Peter Huber Kältemaschinenbau Unichiller 025-H OLÉ
Peter Huber Kältemaschinenbau Unichiller 025-H OLÉ — Recirculating chillers with Noise level 64 dB.
The Unichiller 025-H OLÉ is an air-cooled recirculating chiller with an immersion pump and OLED controller, rated for -10 to 100 °C and 2.5 kW cooling at 15 °C. It is the 2.5 kW OLÉ variant of the Unichiller series, distinguished from the 015 siblings by higher capacity and 64 dB(A) noise. It serves externally closed process loops requiring stable temperature control.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller 025-H OLÉ Current | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 64 dB(A) |
| Maximum delivery flow rate | 29 l/min (1 bar) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | Immersion pump |
| Temperature range | -10...100 °C |
| Weight | 76 kg |
| Current consumption | 14 A |
| Fuse rating | 16 A |
| Power supply | 208-230V 1~/2~ 60Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- The Unichiller 025-H OLÉ is a free-standing recirculating chiller with an immersion pump (non-adjustable speed) and G3/4 AG male pump connections. It uses R-290 (A3, H220) refrigerant and is rated IP20, safety class III/FL.
- Within the Unichiller series, the 025-H OLÉ is the higher-capacity OLÉ-controlled variant: the 015 siblings share 63 dB(A) noise, while this model is rated 64 dB(A). The 'H' and 'OLÉ' suffixes denote the hydraulic/controller configuration; the 025 code is a size/volume code, not a rating.
- Cooling capacity is temperature-dependent: 2.5 kW at 15 °C, 2 kW at 0 °C and 1.2 kW at -10 °C, valid at 20 °C room temperature. Capacity drops as ambient rises.
Behavior and media
- Temperature range is -10 to 100 °C with 0.1 K display resolution on the OLED display. The unit is designed for externally closed applications only.
- The plastic immersion pump is not resistant to acetone or polyglycols; for freeze protection, water should be mixed with glysantine or ethylene glycol.
- Maximum delivery flow rate is 29 l/min at 1 bar; pump speed is not adjustable.
Installation, control and operation
- Electrical supply: 208-230 V 1~/2~ 60 Hz, 14 A max current, 16 A fuse. Voltage tolerance ±5% only with simultaneous frequency tolerance ±2%; -5% voltage with +2% frequency is not allowed. Single/two-phase devices are delivered with a power cable and country-specific plug (specify at ordering).
- Controller: OLÉ with OLED display; interfaces USB (Device) and RS232. Autostart function for power failure is available; power-failure response can be configured as OFF/Standby, ON, or Power Failure Auto via the Pilot ONE.
- Installation requires indoor use only, illuminance at least 300 lx, altitude up to 2000 m, ambient 5–40 °C, and wall clearance of 50–200 cm per side for maintenance on free-standing models. Leveling feet must be activated and parking brakes applied before operation. Cooling water supply must be shut off even for short downtimes.
- The unit must not be installed in an ATEX zone; refrigerant charge and room size must be checked against the refrigerant limit per m³. Electrical lines directly below a water-cooled unit must be protected against liquid ingress.
Integration & Operating Notes
Free-standing models require a wall clearance of 50 to 200 cm on either side to allow maintenance access and adequate air flow. Plan the installation footprint accordingly, and ensure the unit is indoors at illuminance of at least 300 lx and altitude up to 2000 m.
The unit accepts 208-230 V 1~/2~ 60 Hz with 14 A max current and a 16 A fuse. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%; combining -5% voltage with +2% frequency is not allowed. Size the breaker and cable for 16 A and specify the country-specific plug at ordering.
The unit is designed for externally closed applications. The plastic immersion pump is not resistant to acetone or polyglycols, so these fluids must not be used. For sub-zero operation, mix water with glysantine or ethylene glycol for freeze protection.
The controller supports OFF/Standby, ON, or Power Failure Auto after a power interruption. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles. Select the mode that matches the process risk.
Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. Shut off the cooling water supply even for short downtimes such as overnight to prevent water damage and corrosion.
Selection & Integration Q&A
Choose the 025-H OLÉ when you need 2.5 kW cooling at 15 °C and can accept 64 dB(A) noise; the 015 siblings offer lower capacity at 63 dB(A). Select the 025 for higher heat loads within the -10 to 100 °C range.
It requires 208-230 V 1~/2~ 60 Hz, 14 A max current, 16 A fuse. Voltage tolerance ±5% only with frequency ±2%; -5% voltage with +2% frequency is not allowed. A power cable and country-specific plug are supplied if specified at ordering.
Indoors only, 5–40 °C ambient, illuminance ≥300 lx, altitude ≤2000 m, IP20 dry location, 50–200 cm side clearance. Not for ATEX zones. Cooling capacity is valid at 20 °C room temperature and drops as ambient rises.
Refrigerant circuit work must be by approved contractors. Hoses/fittings must match G3/4 male pump connection. For sub-zero use, add glysantine or ethylene glycol. Cooling water supply must be shut off during downtimes. No cables beyond the power cord are included.