Peter Huber Kältemaschinenbau Unichiller GL 300w
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller GL 300w

Peter Huber Kältemaschinenbau Unichiller GL 300w — Recirculating chillers.

The Unichiller GL 300w is a water-cooled recirculating chiller with a 30 l expansion volume, a fixed-speed pressure pump delivering up to 100 l/min at 3.5 bar, and a -20…40 °C working range. It is the water-cooled GL variant in the Unichiller series, distinguished from air-cooled siblings by its G3/4 cooling-water circuit. It serves externally closed process loops requiring stable temperature control with Pilot ONE electronics.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Pump typeSafety classTemperature range, °CPower supplyExpansion volume, m³Minimum fill volume, m³
Unichiller GL 300w Current Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller 110T C3I / NFL-10–40400V 3~ 50Hz0.007—
Unichiller 110T-H C3III / FL-10–100400V 3~ 50Hz0.007—
Unichiller 110Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 130T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 130T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 130Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 160T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 160T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 160Tw C3I / NFL-20–40400V 3~ 50Hz0.01—
Unichiller 180-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 180T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 180T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 180Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 180Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 180w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 180w-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 200T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 200Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 210T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 210T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 210Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 230-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 230w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 230w-H E1III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller 250T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 250T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 250Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 260T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 260T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 260Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 260Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 300T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 300T-H D3III / FL-20–100460V 3~ 60Hz0.0390.014
Unichiller 300Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 300Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 350T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 350Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 500Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw-H D3III / FL-20–100400V 3~ 50Hz0.007—
Unichiller 700Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 800Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller GL 1000w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.05—
Unichiller GL 200w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 250w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 400w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 750w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.05—
Unichiller P180 E2I / NFL-20–40—0.0480.018
Unichiller P180-H E2III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller P180w E2I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller P180w-H E2III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller P230 E2I / NFL-20–40460V 3~ 60Hz0.0480.018
Unichiller P230-H E2III / FL-20–100460V 3~ 60Hz0.0480.018

Full specifications

Core Performance & Functional Specifications
Expansion volume 30 l
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type Pressure pump, speed not variable
External sensor connection Pt100
Temperature range -20...40 °C
Electrical, Power & Drive Specifications
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G3/4 male
Cooling water differential pressure 1 bar (min)
Cooling Water Pressure 6 bar (max)
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior under load and media

Installation, connection and control

Integration & Operating Notes

Process Limits
Cooling-water inlet must stay within 5–20 °C

Operating with cooling-water inlet below 5 °C or above 20 °C is outside the design range; lower temperatures require insulation of the cooling-water pipes to prevent condensation on the circuit and adjacent electrical lines.

Datasheet, page 2, operation
Process Limits
Cooling-water differential pressure 1–6 bar at G3/4 connection

The supply must provide at least 1 bar differential pressure to achieve design flow, and must never exceed 6 bar at the connection; exceeding the maximum risks damage to the cooling-water circuit and connections.

Datasheet, page 1, installation
Electrical
Three-phase unit delivered with cable but no plug

Because current consumption is below 63 A, the unit ships with a cable only; the installer must provide a suitable plug or hardwired connection rated for the 400 V 3~ 50 Hz supply.

Datasheet, page 2, installation
Mounting
Maintain 50–200 cm side clearance for service access

Free-standing models require this wall clearance on either side to allow maintenance access; also verify room volume against the refrigerant charge on the rating plate to avoid exceeding the permissible refrigerant concentration per m³ of ambient air.

Operation Manual, page 25, installation
Mounting
Not permitted in ATEX zones; indoor use only

The unit is not explosion-protected and must not be installed or started inside an ATEX zone; it is for indoor use at illuminance of at least 300 lx and up to 2000 m altitude.

Operation Manual, page 13 and page 25, installation
Process Limits
Externally closed applications only

The hydraulic circuit must be designed as an externally closed loop; open baths or vented circuits are outside the intended application and may cause pump cavitation or overflow.

Operation Manual, page 34, selection
Maintenance
Refrigerant circuit work restricted to approved contractors

Any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors; the refrigerant is R-744 (CO2), safety group A1, GHS H280, UN 2857.

Operation Manual, page 17, maintenance
Maintenance
Shut off cooling water even for overnight downtime

Close the cooling-water supply to the unit during any downtime, including short overnight stops, to prevent water damage and corrosion in the cooling-water circuit.

Operation Manual, page 28, operation

Selection & Integration Q&A

When should I choose the Unichiller GL 300w instead of an air-cooled Unichiller 110T variant?

Choose the GL 300w when a cooling-water circuit with 1–6 bar differential pressure is available and the 30 l expansion volume and 100 l/min pump delivery suit the loop. Air-cooled 110T variants avoid water connections but are louder (74 dB(A) vs 65 dB(A) for water-cooled 110Tw).

What cooling-water supply and piping must be provided for the GL 300w?

Provide a cooling-water circuit with G3/4 male mating connections, differential pressure between 1 and 6 bar, and inlet temperature 5–20 °C. Use water compatible with copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM; insulate pipes if inlet is below 5 °C.

What installation environment and clearance does the manual require?

Indoor use only, 5–40 °C ambient, at least 300 lx illuminance, up to 2000 m altitude, not in an ATEX zone. Free-standing models need 50–200 cm wall clearance per side; engage leveling feet or parking brakes before start-up and protect electrical lines below the unit from condensation.

What is not included in the base delivery and what service access is restricted?

The three-phase unit ships with a cable but no plug; the installer must provide a suitable plug or hardwired connection. Refrigerant-circuit work is restricted to approved refrigeration contractors. Shut off cooling water during any downtime, including overnight.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller GL 300w
Datasheet ·30,3 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF