Peter Huber Kältemaschinenbau Unichiller P010-H OLÉ
Peter Huber Kältemaschinenbau Unichiller P010-H OLÉ — Recirculating chillers with Noise level 57 dB.
The Unichiller P010-H OLÉ is an air-cooled, CFC/HCFC-free recirculating chiller with a plastic pump (type B, non-adjustable) and G3/4 male connections, rated -20 to 100 °C. Its 'P' designation targets externally closed loops with high pressure drop, where the pump still delivers 6 l/min at 2.0 bar. It serves as a closed-circuit cooling source for process equipment requiring controlled coolant temperature.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P010-H OLÉ Current | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 57 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| Temperature range | -20...100 °C |
| Weight | 53 kg |
| Fuse rating | 16 A |
| Power supply | 220-240V 1~/2~ 50/60Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- Air-cooled refrigeration circuit, CFC- and HCFC-free, in a free-standing chassis (53 kg) with casters/leveling feet provisions.
- OLÉ controller with OLED display, 0.1 K resolution, USB (Device) and RS232 interfaces.
- Plastic circulation pump type B, fixed speed, G3/4 AG male pump connection.
- Within the Unichiller series, the 'P' in the model name marks this unit as particularly suitable for applications requiring high pressure drops; sibling Unichiller 015 variants (63 dB(A)) are the larger-frame alternatives, while this P010-H OLÉ is rated 57 dB(A).
Hydraulic and thermal behavior
- Operating range -20 to 100 °C; cooling capacity is strongly temperature-dependent: 1 kW at 15 °C, 0.8 kW at 0 °C, 0.5 kW at -10 °C and 0.15 kW at -20 °C, so cold-end duty requires derating or longer pull-down.
- Pump curve: 21 l/min at 0.5 bar, 17 l/min at 1.0 bar, 11 l/min at 1.5 bar, 6 l/min at 2.0 bar; maximum delivery 25 l/min at maximum delivery pressure 2.5 bar. High-pressure-drop circuits therefore see reduced flow.
- Minimum filling capacity 3.8 l; expansion tank 1.7 l.
- Output data are valid at 20 °C room temperature; cooling capacity may drop as ambient temperature rises.
Installation, control and operation
- Power supply 220-240 V 1~/2~ 50/60 Hz, max. current 14.5 A, 16 A fuse; voltage tolerance ±5% and frequency ±2%, but the combination of -5% voltage with +2% frequency is not allowed. Single/two-phase units ship with power cable and country-specific plug, to be specified at ordering.
- Protection IP20; ambient 5 to 40 °C; indoor use only, illuminance at least 300 lx, altitude up to 2000 m.
- Air-cooled condenser requires room ventilation and wall clearance of 50 to 200 cm per side for maintenance on free-standing models.
- Power-failure response configurable (OFF/Standby, ON, Power Failure Auto); Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached.
Integration & Operating Notes
Cooling capacity falls to 0.5 kW at -10 °C and only 0.15 kW at -20 °C, so processes needing sustained load near the lower limit must be sized with margin or accept long pull-down times; the 1 kW figure applies only at 15 °C.
The type B plastic pump is not resistant to acetone or polyglycols (depending on manufacturer), so these fluids must be avoided or a more resistant plastic specified; for sub-zero operation water should be mixed with glysantine or ethylene glycol for freeze protection.
Supply must stay within ±5% voltage and ±2% frequency, but the specific combination of -5% voltage and +2% frequency is explicitly not allowed; the circuit must also carry 14.5 A maximum with a 16 A fuse, and the country-specific plug must be stated at ordering.
Free-standing installation requires a wall clearance of 50 to 200 cm on either side for maintenance access, and the air-cooled condenser needs sufficient room ventilation; the unit is IP20 and must be used indoors at 5-40 °C ambient with at least 300 lx illuminance.
The unit is not explosion-protected and must not be installed or started up within an ATEX zone; refrigerant charge versus room size must also be checked against the limit per m³ of ambient air at the installation site.
The chiller is designed for externally closed applications, so open baths or circuits that expose the coolant to atmosphere are outside its intended use; the 'P' model designation additionally suits loops with high pressure drop, where flow falls to 6 l/min at 2.0 bar.
The power-failure response can be set to OFF/Standby, ON or Power Failure Auto via the controller; for exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached instead of switching off all poles.
Any work on the coolant/refrigerant circuit must be carried out by approved refrigeration and air-conditioning system contractors; the unit's DIN 12876 safety classification (III/FL) depends on whether the thermal fluid is combustible and is stated on the data sheet.
Selection & Integration Q&A
Pick the P010-H OLÉ for high-pressure-drop, externally closed loops: its 'P' designation suits such applications and it runs at 57 dB(A) versus 63 dB(A) for the 015 siblings. Choose a 015 variant when higher cooling capacity or a larger frame is needed.
The pump connection is G3/4 male, so hoses/fittings must be G3/4 female, counterheld and tightened to the manual's torque limits. The circuit must be externally closed, hold at least 3.8 l fill, and its pressure drop should be checked against the pump curve (6 l/min at 2.0 bar).
Indoors only, 5-40 °C ambient, IP20, at least 300 lx illuminance and up to 2000 m altitude; not in an ATEX zone. Allow 50-200 cm side clearance for maintenance, ensure room ventilation for the air-cooled condenser, and activate leveling feet/parking brakes before start-up.
Refrigerant-circuit service must be done by approved refrigeration contractors; the DIN 12876 safety class (III/FL) depends on the fluid chosen. The unit ships with a power cable and country-specific plug only if specified at ordering; coolant (water plus glysantine or ethylene glycol) and mating G3/4 fittings are not included.