Peter Huber Kältemaschinenbau Unichiller 600Tw
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 600Tw

Peter Huber Kältemaschinenbau Unichiller 600Tw — Recirculating chillers.

The Unichiller 600Tw is a water-cooled recirculating chiller rated at 60 kW with R-449A refrigerant, operating from -20 to 40 °C. It is the large-capacity member of the Unichiller series, distinguished by its 400 V three-phase supply and 45 A draw. It serves externally closed process loops requiring high cooling capacity and a stable temperature setpoint.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Pump typeSafety classTemperature range, °CPower supplyExpansion volume, m³Minimum fill volume, m³
Unichiller 600Tw Current D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 110T C3I / NFL-10–40400V 3~ 50Hz0.007—
Unichiller 110T-H C3III / FL-10–100400V 3~ 50Hz0.007—
Unichiller 110Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 130T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 130T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 130Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 160T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 160T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 160Tw C3I / NFL-20–40400V 3~ 50Hz0.01—
Unichiller 180-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 180T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 180T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 180Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 180Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 180w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 180w-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 200T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 200Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 210T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 210T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 210Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 230-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 230w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 230w-H E1III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller 250T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 250T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 250Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 260T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 260T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 260Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 260Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 300T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 300T-H D3III / FL-20–100460V 3~ 60Hz0.0390.014
Unichiller 300Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 300Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 350T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 350Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 500Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw-H D3III / FL-20–100400V 3~ 50Hz0.007—
Unichiller 700Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 800Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller GL 1000w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.05—
Unichiller GL 200w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 250w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 300w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 400w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 750w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.05—
Unichiller P180 E2I / NFL-20–40—0.0480.018
Unichiller P180-H E2III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller P180w E2I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller P180w-H E2III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller P230 E2I / NFL-20–40460V 3~ 60Hz0.0480.018
Unichiller P230-H E2III / FL-20–100460V 3~ 60Hz0.0480.018

Full specifications

Core Performance & Functional Specifications
Expansion volume 7 l
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type D3
External sensor connection Pt100
Temperature range -20...40 °C
Dimensions, Weight & Mechanical Design
Weight 598 kg
Electrical, Power & Drive Specifications
Current consumption 45 A (max)
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1 1/4 male
Cooling Water Pressure 6 bar (max)
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior under load and media

Installation, connection and control

Integration & Operating Notes

Electrical
Provide a 3x50 A fuse and a suitable plug on site

The unit draws up to 45 A at 400 V 3~ 50 Hz and is delivered with cable but without a plug. The installer must provide a 3x50 A protection device and a matching plug; voltage and frequency tolerances are ±5% and ±2%, but the combination of -5% voltage with +2% frequency is not permitted.

Unichiller 600Tw Datasheet, page 2
Process Limits
Cooling water must be 5–20 °C with ≥1.5 bar differential

The chiller requires cooling water with a differential pressure of at least 1.5 bar and a maximum supply pressure of 6 bar. Intake temperature must be between 5 and 20 °C; capacity drops as water temperature rises. Pipes must be insulated if the water temperature can fall below the condensation point.

Unichiller 600Tw Datasheet, pages 1–2
Mounting
Keep 50–200 cm clearance per side and secure the unit

A wall clearance of 50 to 200 cm per side is required for maintenance. Before switching on, parking brakes must be activated at the casters and/or leveling feet unscrewed/activated to prevent movement. The unit must be installed indoors at 5–40 °C ambient and at least 300 lx illuminance.

Unichiller Operation Manual, pages 25 and 31
Safety
Configure power-failure response and overtemperature mode

The Pilot ONE allows the power-failure response to be set as OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles; this must be selected according to the process risk.

Unichiller Operation Manual, pages 18–19
Maintenance
Refrigerant circuit work only by approved contractors

Work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A with a GWP of 1397 and a CO2 equivalent of 8.4 t, so leak checks and environmental reporting obligations apply. Cooling water supply must be shut off even for short downtimes such as overnight.

Unichiller Operation Manual, pages 17 and 28
Process Limits
Externally closed applications only; no ATEX zones

The unit is designed only for externally closed applications and must not be installed or started up inside an ATEX zone because it is not explosion-protected. The refrigerant charge and room size must be checked at installation to avoid exceeding the refrigerant limit per m³ of ambient air.

Unichiller Operation Manual, pages 13, 15 and 34

Selection & Integration Q&A

When should I choose the Unichiller 600Tw instead of a smaller sibling like the 110Tw?

Choose the 600Tw when you need 60 kW cooling capacity at 15 °C water and a three-phase 400 V supply with 45 A draw. The 110Tw is smaller; the 600Tw is water-cooled and requires a facility cooling-water circuit with ≥1.5 bar differential pressure.

What are the requirements for the cooling-water circuit and electrical supply when integrating this chiller?

Cooling water: 5–20 °C intake, ≥1.5 bar differential, max 6 bar supply, G1 1/4 male connections. Electrical: 400 V 3~ 50 Hz, 45 A max, 3x50 A fuse, cable supplied without plug. Voltage/frequency tolerances ±5%/±2%, but -5% voltage with +2% frequency is not allowed.

What mounting and environmental limits apply to the 600Tw?

Install indoors only, at 5–40 °C ambient, ≥300 lx illuminance, up to 2000 m altitude. Keep 50–200 cm wall clearance per side. Activate parking brakes or leveling feet before operation. Do not install in an ATEX zone. Protect electrical lines below the unit from condensation.

What maintenance and service requirements should I plan for, and what is not included in the base delivery?

Refrigerant circuit work must be done by approved contractors; R-449A has GWP 1397 and CO2e 8.4 t. Shut off cooling water even overnight. The unit is delivered with cable but without a plug; the 3x50 A fuse and plug are site-provided. Minimum filling capacity is 12.7 l; expansion volume 7 l.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller 600Tw Datasheet
Datasheet ·94,0 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF