Peter Huber Kältemaschinenbau Unichiller 025w OLÉ
Peter Huber Kältemaschinenbau Unichiller 025w OLÉ — Recirculating chillers with Noise level 60 dB.
Water-cooled recirculating chiller with a 2 kW cooling capacity at 0 °C and a -10…40 °C working range, distinguished within the Unichiller series by its OLÉ controller and 025w water-cooled condenser. It serves externally closed process loops where heat is rejected to a 1–6 bar cooling water supply rather than to room air.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller 025w OLÉ Current | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025 | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 60 dB(A) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | Immersion pump |
| Temperature range | -10...40 °C |
| Weight | 61 kg |
| Power supply | 220-240V 1~ 50Hz |
| Controller | OLÉ |
| Display resolution | 0, 1 K |
| Digital interface | USB (Device), RS232 Interface |
| Temperature display | OLED Display |
| Ambient temperature limit | 5...40 °C |
| Cooling capacity | 2 kW (at 0 °C) |
| Cooling water connection | G1/2 male |
| Cooling water consumption | 72 л/час (at 15°C, flow -10°C) at 15°C, flow 0°C: 84 l/h · at 15°C, flow 15°C: 84 l/h |
| Cooling water differential pressure | 1 bar (min.) |
| Cooling Water Pressure | 6 bar (max.) |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- The Unichiller 025w OLÉ is a water-cooled (w suffix) recirculating chiller with an immersion pump and a fixed-speed pump; the OLÉ controller provides an OLED display with 0.1 K resolution, USB device and RS232 interfaces.
- Within the series it sits above the 015 siblings (63 dB(A)); this model is rated 60 dB(A) and uses a water-cooled condenser, so it rejects heat to the cooling water circuit instead of the room.
- The pump connection is G3/4 AG male; the cooling water connection is G1/2 male. The unit is IP20, safety class I / NFL, and weighs 61 kg.
Behavior under load and media
- Cooling capacity is 2 kW at 0 °C. Cooling water consumption is 84 l/h at 15 °C cooling water with 0 °C flow and also 84 l/h with 15 °C flow; at -10 °C flow it is 72 l/h.
- Performance is tied to cooling water conditions: as cooling water temperature rises, cooling power drops and cooling water flow rate may increase, so site performance must be derated from the 15 °C basis.
- The plastic pump is not resistant to acetone and polyglycols; for freeze protection water should be mixed with glysantine or ethylene glycol.
Installation, control and operation
- The unit is for indoor use only, at 5…40 °C ambient, at least 300 lx illuminance and up to 2000 m altitude; it must not be installed in an ATEX zone. Free-standing models need 50–200 cm wall clearance per side for maintenance.
- Cooling water must be 5–20 °C intake with 1 bar minimum differential pressure and 6 bar maximum; shut off cooling water even for overnight downtimes. Electrical lines below the unit must be protected against condensate.
- Power is 220–240 V 1~ 50 Hz with ±5% voltage and ±2% frequency tolerance (certain combinations such as -5% voltage with +2% frequency are not allowed); a country-specific plug must be specified at ordering. Autostart after power failure is available, and Process Safety mode can release maximum cooling instead of switching off.
Integration & Operating Notes
The condenser is designed for cooling water intake between 5 °C and 20 °C. Colder water requires insulating the cooling water pipes to prevent condensation; warmer water reduces cooling capacity and may raise the required flow rate, so the 2 kW rating at 0 °C cannot be assumed outside this window.
The water circuit needs at least 1 bar differential pressure to achieve the stated flow, and must never exceed 6 bar. The G1/2 male connection must be matched to the site supply; exceeding the maximum pressure risks damage to the condenser and internal piping.
The 220–240 V 1~ 50 Hz supply allows ±5% voltage only with a simultaneous ±2% frequency tolerance, and combinations such as -5% voltage with +2% frequency are not permitted. Verify site power quality before installation; the country-specific plug must be specified when ordering.
Install only indoors at 5–40 °C ambient, at least 300 lx illuminance and up to 2000 m altitude; the unit is not explosion-protected and must not be placed in an ATEX zone. Free-standing models require 50–200 cm wall clearance per side for maintenance access, and leveling feet or parking brakes must be set before start-up.
The immersion pump is not resistant to acetone or polyglycols (depending on manufacturer), so these fluids require an alternative pump option or must be avoided. For freeze protection, mix water with glysantine or ethylene glycol rather than using pure water.
The unit contains R-449A (GWP 1397, CO2 equivalent 0.6 t); any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. Shut off cooling water even for short downtimes such as overnight to prevent water damage and corrosion.
The power-failure response can be set to OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles; choose the mode that matches the process risk.
Selection & Integration Q&A
Choose the 025w OLÉ when you need 2 kW at 0 °C and water-cooled heat rejection (no room heat load) with the OLÉ controller; the 015 siblings are air-cooled, 63 dB(A), and lower capacity. Pick a 015 when cooling water is unavailable or capacity demand is lower.
Indoor use only, 5–40 °C ambient, ≥300 lx, ≤2000 m altitude, not in ATEX zones; 50–200 cm side clearance for free-standing units. Leveling feet/parking brakes must be set before start-up, and cooling water must be shut off even overnight.
The country-specific power plug must be specified at ordering; the Pt100 sensor connection for process temperature display is a factory-fitted option at extra cost. Refrigerant circuit service requires approved contractors; no consumables or cables beyond the power cable are included.