Peter Huber Kältemaschinenbau Unichiller 110Tw
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 110Tw

Peter Huber Kältemaschinenbau Unichiller 110Tw — Recirculating chillers with Noise level 65 dB.

The Unichiller 110Tw is a water-cooled recirculating chiller designed for externally closed applications. It operates from -20 to 40 °C using the Pilot ONE controller and a fixed-speed C3 pump. Its 65 dB(A) noise level distinguishes it from the 74 dB(A) siblings, making it suitable for noise-sensitive installations.

Noise level
65 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Pump typeSafety classTemperature range, °CPower supplyExpansion volume, m³Minimum fill volume, m³
Unichiller 110Tw Current C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 110T C3I / NFL-10–40400V 3~ 50Hz0.007—
Unichiller 110T-H C3III / FL-10–100400V 3~ 50Hz0.007—
Unichiller 130T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 130T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 130Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 160T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 160T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 160Tw C3I / NFL-20–40400V 3~ 50Hz0.01—
Unichiller 180-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 180T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 180T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 180Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 180Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 180w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 180w-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 200T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 200Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 210T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 210T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 210Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 230-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 230w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 230w-H E1III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller 250T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 250T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 250Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 260T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 260T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 260Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 260Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 300T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 300T-H D3III / FL-20–100460V 3~ 60Hz0.0390.014
Unichiller 300Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 300Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 350T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 350Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 500Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw-H D3III / FL-20–100400V 3~ 50Hz0.007—
Unichiller 700Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 800Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller GL 1000w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.05—
Unichiller GL 200w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 250w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 300w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 400w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 750w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.05—
Unichiller P180 E2I / NFL-20–40—0.0480.018
Unichiller P180-H E2III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller P180w E2I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller P180w-H E2III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller P230 E2I / NFL-20–40460V 3~ 60Hz0.0480.018
Unichiller P230-H E2III / FL-20–100460V 3~ 60Hz0.0480.018

Full specifications

Core Performance & Functional Specifications
Noise level 65 dB(A)
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type C3
External sensor connection Pt100
Temperature range -20...40 °C
Dimensions, Weight & Mechanical Design
Weight 225 kg
Electrical, Power & Drive Specifications
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G3/4 male
Cooling water consumption 89 l/h (cooling water 15°C, flow -10°C)
cooling water 15°C, flow 0°C: 191 l/h · cooling water 15°C, flow 15°C: 400 l/h
Cooling water differential pressure 1 bar (min)
Cooling Water Pressure 6 bar (max)
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and positioning

Behavior under load and media

Installation, connection, and control

Integration & Operating Notes

Mounting
Maintain 50–200 cm side clearance for service access

Free-standing installation requires a wall clearance of 50 to 200 cm on either side to allow maintenance access. Insufficient clearance can prevent servicing of the refrigerant circuit and pump.

Unichiller Operation Manual, page 25
Electrical
Provide a 3x16 A fuse and a suitable plug on site

The unit draws up to 13.5 A at 400 V 3~ 50 Hz and requires a 3x16 A fuse. It is delivered with a cable but without a plug, so the installer must provide a compatible plug. Voltage and frequency tolerances are only valid in combination (±5% voltage with ±2% frequency).

Unichiller 110Tw Datasheet, page 2
Cooling & Media
Cooling water must be 5–20 °C and 1–6 bar

The cooling water supply must have a differential pressure between 1 and 6 bar and an intake temperature between 5 °C and 20 °C. Below the condensation point, internal cooling water pipes must be insulated. The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, so only compatible water may be used.

Unichiller 110Tw Datasheet, page 2
Process Limits
Use only in externally closed applications

The unit is designed for externally closed circuits. Open baths or circuits that do not suit the expansion tank design must not be used. The minimum filling capacity is 6.5 l, and the expansion volume is 5.5 l.

Unichiller 110Tw Datasheet, page 1
Operation
Configure power-failure response to match process risk

The Pilot ONE controller allows the power-failure response to be set to OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached, instead of switching off all poles.

Unichiller Operation Manual, pages 18–19
Maintenance
Refrigerant circuit work requires certified contractors

Work on the refrigerant circuit must only be performed by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A with a GWP of 1397 and a charge of 1.75 kg (2.4 t CO2e), so F-gas regulations apply.

Unichiller Operation Manual, page 17; Datasheet page 1
Operation
Shut off cooling water during downtimes

The cooling water supply must be shut off even for short downtimes such as overnight to prevent water damage and corrosion.

Unichiller Operation Manual, page 28

Selection & Integration Q&A

When should I choose the Unichiller 110Tw over the 110T or 110Tw-H?

Choose the 110Tw when water cooling is available and low noise (65 dB(A)) is required. The 110T is air-cooled and louder (74 dB(A)). The 110Tw-H adds a heater for higher temperature control but has the same noise level.

What are the requirements for the cooling water supply and the process circuit connections?

Cooling water: 5–20 °C, differential pressure 1–6 bar, connection G3/4 male. Process circuit: pump connections G1 1/4 male, minimum filling volume 6.5 l, expansion volume 5.5 l. Ensure water quality is compatible with copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM.

What are the mounting and ambient limits for the 110Tw?

Install indoors only, at 5–40 °C ambient, with 50–200 cm side clearance for maintenance. Leveling feet must be extended and parking brakes applied. Do not install in ATEX zones. Electrical lines below the unit must be protected from liquid ingress.

What maintenance is required and what accessories are needed but not included?

Refrigerant circuit work must be by certified contractors. Shut off cooling water during downtimes. A plug for the 400 V cable must be provided on site. No other accessories are specified in the provided documents.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 110Tw Datasheet
Datasheet ·79,9 КБ ·2 pp.
View PDF