Peter Huber Kältemaschinenbau Unichiller P015w-H OLÉ
Peter Huber Kältemaschinenbau Unichiller P015w-H OLÉ — Recirculating chillers with Noise level 54 dB.
The Unichiller P015w-H OLÉ is a water-cooled recirculating chiller with a 1.7 L internal volume, rated for -20 to 100 °C and built for externally closed, high-pressure-drop loops. Its 'P' designation and OLÉ controller distinguish it from the 015 series siblings, which share the same 63 dB(A) noise level but lack the high-pressure-drop pump configuration.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P015w-H OLÉ Current | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 54 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| Temperature range | -20...100 °C |
| Weight | 54 kg |
| Power supply | 220-240V 1~/2~ 50Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 36 л/час (at 15°C, flow -20°C) at 15°C, flow -10°C: 48 л/час · at 15°C, flow 0°C: 60 l/h · at 15°C, flow 15°C: 68 l/h |
| Cooling water differential pressure | 1 bar (min.) |
| Cooling Water Pressure | 6 bar (max.) |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- The P015w-H OLÉ is a water-cooled refrigeration machine using CFC- and HCFC-free R-449A (GWP 1397), with a copper/stainless steel 1.4401/MS/PA/PPE/PTFE/EPDM cooling-water circuit.
- The 'P' in the model name marks it as particularly suitable for applications requiring high pressure drops; the 'w' denotes water cooling, and 'OLÉ' is the controller variant.
- Sibling models Unichiller 015, 015-H, 015-H OLÉ and 015 OLÉ are air-cooled equivalents rated at 63 dB(A); this water-cooled unit is specified at 54 dB(A).
- Pump connection is G3/4 male; cooling-water connection is G1/2 male. The pump is type B and is not speed-adjustable.
Behavior and media
- Temperature range is -20 to 100 °C with 0.1 K display resolution on an OLED display.
- Cooling-water consumption depends on the flow temperature: 68 l/h at 15 °C flow, 60 l/h at 0 °C, 48 l/h at -10 °C and 36 l/h at -20 °C, all at 15 °C cooling-water inlet.
- Cooling power drops as cooling-water temperature rises, and the required cooling-water flow rate may increase accordingly.
- The unit is intended only for externally closed applications; it is not explosion-protected and must not be installed in an ATEX zone.
Installation, control and operation
- Cooling water must be supplied at 5–20 °C inlet with a minimum differential pressure of 1 bar and maximum pressure of 6 bar; pipes below the condensation point must be insulated.
- Power supply is 220–240 V, 1~/2~, 50 Hz; voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed. Single/two-phase units ship with a country-specific plug that must be specified at ordering.
- The OLÉ controller provides USB (Device) and RS232 interfaces, adjustable overtemperature protection to DIN 12876, safety class III/FL, and a configurable power-failure response (OFF/Standby, ON, or Power Failure Auto).
- Process Safety mode releases maximum cooling capacity when the OT trigger value is reached instead of switching off all poles.
- Protection rating is IP20; ambient operating range is 5–40 °C; the unit is for indoor use only at ≥300 lx and up to 2000 m altitude.
Integration & Operating Notes
Exceeding 6 bar risks damage to the cooling-water circuit, while falling below 1 bar differential pressure starves the condenser. Inlet temperatures above 20 °C reduce cooling power and may require higher flow; below the condensation point, pipes must be insulated to prevent condensate.
The ±5% voltage tolerance applies only with a simultaneous ±2% frequency tolerance, and certain combinations are not allowed. Verify site power quality against this combined envelope before commissioning; the country-specific plug must be specified at ordering for single/two-phase units.
The unit is designed for externally closed applications and is not explosion-protected, so it must not be installed or started up inside an ATEX zone. Refrigerant charge and room size must be checked at installation to avoid exceeding the refrigerant limit per m³ of ambient air.
The cooling water supply must be shut off even for short downtimes such as overnight to prevent water damage and corrosion. Work on the refrigerant circuit must only be performed by approved refrigeration/air-conditioning contractors; the unit uses R-449A with GWP 1397.
Selection & Integration Q&A
Choose the P015w-H OLÉ for high-pressure-drop process loops and where water cooling is available; it is rated 54 dB(A) versus 63 dB(A) for the air-cooled 015-H OLÉ. The 015-H OLÉ suits sites without a cooling-water supply.
Provide 5–20 °C cooling water at 1–6 bar differential pressure with G1/2 male connections; flow demand is 68 l/h at 15 °C flow temperature down to 36 l/h at -20 °C. Insulate pipes below the condensation point and use only water compatible with copper, 1.4401, MS, PA, PPE, PTFE and EPDM.
Indoor use only at ≥300 lx and up to 2000 m altitude, ambient 5–40 °C, IP20. Allow 50–200 cm wall clearance per side for maintenance, protect cables below against condensate, and activate leveling feet and parking brakes before startup.
The country-specific plug must be specified at ordering; the Pt100 sensor connection is a factory-fitted option for display only, not control. Plan to shut off cooling water during overnight downtime and schedule refrigerant-circuit work only with approved contractors.