applying them simultaneously in opposite directions. Check the actual supply quality at the installation point; a 230 V/50 Hz nominal with high voltage and low frequency (or vice versa) is outside the permitted envelope.
Free-standing installation requires a wall clearance of 50 to 200 cm on either side for maintenance. Air-cooled units also reject heat to the room, so ambient temperature must stay between 5 and 40 °C and the room must be ventilated accordingly.
The unit is not explosion-protected and must not be installed or started inside an ATEX zone. It is for indoor use at illuminance ≥300 lx and altitude up to 2000 m. Refrigerant charge and room volume must be checked against the refrigerant limit per m³ of ambient air.
The pump delivers 25 l/min maximum and 5 l/min at 3 bar. The external circuit pressure drop must be checked against this curve; a high-drop loop will reduce flow below the required rate. Models with 'P' in the model name are specifically suited to high-pressure-drop applications, which the 020T is not designated as.
The Pilot ONE can be set to OFF/Standby, ON, or Power Failure Auto after a mains outage. For exothermic processes, Process Safety mode releases maximum cooling when the overtemperature trigger is reached instead of switching off all poles. Select the mode that matches the process risk before leaving the unit unattended.
Any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The unit contains R-449A (1.2 kg, 1.7 t CO2 equivalent), so leak reporting and environmental compliance obligations apply.
Maximum tightening torques for the G3/4 male pump connections must not be exceeded, and the connections must be counterheld during hose installation to avoid damaging the pump housing or creating leaks.
Selection & Integration Q&A
Choose the 020T when the required cooling capacity at the coldest operating point exceeds what the 015 variants provide; the 020T delivers 2 kW at 0 °C and 0.8 kW at -20 °C. The 015 variants share a 63 dB(A) noise figure, so if noise is the deciding factor, compare against that figure. The 020T is not designated for high-pressure-drop loops (no 'P' in the model name).
Refrigerant circuit work must be done by approved refrigeration contractors. The unit needs a minimum 2.5 l fill with 2 l expansion volume; heat-transfer fluid is not included. The country-specific plug must be specified at order. No maintenance interval is stated in the provided digests; consult the manual's Maintenance section.