Peter Huber Kältemaschinenbau Unichiller P022w-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P022w-H

Peter Huber Kältemaschinenbau Unichiller P022w-H — Recirculating chillers with Noise level 60 dB.

The Unichiller P022w-H is a water-cooled recirculating chiller with a plastic pump (type B) and Pilot ONE controller, covering -10 to 100 °C. Its 'P' designation targets high-pressure-drop process loops, distinguishing it from the 015 series siblings. It serves externally closed circuits requiring up to 25 l/min at 2.5 bar.

Noise level
60 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller P022w-H Current 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 60 dB(A)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
External sensor connection Pt100
Temperature range -10...100 °C
Dimensions, Weight & Mechanical Design
Weight 65 kg
Electrical, Power & Drive Specifications
Current consumption 14 A
Fuse rating 16 A
Power supply 220-240V 1~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1/2 male
Cooling water consumption 77 l/h (at 15°C, flow -10°C)
at 15°C, flow 0°C: 96 l/h · at 15°C, flow 15°C: 95 l/h
Cooling water differential pressure 1 bar
Cooling Water Pressure 6 bar
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Behavior and media constraints

Installation and control

Integration & Operating Notes

Cooling & Media
Cooling water pressure must stay within 1–6 bar

Too low a differential pressure will trip the unit; too high may damage the cooling circuit. Verify site supply pressure at commissioning and install a regulator if the mains can exceed 6 bar.

Unichiller P022w-H Datasheet, page 2
Electrical
Supply must be 220–240 V 1~ 50 Hz with 16 A fuse

The unit draws up to 14 A; a 16 A circuit is mandatory. Voltage and frequency tolerances of ±5 % and ±2 % must not occur simultaneously in the same direction, so verify supply quality before connection.

Unichiller P022w-H Datasheet, page 2
Process Limits
Only externally closed circuits are permitted

The manual states the unit is designed for externally closed applications. Open baths or circuits exposed to atmosphere are outside the intended use and may cause pump or fluid problems.

Unichiller Operation Manual, page 34
Process Limits
Plastic pump incompatible with acetone and polyglycols

The type B plastic pump is not resistant to acetone or polyglycols (depending on manufacturer). Select an alternative heat transfer fluid or a more resistant pump variant if these media are required.

Unichiller P022w-H Datasheet, page 2
Mounting
Maintain 50–200 cm wall clearance per side

Free-standing models require this clearance for maintenance access. Also observe refrigerant charge versus room volume to avoid exceeding the limit per m³ of ambient air, and install only indoors at ≥300 lx and up to 2000 m altitude.

Unichiller Operation Manual, page 25
Mounting
Protect electrical lines below the unit from condensate

Water-cooled units can produce condensation; electrical lines directly below must be protected against liquid ingress. Also shut off cooling water supply even for short downtimes such as overnight to prevent water damage.

Unichiller Operation Manual, page 28
Safety
Not permitted inside ATEX zones due to R-290 refrigerant

The unit is not explosion-protected and uses flammable R-290 (A3, H220). Do not install or start up within an ATEX zone; consider ignition sources and ventilation per the refrigerant charge and room size.

Unichiller Operation Manual, page 13; Datasheet page 1
Control & I/O
Configure power-failure response for process safety

The Pilot ONE allows OFF/Standby, ON, or Power Failure Auto after a power outage. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles.

Unichiller Operation Manual, pages 18–19
Maintenance
Refrigerant circuit work only by approved contractors

Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. Plan service access accordingly and ensure the 50–200 cm side clearance is kept free.

Unichiller Operation Manual, page 17

Selection & Integration Q&A

When should I choose the P022w-H over the Unichiller 015 siblings?

Choose the P022w-H for high-pressure-drop process loops (the 'P' designation) and when water cooling is available. The 015 series are air-cooled alternatives at 63 dB(A); the P022w-H is water-cooled at 60 dB(A) and requires a cooling water supply of 1–6 bar.

What cooling water supply and electrical infrastructure must be provided for this chiller?

Provide cooling water at 5–20 °C inlet with 1–6 bar differential pressure and capacity for 77–96 l/h. Electrical supply must be 220–240 V 1~ 50 Hz, 14 A max, protected by a 16 A fuse; voltage/frequency tolerances ±5 %/±2 % not simultaneously in the same direction.

What are the mounting and environment limits from the manual?

Install indoors only, at ≥300 lx and up to 2000 m altitude, with 50–200 cm wall clearance per side for maintenance. Ambient must be 5–40 °C, IP20 excludes wet/dusty locations, and ATEX zones are prohibited due to R-290 refrigerant.

What maintenance and consumables are required beyond base delivery?

Refrigerant circuit work requires approved refrigeration contractors. Minimum fill is 3.8 l with 1.7 l expansion volume; use glysantine or ethylene glycol for freeze protection. Cooling water must be shut off during downtimes; no cables or accessories are included beyond the stated interfaces.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P022w-H Datasheet
Datasheet ·31,1 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF