Peter Huber Kältemaschinenbau Unichiller P012w-H OLÉ
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P012w-H OLÉ

Peter Huber Kältemaschinenbau Unichiller P012w-H OLÉ — Recirculating chillers.

The Unichiller P012w-H OLÉ is a water-cooled recirculating chiller with a plastic pump (type B) and a temperature range of -20 to 100 °C, built for externally closed circuits with high pressure drop. Its 'P' designation marks it as the high-pressure-drop variant within the Unichiller series, distinguishing it from the 015 siblings. It serves as a precision cooling source for laboratory and industrial processes requiring stable temperature control.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller P012w-H OLÉ Current —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
Temperature range -20...100 °C
Dimensions, Weight & Mechanical Design
Weight 61 kg
Electrical, Power & Drive Specifications
Fuse rating 16 A
Power supply 208V 2~ 60Hz
Interfaces, Connections & Control
Controller OLÉ
Display resolution 0, 1 K
Digital interface USB (Device), RS232 Interface
Temperature display OLED Display
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 48 л/час (at 15°C, flow -10°C)
at 15°C, flow 0°C: 57 l/h · at 15°C, flow 15°C: 60 l/h
Cooling water differential pressure 1 bar (min)
Cooling Water Pressure 6 bar (max)
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and Series Positioning

Behavior Under Load and Media

Installation, Control and Operation

Integration & Operating Notes

Process Limits
Cooling water inlet must stay between 5 °C and 20 °C

Operating outside this range risks condensation inside the unit and reduced cooling performance. If the cooling water temperature falls below the dew point, the internal cooling water pipes must be insulated to prevent condensation damage.

Unichiller P012w-H OLÉ Datasheet, page 2
Process Limits
Cooling water circuit requires 1–6 bar differential pressure

The site water supply must deliver a minimum differential pressure of 1 bar and must not exceed 6 bar. Insufficient pressure leads to inadequate flow and reduced cooling; excessive pressure may damage the unit.

Unichiller P012w-H OLÉ Datasheet, page 1
Electrical
Supply must be 208 V 2~ 60 Hz with 16 A fuse

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed. The unit is supplied with a cable but without a plug; a suitable plug must be provided on site.

Unichiller P012w-H OLÉ Datasheet, page 2
Mounting
Maintain 50–200 cm wall clearance per side

Free-standing models require this clearance for maintenance access. The unit must be installed indoors, protected from water ingress (IP20), at an ambient temperature of 5–40 °C and illuminance of at least 300 lx.

Unichiller Operation Manual, page 25
Mounting
Do not install in ATEX zones

The unit is not explosion-protected and must not be installed or started up inside an ATEX zone. Refrigerant charge and room size must be checked to avoid exceeding the refrigerant limit per m³ of ambient air.

Unichiller Operation Manual, page 13
Control & I/O
Configure power-failure response for process safety

The power-failure response can be set to OFF/Standby, ON, or Power Failure Auto via the Pilot ONE controller. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles.

Unichiller Operation Manual, pages 18–19
Maintenance
Shut off cooling water even for overnight downtime

The cooling water supply must be shut off during short downtimes to prevent water damage and corrosion. Refrigerant circuit work must only be performed by approved refrigeration/air-conditioning contractors.

Unichiller Operation Manual, page 28
Process Limits
Plastic pump is not resistant to acetone or polyglycols

These fluids must be avoided or a more resistant pump specified. For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.

Unichiller P012w-H OLÉ Datasheet, page 2

Selection & Integration Q&A

When should I choose the P012w-H OLÉ over the 015 series siblings?

Choose the P012w-H OLÉ for water-cooled installations and high-pressure-drop applications, as indicated by the 'P' in the model name. The 015 siblings are air-cooled (63 dB(A)) and lack the high-pressure-drop designation, making them unsuitable for such loops.

What are the requirements for the cooling water supply and pump connections?

The cooling water supply must provide 1–6 bar differential pressure and connect via G1/2 male fittings. The pump connection is G3/4 AG male; maximum tightening torques must be observed and connections counterheld during hose installation.

What are the mounting and environmental limits for this chiller?

Install indoors only, at 5–40 °C ambient, with at least 300 lx illuminance and up to 2000 m altitude. Maintain 50–200 cm wall clearance per side. Do not install in ATEX zones. Activate leveling feet and parking brakes before startup.

What maintenance and accessories are required that are not included in the base delivery?

A suitable plug must be provided on site (cable supplied without plug). Refrigerant circuit work requires approved contractors. Shut off cooling water during downtimes. For freeze protection, use glysantine or ethylene glycol mixtures; the plastic pump is not resistant to acetone or polyglycols.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P012w-H OLÉ Datasheet
Datasheet ·85,2 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.