Peter Huber Kältemaschinenbau Unichiller 230-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 230-H

Peter Huber Kältemaschinenbau Unichiller 230-H — Recirculating chillers.

The Unichiller 230-H is an air-cooled, externally closed recirculating chiller with a 54 l/min E1 pump, G1 1/4 male connections and a -20…100 °C working range. Within the Unichiller series it is the 230-size, high-capacity modification, distinguished by 23 kW cooling at 20 °C falling to 5.5 kW at -20 °C. It serves closed process loops requiring stable temperature control with Pilot ONE and adjustable DIN 12876 overtemperature protection.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Pump typeSafety classTemperature range, °CPower supplyExpansion volume, m³Minimum fill volume, m³
Unichiller 230-H Current E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 110T C3I / NFL-10–40400V 3~ 50Hz0.007—
Unichiller 110T-H C3III / FL-10–100400V 3~ 50Hz0.007—
Unichiller 110Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 130T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 130T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 130Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 160T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 160T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 160Tw C3I / NFL-20–40400V 3~ 50Hz0.01—
Unichiller 180-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 180T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 180T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 180Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 180Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 180w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 180w-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 200T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 200Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 210T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 210T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 210Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 230w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 230w-H E1III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller 250T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 250T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 250Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 260T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 260T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 260Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 260Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 300T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 300T-H D3III / FL-20–100460V 3~ 60Hz0.0390.014
Unichiller 300Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 300Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 350T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 350Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 500Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw-H D3III / FL-20–100400V 3~ 50Hz0.007—
Unichiller 700Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 800Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller GL 1000w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.05—
Unichiller GL 200w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 250w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 300w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 400w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 750w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.05—
Unichiller P180 E2I / NFL-20–40—0.0480.018
Unichiller P180-H E2III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller P180w E2I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller P180w-H E2III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller P230 E2I / NFL-20–40460V 3~ 60Hz0.0480.018
Unichiller P230-H E2III / FL-20–100460V 3~ 60Hz0.0480.018

Full specifications

Core Performance & Functional Specifications
Expansion volume 48 l
Heating capacity 2 kW
Minimum fill volume 18 l
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type E1
External sensor connection Pt100
Temperature range -20...100 °C
Dimensions, Weight & Mechanical Design
Weight 477 kg
Electrical, Power & Drive Specifications
Current consumption 14 A
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Electrical
Site must supply 400 V 3~ with 16 A protection per phase

The 14 A three-phase load requires a 16 A fuse per phase and a site-fitted plug, since units below 63 A ship with cable only. Voltage and frequency tolerances are coupled: ±5 % voltage only with ±2 % frequency, and -5 % voltage with +2 % frequency is not allowed.

Unichiller 230-H Technical Datasheet, page 2
Process Limits
Size the load at the coldest operating point, not at 20 °C

Cooling capacity falls from 23 kW at 20 °C to 5.5 kW at -20 °C, and the datasheet ratings assume 20 °C room temperature. A process sized on the 20 °C figure will be undercooled at low temperature or in a warm room approaching the 40 °C ambient limit.

Unichiller 230-H Technical Datasheet, page 1
Process Limits
Match external loop pressure drop to the pump curve

The E1 pump delivers 54 l/min at zero head but only 11 l/min at 3.0 bar, and pump speed is not adjustable. The external circuit must be designed so its pressure drop leaves sufficient flow; models with 'P' in the name are the alternative for high-pressure-drop applications.

Unichiller 230-H Technical Datasheet, page 1; Unichiller Operation Manual, page 34
Mounting
Keep 50–200 cm wall clearance per side for maintenance

Free-standing units require 50 to 200 cm clearance on either side, and the air-cooled condenser needs sufficient free space to avoid derating. The unit is IP20 and must be installed indoors, dry, at 5–40 °C ambient and at least 300 lx illuminance, up to 2000 m altitude.

Unichiller Operation Manual, page 25; Unichiller 230-H Technical Datasheet, page 2
Mounting
Not permitted inside an ATEX zone

The chiller is not explosion-protected and must not be installed or started up within an ATEX zone. Refrigerant charge (1.49 kg R-449A) must also be checked against room volume to stay within the refrigerant limit per m³ of ambient air.

Unichiller Operation Manual, pages 13 and 15
Process Limits
Closed external circuit only; open baths are not valid

The unit is designed for externally closed applications, so the hydraulic circuit must be sealed. Minimum filling capacity is 18 l with 48 l expansion volume, which sets the fluid charge and expansion allowance for the loop.

Unichiller Operation Manual, page 34; Unichiller 230-H Technical Datasheet, page 1
Control & I/O
Configure power-failure response and OT mode before commissioning

The Pilot ONE allows OFF/Standby, ON or Power Failure Auto after a mains failure, and Process Safety mode releases maximum cooling at the OT trigger instead of switching off all poles. For exothermic processes the OT trigger and mode must be set deliberately, not left at default.

Unichiller Operation Manual, pages 18–19
Maintenance
Refrigerant circuit work only by approved contractors

Any work on the coolant/refrigerant circuit must be carried out by approved refrigeration and air-conditioning system contractors. R-449A is A1 with GHS H280, so leak checks, labelling and F-gas reporting obligations apply to the 1.49 kg charge.

Unichiller Operation Manual, page 17; Unichiller 230-H Technical Datasheet, page 1
Electrical
Industrial EMC class may need extra measures in residential areas

The unit is classified EN55011 Class A Group 1, which is the industrial disturbance class. Installation near residential or light-industrial sensitive equipment may require additional EMC measures, and electrical lines below the unit must be protected against condensate ingress.

Unichiller 230-H Technical Datasheet, page 2; Unichiller Operation Manual, page 28

Selection & Integration Q&A

When should I choose the Unichiller 230-H instead of a 110T or 110Tw sibling?

Pick the 230-H when the process needs the larger 230-size capacity (23 kW at 20 °C, 5.5 kW at -20 °C) and a 54 l/min pump. Choose a 110Tw variant when low noise (65 dB(A)) matters more than capacity; the 110T is 74 dB(A).

What must the external hydraulic circuit and electrical supply provide for this chiller?

A sealed external loop with G1 1/4 male mating fittings, at least 18 l fill and pressure drop compatible with 54 l/min at zero head / 11 l/min at 3.0 bar. Supply is 400 V 3~ 50 Hz, 14 A, 16 A fuse per phase; the plug is not included.

What installation environment and duty limits does the manual impose?

Indoors only, 5–40 °C ambient, at least 300 lx, up to 2000 m altitude, IP20, no ATEX zone, 50–200 cm wall clearance per side. Cooling capacity is rated at 20 °C room temperature and drops as ambient rises.

What maintenance and accessories are required beyond the base delivery?

Refrigerant work only by approved contractors; R-449A charge 1.49 kg subject to leak checks and F-gas reporting. The unit ships with cable but no plug, so the site plug is a required extra; leveling feet/parking brakes must be set before start-up.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller 230-H Technical Datasheet
Datasheet ·200,1 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF