Peter Huber Kältemaschinenbau Unichiller 015-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 015-H

Peter Huber Kältemaschinenbau Unichiller 015-H — Recirculating chillers with Noise level 63 dB.

The Unichiller 015-H is an air-cooled recirculating chiller with an immersion pump and Pilot ONE controller, rated -20 to 100 °C. Within the 015 series it is the standard (non-OLÉ) variant; the -H suffix denotes this configuration. It serves externally closed cooling loops, delivering up to 29 l/min at 1 bar through G3/4 male connections.

Noise level
63 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller 015-H Current 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 63 dB(A)
Maximum delivery flow rate 29 l/min (1 bar)
Pump connection G3/4 AG male
Pump speed adjustable Yes
Pump type Immersion pump
External sensor connection Pt100
Temperature range -20...100 °C
Dimensions, Weight & Mechanical Design
Weight 55 kg
Electrical, Power & Drive Specifications
Fuse rating 16 A
Power supply 220-240V 1~/2~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Behavior and media

Installation, control and operation

Integration & Operating Notes

Process Limits
Externally closed loops only; no open bath use

The unit is designed for externally closed applications, so the hydraulic circuit must be a sealed loop with the external Pt100 sensor placed in the process. Open-tank or atmospheric operation is outside the intended use and invalidates the rating.

Unichiller Operation Manual, Function Description / Selection
Electrical
Size the supply for 14.5 A and a 16 A fuse

The 220-240 V 1~/2~ 50 Hz supply must carry a maximum current of 14.5 A protected by a 16 A fuse. Combined voltage/frequency deviation outside the permitted envelope (-5% voltage with +2% frequency explicitly not allowed) must be avoided at the installation point.

Unichiller 015-H Technical Data, Specifications
Mounting
Keep 50-200 cm wall clearance per side for service

Free-standing installation requires 50 to 200 cm wall clearance on either side for maintenance access, and the air-cooled condenser needs unobstructed airflow. Leveling feet must be unscrewed/activated and parking brakes applied before switch-on.

Unichiller Operation Manual, Installation / Commissioning
Mounting
Indoor only, ≥300 lx, max 2000 m altitude, no ATEX zone

The unit is not explosion-protected and must not be installed or started in an ATEX zone. It is for indoor use only at an illuminance of at least 300 lx and up to 2000 m altitude; refrigerant charge versus room volume must be checked against the limit per m³ of ambient air.

Unichiller Operation Manual, Installation
Process Limits
Do not use acetone or polyglycol with the plastic pump

The plastic immersion pump is not resistant to acetone or polyglycols (depending on manufacturer). For freeze protection, mix water with glysantine or ethylene glycol rather than using pure water, and plan the fluid charge within the 3.8 l minimum filling and 1.7 l expansion volume.

Unichiller 015-H Technical Data, Specifications
Control & I/O
Configure power-failure response before unattended runs

The Pilot ONE allows the power-failure response to be set to OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling capacity when the OT trigger value is reached instead of switching off all poles — select the mode that matches the process risk.

Unichiller Operation Manual, Normal Operation / Safety
Maintenance
Refrigerant circuit work only by approved contractors

Any work on the coolant/refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The refrigerant is R-290 (A3, H220), flammable, which affects site safety classification and handling requirements.

Unichiller Operation Manual, Maintenance / Safety

Selection & Integration Q&A

When should I choose the 015-H rather than the 015w or an OLÉ variant?

Pick the 015-H for the standard build at 63 dB(A). Choose the 015w if 54 dB(A) noise matters more. OLÉ variants (015 OLÉ, 015-H OLÉ) are separate configurations; confirm their differences against the datasheet before substituting, since this card covers only the 015-H.

What must the external loop and its fittings provide to mate with this chiller?

The pump connection is G3/4 AG male, so hoses/fittings must match that thread and be counterheld at the maximum tightening torque. The loop must be externally closed, with the external Pt100 sensor placed in the process, and its pressure drop checked against 29 l/min at 1 bar (21 l/min at 0.5 bar).

What site conditions and duty limits apply to installing the 015-H?

Indoor only, ≥300 lx, max 2000 m altitude, ambient 5-40 °C, no ATEX zone, IP20 (protect from water). Allow 50-200 cm wall clearance per side for service and airflow. Cooling capacity is rated at 20 °C room temperature and drops as ambient rises, so verify the heat load at the actual site ambient.

What is not included in base delivery and what service does the unit require?

Single/two-phase units ship with a power cable and country-specific plug that must be specified at ordering; heat-transfer fluid and mating hoses are not part of the unit. Refrigerant-circuit work is restricted to approved refrigeration contractors; plan fluid preparation (water with glysantine or ethylene glycol) and periodic maintenance access per the manual.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 015-H Technical Data
Datasheet ·167,9 КБ ·2 pp.
View PDF