Peter Huber Kältemaschinenbau Unichiller P180
Peter Huber Kältemaschinenbau Unichiller P180 — Recirculating chillers.
The Unichiller P180 is a free-standing, air-cooled recirculating chiller with a non-variable E2 pressure pump and G1 1/4 male connections, rated -20 to 40 °C. Its 'P' designation targets process loops with high pressure drop, where cooling capacity falls from 20 kW at 20 °C to 6 kW at -10 °C. It serves externally closed industrial cooling circuits requiring Pilot ONE control and Ethernet/RS232/USB data access.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Pump type | Safety class | Temperature range, °C | Power supply | Expansion volume, m³ | Minimum fill volume, m³ |
|---|---|---|---|---|---|---|
| Unichiller P180 Current | E2 | I / NFL | -20–40 | — | 0.048 | 0.018 |
| Unichiller 110T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 130T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 160T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.01 | — |
| Unichiller 180-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 180Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 180w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180w-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 200T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 200Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 210T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 230-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w-H | E1 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller 250T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 260T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 260Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 300T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 300T-H | D3 | III / FL | -20–100 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 300Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 300Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 350T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 350Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 500Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 700Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 800Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller GL 1000w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.05 | — |
| Unichiller GL 200w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 250w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 300w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 400w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 750w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.05 | — |
| Unichiller P180-H | E2 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w | E2 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230 | E2 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
Full specifications
| Expansion volume | 48 l |
| Minimum fill volume | 18 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | E2 |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Cooling capacity | 20 kW (at 20 °C) at 0 °C: 18 kW · at -10 °C: 6 kW |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- Free-standing cabinet, 938 x 1288 x 2003 mm (W x D x H), IP20, EMC Class A Group 1 to EN 55011 — industrial emission class, not for residential areas.
- The 'P' in the model name marks this modification as particularly suitable for applications requiring high pressure drops; the E2 pump is a pressure pump with fixed speed (pump speed not adjustable).
- Sibling Unichiller 110T variants differ in acoustic profile (74 dB(A) for 110T/110T-H, 65 dB(A) for 110Tw/110Tw-H); the P180 is a distinct high-pressure-drop modification, not a noise variant.
- Hydraulic circuit: G1 1/4 AG male pump connection, minimum filling capacity 18 l, expansion volume 48 l. Designed for externally closed applications only.
Behavior under load and temperature
- Cooling capacity is strongly temperature-dependent: 20 kW at 20 °C, 18 kW at 0 °C, 6 kW at -10 °C, and 3.5 kW at -20 °C per the datasheet. Sizing must use the capacity at the actual operating temperature, not the +20 °C nominal.
- Capacity figures are referenced to 20 °C room temperature; the datasheet warns capacity may drop as ambient rises. Permissible ambient range is 5 to 40 °C.
- Operating temperature range -20 to 40 °C; external Pt100 sensor connection available for process-side control.
- Refrigerant R-449A, GWP 1397, charge equivalent to 2.1 t CO2 — leak-check and record-keeping obligations apply.
Control, installation and operation
- Pilot ONE controller with Ethernet, USB host/device and RS232; power-failure response configurable as OFF/Standby, ON, or Power Failure Auto.
- Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached, instead of switching all poles off — relevant for exothermic loads.
- Electrical: 460 V 3~ 60 Hz supply; three-phase devices below 63 A are delivered with cable but without plug; external branch circuit protection to UL 489 is mandatory. Voltage tolerance ±5% only with frequency tolerance ±2%, and the combination -5% voltage with +2% frequency is explicitly not allowed.
- Installation: indoors only, illuminance at least 300 lx, altitude up to 2000 m; wall clearance 50–200 cm per side for maintenance; leveling feet/parking brakes set before start-up; pump connections counterheld and tightened to the manual's torque table.
- Not explosion-protected: must not be installed or started in an ATEX zone. Refrigerant charge versus room volume must be checked at installation.
Integration & Operating Notes
The unit is configured for a 460 V three-phase 60 Hz supply. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and the datasheet explicitly forbids -5% voltage combined with +2% frequency. Verify the site configuration before ordering; a mismatched supply prevents commissioning.
Three-phase devices drawing less than 63 A are supplied with cable but without a plug, so the installer must provide a suitable plug or hardwire the unit. External branch circuit protection according to UL 489 is required and must be sized from the electrical schematics.
Free-standing installation requires a wall clearance of 50 to 200 cm on either side for maintenance access. The cabinet is 938 x 1288 x 2003 mm, so door widths, ceiling height and service routes must be planned for this footprint before delivery.
The manual restricts use to indoor locations with illuminance of at least 300 lx and a maximum altitude of 2000 m. Ambient temperature must stay between 5 and 40 °C; outside this window cooling capacity drops and reliability is affected. The unit is not explosion-protected and must not be installed in an ATEX zone.
The chiller is designed only for externally closed applications. Minimum filling capacity is 18 l and expansion volume is 48 l, which sets the minimum loop volume and expansion headroom; undersized loops cause control and overflow problems. The G1 1/4 male pump connection requires matching hoses and fittings.
Cooling capacity falls from 20 kW at 20 °C to 6 kW at -10 °C and 3.5 kW at -20 °C. Capacity figures are valid at 20 °C room temperature and may drop as ambient rises. Selection based on the nominal +20 °C figure will undersize low-temperature duty.
The Pilot ONE allows the power-failure response to be set to OFF/Standby, ON, or Power Failure Auto. The chosen behavior determines whether the process restarts automatically after an outage; select it deliberately for the process risk profile rather than leaving the default.
In Process Safety mode the controller releases maximum cooling capacity when the overtemperature trigger value is reached, instead of switching off all poles. This is relevant for exothermic processes where cutting cooling would cause runaway temperatures; confirm the mode matches the process hazard analysis.
Work on the refrigerant circuit must only be performed by approved refrigeration/air-conditioning system contractors. The R-449A charge (GWP 1397, 2.1 t CO2 equivalent) also triggers leak-check and record-keeping obligations in many jurisdictions; plan service access accordingly.
Selection & Integration Q&A
Choose the P180 when the process loop has high pressure drop, since the 'P' designation and E2 pressure pump target that duty. The 110T family differs mainly in acoustic profile (74 vs 65 dB(A) for Tw variants); select those when noise is the deciding constraint rather than loop pressure drop.
A 460 V 3~ 60 Hz supply within ±5% voltage and ±2% frequency, with the combination -5% voltage and +2% frequency explicitly not allowed. The unit arrives with cable but no plug (below 63 A), so provide a plug or hardwiring plus external UL 489 branch protection sized from the schematics.
Indoors only, at least 300 lx, altitude up to 2000 m, ambient 5–40 °C, with 50–200 cm wall clearance per side for maintenance. It is not explosion-protected, so no ATEX zone. Set leveling feet or parking brakes before start-up, and check refrigerant charge against room volume.
No plug is supplied for the three-phase cable, and no mating hoses or G1 1/4 fittings are included. Refrigerant circuit work requires approved refrigeration contractors, and the R-449A charge (2.1 t CO2e) brings leak-check and record-keeping duties; cooling water must be shut off even overnight.