Peter Huber Kältemaschinenbau Unichiller 130T
Peter Huber Kältemaschinenbau Unichiller 130T — Recirculating chillers with Noise level 74 dB.
The Unichiller 130T is an air-cooled, three-phase recirculating chiller rated for -10 to 40 °C with a Pilot ONE controller and a fixed-speed C3 pump. It is the 130-size member of the Unichiller series, distinguished from the 110T siblings by its larger capacity and 12 A current draw. It serves externally closed process loops requiring G1 1/4 connections and a minimum 14 l fill.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Pump type | Safety class | Temperature range, °C | Power supply | Expansion volume, m³ | Minimum fill volume, m³ |
|---|---|---|---|---|---|---|
| Unichiller 130T Current | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 110T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 130T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 160T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.01 | — |
| Unichiller 180-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 180Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 180w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180w-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 200T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 200Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 210T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 230-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w-H | E1 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller 250T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 260T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 260Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 300T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 300T-H | D3 | III / FL | -20–100 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 300Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 300Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 350T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 350Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 500Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 700Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 800Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller GL 1000w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.05 | — |
| Unichiller GL 200w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 250w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 300w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 400w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 750w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.05 | — |
| Unichiller P180 | E2 | I / NFL | -20–40 | — | 0.048 | 0.018 |
| Unichiller P180-H | E2 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w | E2 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230 | E2 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
Full specifications
| Noise level | 74 dB(A) |
| Expansion volume | 39 l |
| Minimum fill volume | 14 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | C3 |
| External sensor connection | Pt100 |
| Temperature range | -10...40 °C |
| Weight | 494 kg |
| Current consumption | 12 A |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- Air-cooled refrigeration circuit using R-449A (A1, H280; CO2 equivalent 6.1 t) with a 400 V 3~ 50 Hz supply and 12 A current consumption.
- Fixed-speed pump type C3 with G1 1/4 AG male connections; pump speed is not adjustable.
- 39 l expansion volume and 14 l minimum fill volume define the hydraulic envelope.
- Compared with the Unichiller 110T and 110T-H siblings (74 dB(A)), the 130T shares the same 74 dB(A) sound pressure level but is the larger-capacity modification; the 110Tw variants are quieter at 65 dB(A).
Behavior and operating envelope
- Temperature range -10 to 40 °C; temperature stability at -10 °C is 0.5 K.
- Cooling capacity is rated at 20 °C room temperature and may drop as ambient temperature rises; the permissible ambient range is 5 to 40 °C.
- The unit is designed for externally closed applications only; models with “P” in the model name are the ones suited to high pressure-drop loops, which the 130T is not.
- Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles.
Installation, control and operation
- Pilot ONE controller with Ethernet, USB (Host and Device) and RS232 interfaces; external Pt100 sensor connection.
- Power-failure response configurable as OFF/Standby, ON, or Power Failure Auto.
- Three-phase devices below 63 A are delivered with a cable but without a plug; the customer must provide and fit the plug.
- Voltage tolerance ±5% with simultaneous frequency tolerance ±2%; certain combinations are not allowed.
- IP20 enclosure requires protection from water and dust; indoor use only at ≥300 lx and up to 2000 m altitude.
- Wall clearance of 50 to 200 cm per side is required for maintenance on free-standing models; leveling feet or parking brakes must be activated before start-up.
Integration & Operating Notes
Air-cooled operation requires space around the unit; a wall clearance of 50 to 200 cm per side is required for maintenance on free-standing models. The IP20 enclosure must be kept free of water and dust ingress. The unit may only be used indoors at an illuminance of at least 300 lx and up to 2000 m altitude.
Selection & Integration Q&A
Pick the 130T when the process needs the larger 130-size capacity and a 12 A three-phase draw; the 110T/110T-H share the 74 dB(A) level but are smaller. Choose a 110Tw variant if 65 dB(A) acoustic output is required.
The loop must be externally closed with at least 14 l fill and 39 l expansion allowance, using G1 1/4 AG male connections. Power is 400 V 3~ 50 Hz with 3x16 A fusing; the unit ships with a cable but no plug, so the site must fit one.
Install indoors at 5–40 °C ambient, ≥300 lx, up to 2000 m altitude, with 50–200 cm side clearance and IP20 protection from water/dust. Cooling capacity is rated at 20 °C room temperature and may drop if ambient rises. Not for ATEX zones.
Refrigerant circuit work requires approved refrigeration contractors; R-449A charge has 6.1 t CO2 equivalent, triggering F-gas leak-check and record-keeping. The plug is not included. Register the unit to obtain the 4-year warranty.