Peter Huber Kältemaschinenbau Unichiller P022-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P022-H

Peter Huber Kältemaschinenbau Unichiller P022-H — Recirculating chillers with Noise level 65 dB.

The Unichiller P022-H is an air-cooled, externally closed recirculating chiller with a plastic pressure pump (type B, G3/4 male) and Pilot ONE controller, rated -10 to 100 °C. Its 'P' designation targets process loops with high pressure drop, delivering up to 25 l/min at 2.5 bar. Cooling capacity falls from 2.2 kW at 15 °C to 1 kW at -10 °C, so it is sized for the coldest duty point.

Noise level
65 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller P022-H Current 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 65 dB(A)
Maximum delivery flow rate 25 l/min (pressure pump max; also 2, 5 bar)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
External sensor connection Pt100
Temperature range -10...100 °C
Dimensions, Weight & Mechanical Design
Weight 83 kg
Electrical, Power & Drive Specifications
Current consumption 15 A (max)
Fuse rating 16 A
Power supply 220-240V 1~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Display resolution 0, 1 K
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Electrical
Supply must stay within ±5% voltage and ±2% frequency

The 220-240 V 1~ 50 Hz supply tolerates ±5% voltage with a simultaneous ±2% frequency tolerance, but not all combinations are permitted. Max current is 15 A with a 16 A fuse; verify the site supply and breaker before commissioning.

Unichiller P022-H Chiller Datasheet, Technical Specifications
Process Limits
Loop must be externally closed and filled to at least 3.8 l

The unit is designed only for externally closed applications. Minimum filling capacity is 3.8 l with 1.7 l expansion volume, so the circuit must be filled accordingly and expansion accommodated to avoid insufficient filling or overpressure.

Unichiller Operation Manual, Function Description; Datasheet
Cooling & Media
Avoid acetone and polyglycols with the plastic pump

The plastic pump is not resistant to acetone or polyglycols (depending on manufacturer). For operation near or below 0 °C, mix water with glysantine or ethylene glycol for freeze protection rather than using water alone.

Unichiller P022-H Chiller Datasheet, Technical Specifications
Mounting
Keep 50-200 cm clearance per side and lock the casters

A wall clearance of 50 to 200 cm per side is required for maintenance. Before start-up, activate parking brakes at the casters and/or unscrew the leveling feet so the unit cannot move during operation. Indoor use only, at least 300 lx illuminance, up to 2000 m altitude.

Unichiller Operation Manual, Commissioning
Safety
Process Safety mode releases max cooling on OT trigger

In Process Safety mode the controller releases maximum cooling capacity when the overtemperature trigger value is reached instead of switching off all poles. Select this mode for exothermic processes where cutting cooling would cause runaway temperatures.

Unichiller Operation Manual, Normal Operation
Maintenance
Refrigerant circuit work only by approved contractors

Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A (UN 2857, GWP 1397); observe charge and room size at installation to stay within the refrigerant limit per m³ of ambient air.

Unichiller Operation Manual, Maintenance; Datasheet

Selection & Integration Q&A

When should I choose the P022-H over the Unichiller 015 siblings?

Pick the P022-H when the process loop has high pressure drop (the 'P' designation) and needs up to 25 l/min at 2.5 bar with cooling down to -10 °C. The 015 siblings are lower-capacity, quieter (63 dB(A) vs 65 dB(A)) alternatives for less demanding loops.

What must the external hydraulic circuit and fittings provide?

The loop must be externally closed, connect via G3/4 male threads, hold at least 3.8 l with 1.7 l expansion volume, and its pressure drop must fit the pump curve (25 l/min max, 2.5 bar max). Avoid acetone and polyglycols; use glycol mix for freeze protection.

What installation environment and duty limits apply?

Indoor use only, 5-40 °C ambient, at least 300 lx, up to 2000 m altitude, IP20 (protect from water/dust), no ATEX zones. Keep 50-200 cm clearance per side, lock casters/leveling feet, and expect reduced cooling capacity above 20 °C room temperature.

What maintenance and accessories are required beyond base delivery?

Refrigerant circuit service only by approved refrigeration contractors; check refrigerant charge vs room size. The base unit includes the Pilot ONE controller and Pt100 external sensor input, but hoses, G3/4 fittings, heat transfer fluid/glycol and any interface cables are not included and must be sourced separately.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P022-H Chiller Datasheet
Datasheet ·95,9 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF