Peter Huber Kältemaschinenbau Unichiller P025-H OLÉ
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P025-H OLÉ

Peter Huber Kältemaschinenbau Unichiller P025-H OLÉ — Recirculating chillers with Noise level 64 dB.

The Unichiller P025-H OLÉ is a single-phase, air-cooled recirculating chiller with a 2.5 kW cooling capacity at 15 °C and a -10 to 100 °C working range. Its 'P' designation and non-adjustable pump suit high-pressure-drop, externally closed circuits. It serves sub-ambient and moderate heating duties in industrial environments.

Noise level
64 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller P025-H OLÉ Current 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 64 dB(A)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type B
Temperature range -10...100 °C
Dimensions, Weight & Mechanical Design
Weight 81 kg
Electrical, Power & Drive Specifications
Current consumption 16 A
Fuse rating 16 A
Power supply 220-240V 1~ 50Hz
Interfaces, Connections & Control
Controller OLÉ
Display resolution 0, 1 K
Digital interface USB (Device), RS232 Interface
Temperature display OLED Display
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Process Limits
Do not exceed pump curve limits in high-pressure-drop loops

The fixed-speed pump delivers only 6 l/min at 2.0 bar. If the external circuit's pressure drop exceeds this, flow will fall below the required rate, risking poor temperature control or process shutdown. Verify the loop's pressure drop against the pump curve before commissioning.

Unichiller P025-H OLÉ Datasheet, page 1
Electrical
Supply voltage and frequency tolerances are interdependent

A ±5 % voltage deviation is only permissible with ±2 % frequency deviation, and the combination of -5 % voltage with +2 % frequency is explicitly not allowed. This must be checked at the site to avoid compressor damage.

Unichiller P025-H OLÉ Datasheet, page 2
Mounting
Maintain 50–200 cm wall clearance per side for maintenance access

Free-standing models require this clearance on either side to allow service access and adequate air flow. Insufficient clearance can lead to overheating and reduced cooling capacity, especially in warm ambient conditions.

Unichiller Operation Manual, page 25
Process Limits
Use only externally closed circuits with compatible fluids

The unit is designed for externally closed applications. The plastic pump is not resistant to acetone or polyglycols; for sub-zero operation, a water/glysantine or water/ethylene glycol mixture is recommended. Ensure the thermal fluid is compatible with the pump and circuit materials.

Unichiller Operation Manual, page 34 and Datasheet page 2
Maintenance
Refrigerant circuit work requires certified contractors

Any work on the refrigerant circuit must be performed by approved refrigeration/air-conditioning system contractors. The unit contains R-290 (A3) refrigerant, and improper handling poses flammability risks. Ensure service personnel are qualified and follow local regulations.

Unichiller Operation Manual, page 17

Selection & Integration Q&A

When should I choose the P025-H OLÉ over the Unichiller 015-H OLÉ?

Choose the P025-H OLÉ when your process requires higher cooling capacity (2.5 kW at 15 °C) and can tolerate 64 dB(A) noise. The 015-H OLÉ offers lower capacity and 63 dB(A). The 'P' designation indicates suitability for high-pressure-drop circuits, so select this model if your loop has significant pressure loss.

What are the requirements for connecting the P025-H OLÉ to my process loop?

The pump connection is G3/4 male, so hoses or adapters must match this thread. Ensure the external circuit is externally closed and its pressure drop does not exceed the pump curve (e.g., 6 l/min at 2.0 bar). Use compatible fluids: avoid acetone and polyglycols; for sub-zero, use water with glysantine or ethylene glycol.

What are the ambient and installation limits for the P025-H OLÉ?

Install indoors only, with ambient temperature 5–40 °C, illuminance ≥300 lx, and altitude ≤2000 m. Maintain 50–200 cm wall clearance per side. The IP20 enclosure requires a dry, clean location. Do not install in an ATEX zone. Cooling capacity is rated at 20 °C room temperature and drops as ambient rises.

What maintenance and accessories are required for the P025-H OLÉ?

Refrigerant circuit work must be by certified contractors. Shut off cooling water during downtimes. The unit is delivered with a power cable and country-specific plug (specify at ordering). No other accessories are included; USB and RS232 interfaces are standard. Regular maintenance includes checking fluid quality and pump connections.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P025-H OLÉ Datasheet
Datasheet ·126,8 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF