Peter Huber Kältemaschinenbau Unichiller P022w-H
Peter Huber Kältemaschinenbau Unichiller P022w-H — Recirculating chillers with Noise level 60 dB.
The Unichiller P022w-H is a water-cooled recirculating chiller with a plastic pump (type B) and Pilot ONE controller, covering -10 to 100 °C. Its 'P' designation targets high-pressure-drop process loops, distinguishing it from the 015 series siblings. It serves externally closed circuits requiring up to 25 l/min at 2.5 bar.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P022w-H Current | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 60 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| External sensor connection | Pt100 |
| Temperature range | -10...100 °C |
| Weight | 65 kg |
| Current consumption | 14 A |
| Fuse rating | 16 A |
| Power supply | 220-240V 1~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 77 l/h (at 15°C, flow -10°C) at 15°C, flow 0°C: 96 l/h · at 15°C, flow 15°C: 95 l/h |
| Cooling water differential pressure | 1 bar |
| Cooling Water Pressure | 6 bar |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- Water-cooled refrigeration circuit using R-290 (A3 flammable) refrigerant; cooling water connections G1/2 male, process pump connection G3/4 AG male.
- Plastic pump (type B), non-adjustable speed, max delivery 25 l/min, max delivery pressure 2.5 bar; flow falls to 6 l/min at 2.0 bar.
- The 'P' in the model name marks suitability for applications with high pressure drop, per the operation manual; sibling Unichiller 015 variants (015, 015-H, 015-H OLÉ, 015 OLÉ) are air-cooled alternatives with 63 dB(A) noise.
- IP20 protection, 65 kg, Pilot ONE controller with Ethernet, USB (host and device) and RS232 interfaces; external Pt100 sensor input.
Behavior and media constraints
- Temperature range -10 to 100 °C; cooling water consumption varies with flow temperature: 96 l/h at 0 °C, 95 l/h at 15 °C, 77 l/h at -10 °C (all at 15 °C water inlet).
- Rated output data valid only at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure.
- Plastic pump is not resistant to acetone or polyglycols; freeze protection requires glysantine or ethylene glycol addition.
- Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM; water quality must be compatible.
Installation and control
- Requires 220–240 V 1~ 50 Hz supply, 14 A max current, 16 A fuse; voltage tolerance ±5 % and frequency ±2 %, not simultaneously in the same direction.
- Cooling water supply must provide 1–6 bar differential pressure and 5–20 °C inlet temperature; pipes insulated if below condensation point.
- Pilot ONE controller supports power-failure response modes (OFF/Standby, ON, Power Failure Auto) and Process Safety mode, which releases maximum cooling capacity when the overtemperature trigger is reached.
- Minimum filling capacity 3.8 l, expansion volume 1.7 l; pressure equipment category Art. 4.3 PED.
Integration & Operating Notes
Too low a differential pressure will trip the unit; too high may damage the cooling circuit. Verify site supply pressure at commissioning and install a regulator if the mains can exceed 6 bar.
The unit draws up to 14 A; a 16 A circuit is mandatory. Voltage and frequency tolerances of ±5 % and ±2 % must not occur simultaneously in the same direction, so verify supply quality before connection.
The manual states the unit is designed for externally closed applications. Open baths or circuits exposed to atmosphere are outside the intended use and may cause pump or fluid problems.
The type B plastic pump is not resistant to acetone or polyglycols (depending on manufacturer). Select an alternative heat transfer fluid or a more resistant pump variant if these media are required.
Free-standing models require this clearance for maintenance access. Also observe refrigerant charge versus room volume to avoid exceeding the limit per m³ of ambient air, and install only indoors at ≥300 lx and up to 2000 m altitude.
Water-cooled units can produce condensation; electrical lines directly below must be protected against liquid ingress. Also shut off cooling water supply even for short downtimes such as overnight to prevent water damage.
The unit is not explosion-protected and uses flammable R-290 (A3, H220). Do not install or start up within an ATEX zone; consider ignition sources and ventilation per the refrigerant charge and room size.
The Pilot ONE allows OFF/Standby, ON, or Power Failure Auto after a power outage. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles.
Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. Plan service access accordingly and ensure the 50–200 cm side clearance is kept free.
Selection & Integration Q&A
Choose the P022w-H for high-pressure-drop process loops (the 'P' designation) and when water cooling is available. The 015 series are air-cooled alternatives at 63 dB(A); the P022w-H is water-cooled at 60 dB(A) and requires a cooling water supply of 1–6 bar.
Provide cooling water at 5–20 °C inlet with 1–6 bar differential pressure and capacity for 77–96 l/h. Electrical supply must be 220–240 V 1~ 50 Hz, 14 A max, protected by a 16 A fuse; voltage/frequency tolerances ±5 %/±2 % not simultaneously in the same direction.
Install indoors only, at ≥300 lx and up to 2000 m altitude, with 50–200 cm wall clearance per side for maintenance. Ambient must be 5–40 °C, IP20 excludes wet/dusty locations, and ATEX zones are prohibited due to R-290 refrigerant.
Refrigerant circuit work requires approved refrigeration contractors. Minimum fill is 3.8 l with 1.7 l expansion volume; use glysantine or ethylene glycol for freeze protection. Cooling water must be shut off during downtimes; no cables or accessories are included beyond the stated interfaces.