Peter Huber Kältemaschinenbau Unichiller P022w
Peter Huber Kältemaschinenbau Unichiller P022w — Recirculating chillers with Noise level 60 dB.
Water-cooled recirculating chiller with a plastic pump and Pilot ONE controller, rated 2.2 kW at 15 °C and 1 kW at -10 °C over a -10…40 °C range. The 'P' designation marks it for externally closed loops with high pressure drop, distinguishing it from the 015 siblings. It serves as a secondary cooling stage for laboratory and process circuits.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P022w Current | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 60 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| External sensor connection | Pt100 |
| Temperature range | -10...40 °C |
| Weight | 67 kg |
| Power supply | 208-230V 1~/2~ 60Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 77 л/час (at 15°C, flow -10°C) at 15°C, flow 0°C: 96 l/h · at 15°C, flow 15°C: 95 l/h |
| Cooling water differential pressure | 1 bar |
| Cooling Water Pressure | 6 bar |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- Water-cooled refrigeration circuit (R-449A, 0.45 kg, GWP 1397) with a non-adjustable plastic pump (type B) delivering up to 25 l/min and 2.5 bar; flow falls to 6 l/min at 2.0 bar.
- The 'P' in P022w designates suitability for externally closed applications with high pressure drop, per the operation manual; the sibling Unichiller 015 variants (015, 015-H, 015 OLÉ, 015-H OLÉ) are the air-cooled/other configurations of the series.
- Hydraulics: pump connection G3/4 male, cooling-water connection G1/2 male; minimum filling capacity 3.8 l, expansion volume 1.7 l.
Behavior across the working range
- Cooling power is 2.2 kW at 15 °C, 1.6 kW at 0 °C and 1 kW at -10 °C (ambient +20 °C), so capacity must be sized against the actual process temperature, not the nominal figure.
- Cooling-water consumption at 15 °C intake: 96 l/h at 0 °C flow, 95 l/h at 15 °C flow, 77 l/h at -10 °C flow.
- Temperature range -10…40 °C; ambient 5…40 °C; cooling-water intake 5…20 °C.
Control, installation and operation
- Pilot ONE controller with Ethernet, USB host/device and RS232; external Pt100 sensor connection; power-failure response configurable as OFF/Standby, ON or Power Failure Auto.
- Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles.
- Electrical: 208-230 V 1~/2~ 60 Hz, max 12.5 A, 2×16 A fusing; Class A Group 1 to EN55011; IP20; safety class I/NFL.
- Installation: indoors only, illuminance ≥300 lx, altitude ≤2000 m, 50–200 cm wall clearance per side; leveling feet/parking brakes set before start-up; cooling water shut off even overnight.
Integration & Operating Notes
Below 1 bar differential pressure the chiller cannot reject heat correctly; above 6 bar the water circuit and connections are at risk. Verify the site supply with a gauge before installation and fit a pressure reducer if the mains can exceed 6 bar.
The unit is designed for cooling-water intake between 5 °C and 20 °C. If the water can fall below the condensation point of the surroundings, pipes must be insulated to prevent condensate; electrical lines directly below the unit must be protected against liquid ingress.
The standard plastic pump is not resistant to acetone or polyglycols. For these media a more resistant pump must be ordered; otherwise the fluid must be changed. For freeze protection, mix water with glysantine or ethylene glycol rather than using pure water.
The unit is not explosion-protected and must not be installed in an ATEX zone. It is for indoor use at ≥300 lx and ≤2000 m altitude, with 50–200 cm wall clearance on either side for maintenance. Check refrigerant charge against room volume to stay within the limit per m³ of ambient air.
Any work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The R-449A charge of 0.45 kg (0.6 t CO2e) also triggers leak-reporting obligations; keep the rating-plate data available for service and compliance records.
Close the cooling-water supply to the unit for any downtime, including overnight, to prevent water damage and corrosion in the circuit. Before start-up, activate parking brakes and/or unscrew the leveling feet so the unit cannot move during operation.
Selection & Integration Q&A
Pick the P022w for externally closed loops with high pressure drop, where the 'P' pump curve (25 l/min, 2.5 bar max) is needed. The 015 variants are the other series configurations; compare their cooling capacity and cooling concept against your process load before deciding.
Provide cooling water at 1–6 bar differential and 5–20 °C intake, with G1/2 male couplings; process loop connects to the G3/4 male pump ports. Electrically, supply 208-230 V 1~/2~ 60 Hz with 2×16 A fusing and fit a site plug, since the cable is supplied without one.
Indoors only, outside ATEX zones, at ≥300 lx and ≤2000 m altitude, with 50–200 cm clearance per side and ambient 5–40 °C. Activate parking brakes or leveling feet before start-up, and protect electrical lines below the unit from condensate.
The base unit ships without a mains plug, hose couplings for G3/4 and G1/2 connections, and heat-transfer fluid; the minimum fill is 3.8 l with 1.7 l expansion allowance. Refrigerant-circuit service must be performed by approved contractors; freeze protection requires glysantine or ethylene glycol added on site.