Peter Huber Kältemaschinenbau Unichiller 160Tw
Peter Huber Kältemaschinenbau Unichiller 160Tw — Recirculating chillers with Noise level 65 dB.
The Unichiller 160Tw is a water-cooled recirculating chiller with a 96 l/min pump and 10 l expansion volume, operating from -20 to 40 °C. It is the low-noise (65 dB(A)) variant in the series, distinguished from the 110T/110T-H siblings (74 dB(A)). It serves externally closed cooling circuits requiring a 400 V 3~ supply and G1 1/4 pump connection.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Pump type | Safety class | Temperature range, °C | Power supply | Expansion volume, m³ | Minimum fill volume, m³ |
|---|---|---|---|---|---|---|
| Unichiller 160Tw Current | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.01 | — |
| Unichiller 110T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 130T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 160T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 180Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 180w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180w-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 200T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 200Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 210T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 230-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w-H | E1 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller 250T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 260T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 260Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 300T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 300T-H | D3 | III / FL | -20–100 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 300Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 300Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 350T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 350Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 500Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 700Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 800Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller GL 1000w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.05 | — |
| Unichiller GL 200w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 250w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 300w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 400w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 750w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.05 | — |
| Unichiller P180 | E2 | I / NFL | -20–40 | — | 0.048 | 0.018 |
| Unichiller P180-H | E2 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w | E2 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230 | E2 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
Full specifications
| Noise level | 65 dB(A) |
| Expansion volume | 10 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | C3 |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Weight | 225 kg |
| Current consumption | 12 A (max.) |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G3/4 male |
| Cooling water consumption | 133 л/час (at 15°C, flow -10°C) at 15°C, flow 0°C: 320 l/h · at 15°C, flow 15°C: 600 l/h |
| Cooling water differential pressure | 1 bar (min.) |
| Cooling Water Pressure | 6 bar (max.) |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- Water-cooled refrigeration circuit using R-449A (2.1 kg charge, GWP 1397, 2.9 t CO2e) with an atmospheric open expansion tank.
- Pump type C3 delivers up to 96 l/min at 5.6 bar maximum; pump speed is not adjustable.
- Compared with siblings Unichiller 110T and 110T-H (74 dB(A)), this 160Tw and the 110Tw/110Tw-H share a 65 dB(A) noise level, making the 160Tw the quieter option among the 110T variants.
- Intended only for externally closed applications; models with “P” in the model name are preferred for high pressure-drop loops.
Behavior under load and media
- Temperature range -20 to 40 °C; cooling water inlet must be 5 to 20 °C. Cooling power ratings are valid at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure; higher cooling water temperature reduces cooling power and increases required flow.
- Cooling water consumption at 15 °C inlet: 133 l/h at -10 °C flow, 320 l/h at 0 °C, 600 l/h at 15 °C.
- Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM; only compatible water may be used.
- Minimum filling capacity 6.5 l; expansion volume 10 l.
Installation, control and operation
- Pilot ONE controller with Ethernet, USB (Host and Device) and RS232 interfaces; external Pt100 sensor connection.
- Power supply 400 V 3~ 50 Hz, max. current 12 A, fusing 3x16 A; three-phase devices under 63 A are supplied with cable but without plug.
- Protection IP20; ambient temperature 5 to 40 °C; indoor use only, illuminance at least 300 lx, altitude up to 2000 m.
- Cooling water connections G3/4 male; pump connection G1 1/4 AG male; cooling water pressure min. 1 bar differential, max. 6 bar.
- Power-failure response configurable (OFF/Standby, ON, Power Failure Auto); Process Safety mode releases maximum cooling on overtemperature trigger.
Integration & Operating Notes
Free-standing models require a wall clearance of 50 to 200 cm on either side to allow maintenance and service access. Plan the installation footprint accordingly, and ensure the unit is indoors with illuminance of at least 300 lx and at an altitude not exceeding 2000 m.
The unit draws up to 12 A per phase at 400 V 3~ 50 Hz and requires 3x16 A fusing. Three-phase devices with current consumption below 63 A are delivered with cable but without a plug, so the installer must provide a compatible plug and connection. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%; combinations such as -5% voltage with +2% frequency are not allowed.
The chiller is designed for cooling water intake between 5 °C and 20 °C, with a minimum differential pressure of 1 bar and a maximum pressure of 6 bar. Higher cooling water temperature reduces cooling power and may require increased flow rate. Insulate pipes if water temperature can fall below the condensation point.
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Ensure the cooling water is chemically compatible with these materials to avoid corrosion or damage. The unit is intended for externally closed applications only.
Shut off the cooling water supply to the unit even for shorter downtimes such as overnight to prevent water damage and corrosion. Also protect electrical lines directly below the unit against liquid ingress from condensation.
The Pilot ONE allows the power-failure response to be set to OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached instead of switching off all poles. Select the mode that matches the process risk.
Work on the refrigerant circuit must only be carried out by approved refrigeration/air-conditioning system contractors. The unit uses R-449A with a charge of 2.1 kg; observe the refrigerant quantity and room size to avoid exceeding the limit per m³ of ambient air.
Selection & Integration Q&A
Choose the 160Tw when lower noise (65 dB(A) vs 74 dB(A) for 110T/110T-H) is required. The 110T variants offer higher cooling capacity but are louder. The 160Tw is also water-cooled and suited to externally closed circuits; for high pressure-drop loops, consider a model with “P” in the name.
Cooling water: 5–20 °C inlet, 1 bar min. differential, 6 bar max., G3/4 male connections. Process circuit: G1 1/4 AG male pump connection, externally closed loop, min. filling 6.5 l, expansion volume 10 l. Ensure water compatibility with copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.
Install indoors only, at 5–40 °C ambient, illuminance ≥300 lx, altitude ≤2000 m. Maintain 50–200 cm side clearance for maintenance. Do not install in an ATEX zone. Leveling feet or parking brakes must be engaged before start-up. Protect electrical lines below the unit from condensation.
The unit is delivered with cable but without a plug for three-phase supply; provide a suitable 3x16 A plug. Refrigerant circuit work must be by certified contractors. Shut off cooling water during downtimes. No specific maintenance intervals are stated in the provided documents; follow the manual’s maintenance section.