Peter Huber Kältemaschinenbau Unichiller 022-H OLÉ
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 022-H OLÉ

Peter Huber Kältemaschinenbau Unichiller 022-H OLÉ — Recirculating chillers with Noise level 65 dB.

The Unichiller 022-H OLÉ is an air-cooled, single-phase recirculating chiller with an immersion pump and OLED controller, rated for -10 to 100 °C in externally closed circuits. Its 2.2 kW cooling capacity at 15 °C falls to 1 kW at -10 °C, so heat loads must be checked at the actual working temperature. It serves as a compact process cooling source where a 220–240 V 1~ 50 Hz supply and 5–40 °C ambient are available.

Noise level
65 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Noise level, dBControllerSafety classTemperature range, °CInterfacePower supply
Unichiller 022-H OLÉ Current 65OLÉI / NFL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller 015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 015w-H OLÉ 54OLÉI / NFL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 017T 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017T-H 64Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 017Tw-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020T —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020T-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller 020Tw 60Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 020Tw-H 60Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 022-H 65Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 022w-H —Pilot ONEIII / FL-10–100——
Unichiller 022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller 025T 74Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025T-H 74Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025Tw-H —Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D230V 1~ 50Hz
Unichiller 025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller 025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller 025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P007 58Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208-240V 1~/2~ 50/60Hz
Unichiller P007-H —Pilot ONEIII / FL-20–100——
Unichiller P007-H OLÉ 58OLÉIII / FL-20–100USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P007 OLÉ 58OLÉI / NFL-20–40USB (Device), RS232 Inte208-240V 1~/2~ 50/60Hz
Unichiller P010 57Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P010-H 57Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010-H OLÉ 57OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P010 OLÉ 57OLÉI / NFL-20–40USB (Device), RS232 Inte110-120V 1~ 50/60Hz
Unichiller P010w —Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P010w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012 59Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D208V 2~ 60Hz
Unichiller P012-H 59Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012-H OLÉ 59OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012 OLÉ 59OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P012w-H —Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~/2~ 50/60Hz
Unichiller P012w-H OLÉ —OLÉIII / FL-20–100USB (Device), RS232 Inte208V 2~ 60Hz
Unichiller P012w OLÉ —OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~/2~ 50/60Hz
Unichiller P015 63Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015-H 63Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P015-H OLÉ 63OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015 OLÉ 63OLÉI / NFL-20–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P015w 54Pilot ONEI / NFL-20–40Ethernet, USB (Host u. D220-240V 1~/2~ 50Hz
Unichiller P015w-H 54Pilot ONEIII / FL-20–100Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P015w-H OLÉ 54OLÉIII / FL-20–100USB (Device), RS232 Inte220-240V 1~/2~ 50Hz
Unichiller P022 65Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H 65Pilot ONEI / NFL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022-H OLÉ 65OLÉI / NFL-10–100USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P022 OLÉ 65OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P022w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P022w-H 60Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P022w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz
Unichiller P025 64Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H 64Pilot ONEIII / FL-10–100Ethernet, USB (Host u. D220-240V 1~ 50Hz
Unichiller P025-H OLÉ 64OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025 OLÉ 64OLÉI / NFL-10–40USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w 60Pilot ONEI / NFL-10–40Ethernet, USB (Host u. D208-230V 1~/2~ 60Hz
Unichiller P025w-H OLÉ 60OLÉIII / FL-10–100USB (Device), RS232 Inte220-240V 1~ 50Hz
Unichiller P025w OLÉ 60OLÉI / NFL-10–40USB (Device), RS232 Inte208-230V 1~/2~ 60Hz

Full specifications

Core Performance & Functional Specifications
Noise level 65 dB(A)
Pump connection G3/4 AG male
Pump speed adjustable no
Pump type Immersion pump
Temperature range -10...100 °C
Dimensions, Weight & Mechanical Design
Weight 78 kg
Electrical, Power & Drive Specifications
Current consumption 15 A
Fuse rating 16 A
Power supply 220-240V 1~ 50Hz
Interfaces, Connections & Control
Controller OLÉ
Display resolution 0, 1 K
Digital interface USB (Device), RS232 Interface
Temperature display OLED Display
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Mounting
Maintain 50–200 cm side clearance for service access

Free-standing models require a wall clearance of 50 to 200 cm on either side to allow maintenance access and adequate air flow for the air-cooled condenser. Verify the installation footprint against this before positioning the 78 kg unit.

Unichiller Operation Manual, Installation
Electrical
Supply must stay within ±5% voltage and ±2% frequency

The chiller tolerates voltage deviation of ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed. Confirm site power quality before connection; the unit draws up to 15 A and requires a 16 A fuse on a 220–240 V 1~ 50 Hz supply.

Unichiller 022-H OLÉ Technical Data Sheet, Specifications
Process Limits
Externally closed circuits only; avoid acetone and polyglycols

The unit is designed for externally closed applications. The plastic immersion pump is not resistant to acetone or polyglycols, so these media must be avoided or a more resistant pump specified. For operation near or below 0 °C, mix water with glysantine or ethylene glycol for freeze protection.

Unichiller Operation Manual, Function Description; Technical Data Sheet
Cooling & Media
Cooling capacity depends on setpoint and ambient temperature

Capacity falls from 2.2 kW at 15 °C to 1.6 kW at 0 °C and 1 kW at -10 °C. Datasheet output data are valid at 20 °C room temperature; if ambient rises toward the 40 °C limit, available cooling capacity may drop further, so size the heat load at the actual working temperature.

Unichiller 022-H OLÉ Technical Data Sheet, Specifications
Control & I/O
Configure power-failure response and Process Safety before run

The Pilot ONE allows power-failure response OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles; select the mode that matches the process risk before commissioning.

Unichiller Operation Manual, Normal Operation / Safety
Maintenance
Refrigerant circuit work only by approved contractors

Any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The unit contains R-449A (A1, H280) with 0.59 kg charge and 0.8 t CO2 equivalent; observe refrigerant quantity and room size at installation to avoid exceeding the limit per m³ of ambient air.

Unichiller Operation Manual, Maintenance / Installation

Selection & Integration Q&A

When should I choose the Unichiller 022-H OLÉ instead of the 015-series siblings?

Choose the 022-H OLÉ when you need the higher cooling capacity of this frame (2.2 kW at 15 °C, 1 kW at -10 °C) and the OLÉ controller with OLED display. The 015 siblings are rated 63 dB(A) versus 65 dB(A) here; select a 015 variant if its capacity meets the load and lower noise matters.

What supply and protection must be provided for the 022-H OLÉ, and what plug is supplied?

Provide 220–240 V 1~ 50 Hz with max. 15 A current and a 16 A fuse; voltage tolerance is ±5% with simultaneous ±2% frequency tolerance, and certain combinations are not allowed. Single-phase devices ship with a power cable and country-specific plug that must be specified at ordering.

What installation environment and duty limits apply to this chiller?

Install indoors only, not in an ATEX zone, at ≥300 lx and up to 2000 m altitude, with ambient 5–40 °C. Maintain 50–200 cm side clearance for maintenance. Activate leveling feet/parking brakes before start-up, and shut off cooling water even for overnight downtimes.

What maintenance and consumables are required, and what is not included in base delivery?

Refrigerant circuit work must be done by approved refrigeration/air-conditioning contractors. For freeze protection, mix water with glysantine or ethylene glycol; the plastic pump is not resistant to acetone or polyglycols. The country-specific plug must be specified at ordering; no other accessories are listed in the provided facts.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 022-H OLÉ Technical Data Sheet
Datasheet ·95,8 КБ ·2 pp.
View PDF