Peter Huber Kältemaschinenbau Unichiller GL 200w
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller GL 200w

Peter Huber Kältemaschinenbau Unichiller GL 200w — Recirculating chillers.

The Unichiller GL 200w is a water-cooled recirculating chiller with a natural R-744 refrigerant circuit, rated 20 kW at 19 °C and operating from -20 to 40 °C. It is the 200-series GL modification in the Unichiller line, distinguished by a 460 V three-phase supply and G3/4 cooling-water connections. It serves externally closed process loops requiring stable cooling with Pilot ONE control.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Pump typeSafety classTemperature range, °CPower supplyExpansion volume, m³Minimum fill volume, m³
Unichiller GL 200w Current Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller 110T C3I / NFL-10–40400V 3~ 50Hz0.007—
Unichiller 110T-H C3III / FL-10–100400V 3~ 50Hz0.007—
Unichiller 110Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 130T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 130T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 130Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 160T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 160T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 160Tw C3I / NFL-20–40400V 3~ 50Hz0.01—
Unichiller 180-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 180T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 180T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 180Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 180Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 180w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 180w-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 200T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 200Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 210T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 210T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 210Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 230-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 230w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 230w-H E1III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller 250T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 250T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 250Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 260T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 260T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 260Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 260Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 300T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 300T-H D3III / FL-20–100460V 3~ 60Hz0.0390.014
Unichiller 300Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 300Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 350T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 350Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 500Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw-H D3III / FL-20–100400V 3~ 50Hz0.007—
Unichiller 700Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 800Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller GL 1000w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.05—
Unichiller GL 250w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 300w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 400w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 750w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.05—
Unichiller P180 E2I / NFL-20–40—0.0480.018
Unichiller P180-H E2III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller P180w E2I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller P180w-H E2III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller P230 E2I / NFL-20–40460V 3~ 60Hz0.0480.018
Unichiller P230-H E2III / FL-20–100460V 3~ 60Hz0.0480.018

Full specifications

Core Performance & Functional Specifications
Expansion volume 30 l
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type Pressure pump, speed not variable
External sensor connection Pt100
Temperature range -20...40 °C
Electrical, Power & Drive Specifications
Power supply 460V 3~ 60Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling capacity 20 kW (at 19 °C)
Cooling water connection G3/4 male
Cooling water differential pressure 1 bar (min.)
Cooling Water Pressure 6 bar (max.)
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior and operating envelope

Control, installation and operation

Integration & Operating Notes

Electrical
460 V three-phase supply with tight combined tolerance

The site must provide 460 V 3~ 60 Hz; voltage tolerance of ±5% is permitted only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed. Verify the supply before ordering, since a transformer or a different model may be needed.

Unichiller GL 200w Datasheet, Specifications
Electrical
External UL 489 branch protection and no plug supplied

External branch circuit protection according to UL 489 is required. Three-phase devices drawing less than 63 A are supplied with cable but without a plug, so the installer must provide a suitable plug or hard-wired connection.

Unichiller GL 200w Datasheet, Specifications
Process Limits
Cooling water 5–20 °C intake with 1–6 bar differential

The cooling-water circuit needs at least 1 bar differential pressure and must not exceed 6 bar. Intake temperature must stay between 5 °C and 20 °C; below the condensation point the internal cooling-water pipes must be insulated to prevent condensation.

Unichiller GL 200w Datasheet, Specifications
Mounting
Indoor dry location with 50–200 cm side clearance

IP20 protection and the manual require a dry indoor site with at least 300 lx illuminance and altitude up to 2000 m. Free-standing models need 50–200 cm wall clearance per side for maintenance, and electrical lines directly below the unit must be protected against liquid ingress from condensation.

Unichiller Operation Manual, Setup Mode
Mounting
Secure the unit before start-up and shut off cooling water

Parking brakes must be activated at the casters and/or leveling feet unscrewed before the unit is put into operation. Shut off the cooling water supply even for short downtimes such as overnight to prevent water damage and corrosion.

Unichiller Operation Manual, Commissioning
Control & I/O
Configure power-failure response for the process risk

The Pilot ONE allows the power-failure response to be set as OFF/Standby, ON or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles.

Unichiller Operation Manual, Normal Operation
Maintenance
Refrigerant circuit work restricted to approved contractors

Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The unit is classified to DIN 12876 with identification depending on whether the thermal fluid is combustible, so confirm the fluid before service.

Unichiller Operation Manual, Maintenance
Process Limits
Externally closed loops only; no ATEX zone installation

The unit is designed for externally closed applications and must not be installed or started up inside an ATEX zone because it is not explosion-protected. Models with 'P' in the model name are the ones suited to high pressure-drop applications, not this GL variant.

Unichiller Operation Manual, Function Description

Selection & Integration Q&A

When should I choose the GL 200w instead of a sibling Unichiller 110T or 110Tw?

Choose the GL 200w for a 460 V/60 Hz site needing 20 kW at 19 °C with water cooling and R-744. The 110T is air-cooled at 74 dB(A); the 110Tw is water-cooled at 65 dB(A). Select by supply voltage, cooling-water availability and noise limit.

What must the cooling-water supply and process loop provide for this chiller?

Cooling water at 5–20 °C intake, 1 bar minimum differential pressure and 6 bar maximum, with G3/4 male connections. The process loop must be externally closed and connect to G1 1/4 AG male pump ports; the pump is fixed-speed.

What installation environment and duty-cycle limits apply?

Install indoors only, dry, at 5–40 °C ambient, at least 300 lx, up to 2000 m altitude, with 50–200 cm side clearance. IP20 rules out wet areas; no ATEX zone. Shut off cooling water even overnight and secure casters or leveling feet before start-up.

What is not included in base delivery and what service access is required?

No plug is supplied for three-phase units below 63 A; the installer provides a plug or hard-wired connection plus UL 489 branch protection. Refrigerant-circuit service requires approved refrigeration contractors; confirm the DIN 12876 fluid class before maintenance.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller GL 200w Datasheet
Datasheet ·30,4 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF