Peter Huber Kältemaschinenbau Unichiller P015 OLÉ
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P015 OLÉ

Peter Huber Kältemaschinenbau Unichiller P015 OLÉ — Recirculating chillers with Noise level 63 dB.

The Unichiller P015 OLÉ is a single-phase recirculating chiller with a plastic pump and G3/4 male connections, rated for -20 to 40 °C. Its 'P' designation suits high-pressure-drop loops, and cooling capacity falls from 1.5 kW at 15 °C to 0.3 kW at -20 °C. It serves externally closed cooling circuits requiring a compact, non-explosion-protected indoor unit.

Noise level
63 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller P015 OLÉ Current 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 63 dB(A)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
Temperature range -20...40 °C
Dimensions, Weight & Mechanical Design
Weight 60 kg (net)
Electrical, Power & Drive Specifications
Fuse rating 16 A
Power supply 220-240V 1~ 50Hz
Interfaces, Connections & Control
Controller OLÉ
Display resolution 0, 1 K
Digital interface USB (Device), RS232 Interface
Temperature display OLED Display
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Performance under load

Installation and operation

Integration & Operating Notes

Process Limits
Cooling capacity must be checked at actual operating temperature

Sizing on the 1.5 kW figure at 15 °C will undersize the unit for sub-zero duty, because capacity falls to 0.3 kW at -20 °C. Verify the heat load at the lowest process temperature and at the expected room temperature, since output data are valid at 20 °C ambient.

Unichiller P015 OLÉ Technical Data, page 1
Electrical
Supply tolerances must not be combined unfavorably

The unit accepts 220-240 V 1~ 50 Hz with ±5% voltage and ±2% frequency tolerance, but a -5% voltage combined with +2% frequency is not allowed. Verify site supply quality before connection and size the 16 A fuse and cabling for the 8.5 A max current.

Unichiller P015 OLÉ Technical Data, page 2
Cooling & Media
Plastic pump excludes acetone and polyglycols

The type B plastic pump is not resistant to acetone or polyglycols (depending on manufacturer), so these media must not be used as heat transfer fluid. For sub-zero operation, mix water with glysantine or ethylene glycol for freeze protection rather than using pure water.

Unichiller P015 OLÉ Technical Data, page 2
Mounting
Indoor installation with ATEX and clearance restrictions

The unit is not explosion-protected and must not be installed or started up inside an ATEX zone. Use only indoors at 5–40 °C ambient, at least 300 lx illuminance and up to 2000 m altitude, with 50–200 cm wall clearance per side for maintenance. Check refrigerant charge against room size to avoid exceeding the limit per m³.

Unichiller Operation Manual, pages 13, 15, 25
Mounting
Secure the unit before switching on

Activate parking brakes at the casters (if any) and/or unscrew/activate the leveling feet before putting the unit into operation, to prevent movement and crushing injuries. Counterhold pump connections and do not exceed maximum tightening torques during hose installation.

Unichiller Operation Manual, pages 28, 31
Control & I/O
Configure power-failure response for the process risk

The power-failure response can be set to OFF/Standby, ON or Power Failure Auto via the Pilot ONE. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles; select the mode that matches the process hazard.

Unichiller Operation Manual, pages 18–19
Maintenance
Refrigerant circuit work requires approved contractors

Work on the coolant circuit must only be performed by approved refrigeration/air-conditioning system contractors. Plan the 3.8 l minimum filling capacity and 1.7 l expansion tank into the loop, and shut off cooling water supply even for short downtimes such as overnight.

Unichiller Operation Manual, pages 17, 28; Technical Data, page 1

Selection & Integration Q&A

When should I choose the P015 OLÉ rather than the Unichiller 015 OLÉ or the 015-H OLÉ?

Choose the P015 OLÉ when the external loop has high pressure drop, since the 'P' model is specifically suited to such applications. The 015 OLÉ is the standard variant; the 015-H OLÉ adds a different configuration. All share 63 dB(A) noise.

What hydraulic and electrical requirements must adjacent system parts meet?

Mating hoses and fittings must match the G3/4 AG male pump connection, and the external circuit pressure drop must be checked against the pump curve (21 l/min at 0.5 bar down to 6 l/min at 2.0 bar). Supply must be 220-240 V 1~ 50 Hz with a 16 A fuse.

What mounting and duty-cycle limits apply from the manual?

Install indoors only, outside ATEX zones, at 5–40 °C ambient, at least 300 lx and up to 2000 m altitude, with 50–200 cm wall clearance per side. Activate parking brakes or leveling feet before start-up and verify refrigerant charge against room volume.

What maintenance and consumables are required beyond base delivery?

Refrigerant circuit work must be done by approved refrigeration contractors. Plan for 3.8 l minimum filling capacity and a 1.7 l expansion tank; use glysantine or ethylene glycol for freeze protection. Shut off cooling water even overnight. USB and RS232 interfaces are built in.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P015 OLÉ Technical Data
Datasheet ·102,4 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF