Peter Huber Kältemaschinenbau Unichiller 350T
Peter Huber Kältemaschinenbau Unichiller 350T — Recirculating chillers.
The Unichiller 350T is an air-cooled, CFC/HCFC-free recirculating chiller rated 23 kW at 0 °C and 8 kW at -20 °C, covering -20…40 °C on a 460 V/60 Hz three-phase supply. It is the large-capacity member of the Unichiller series, intended for externally closed process loops requiring high heat rejection.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Pump type | Safety class | Temperature range, °C | Power supply | Expansion volume, m³ | Minimum fill volume, m³ |
|---|---|---|---|---|---|---|
| Unichiller 350T Current | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 110T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 130T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 160T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.01 | — |
| Unichiller 180-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 180Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 180w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180w-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 200T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 200Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 210T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 230-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w-H | E1 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller 250T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 260T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 260Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 300T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 300T-H | D3 | III / FL | -20–100 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 300Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 300Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 350Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 500Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 700Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 800Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller GL 1000w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.05 | — |
| Unichiller GL 200w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 250w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 300w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 400w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 750w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.05 | — |
| Unichiller P180 | E2 | I / NFL | -20–40 | — | 0.048 | 0.018 |
| Unichiller P180-H | E2 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w | E2 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230 | E2 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
Full specifications
| Expansion volume | 39 l |
| Minimum fill volume | 14 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | D3 |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Weight | 640 kg |
| Current consumption | 27 A |
| Power supply | 460V 3~ 60Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Cooling capacity | 15 kW (at 35 °C) at 0 °C: 23 kW · at -10 °C: 14 kW · at -20 °C: 8 kW |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- Air-cooled refrigeration machine using R-449A (A1, H280), CFC- and HCFC-free; net weight 640 kg, overall dimensions 905 × 2172 × 1900 mm.
- Single fixed-speed pump D3 with G1 1/4 male connections; pump speed is not adjustable.
- Within the series, the 350T is the high-capacity unit; the sibling 110T/110Tw variants are smaller machines (the Tw versions are the quieter 65 dB(A) build versus 74 dB(A) on the 110T). Choose the 350T when the process heat load exceeds what the 110-class units can reject.
- Controller: Pilot ONE; interfaces Ethernet, USB (host and device) and RS232; external Pt100 sensor input; safety class I / NFL; IP20.
Behavior under load
- Cooling capacity is strongly temperature-dependent: 23 kW at 0 °C, 15 kW at 35 °C, 14 kW at -10 °C and 8 kW at -20 °C. Capacity is rated at 20 °C room temperature and falls as ambient rises, so the margin must be sized against the actual room climate.
- Permissible operating envelope: -20…40 °C process temperature, 5…40 °C ambient.
- Hydraulic volume: minimum filling capacity 14 l, expansion volume 39 l; the external loop must be compatible with the expansion tank.
Installation, control and operation
- 460 V 3~ 60 Hz supply, 27 A current consumption, 3×32 A fusing; external branch protection to UL 489 is mandatory. Three-phase units below 63 A are delivered with cable but without plug.
- Voltage tolerance ±5 % and frequency tolerance ±2 % must not be combined in the unfavorable direction.
- The unit is designed for externally closed applications only; models with “P” in the name are the ones suited to high pressure-drop loops, which the 350T is not.
- Power-failure response is configurable on the Pilot ONE (OFF/Standby, ON, Power Failure Auto); Process Safety mode releases maximum cooling when the overtemperature trigger is reached.
Integration & Operating Notes
The 460 V three-phase supply draws 27 A and requires 3×32 A fusing; external branch circuit protection according to UL 489 must be installed by the customer. Because the unit is below 63 A it ships with a cable but no plug, so the final connection hardware is a site responsibility.
Voltage may deviate ±5 % and frequency ±2 %, but the two tolerances must not be combined in the unfavorable direction. Supply quality outside this envelope risks compressor and electronics damage, so the site supply should be measured before startup.
Free-standing installation requires a wall clearance of 50 to 200 cm on either side for maintenance. The air-cooled condenser also needs unobstructed airflow for heat rejection; restricted ventilation reduces cooling capacity and can cause overheating.
At 905 × 2172 × 1900 mm and 640 kg net, the installation route and floor must be verified before delivery. Leveling feet must be unscrewed/activated and parking brakes applied before the unit is switched on to prevent movement during operation.
The 350T is designed for externally closed applications. Unlike models with “P” in the name, it is not the variant intended for high pressure-drop process loops, so circuit pressure loss must be checked against the D3 pump characteristic before selection.
The unit is not explosion-protected and must not be installed or started up within an ATEX zone. Refrigerant charge and room size must also be checked at installation to stay within the permissible refrigerant quantity per m³ of ambient air.
The Pilot ONE allows the power-failure response to be set to OFF/Standby, ON or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling when the overtemperature trigger is reached instead of switching off all poles; the chosen logic must match the process hazard analysis.
Any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning contractors. The R-449A charge has a CO2 equivalent of 11.2 t, which triggers F-gas record-keeping and periodic leak-check obligations in many jurisdictions.
IP20 protection means the unit must be installed indoors, protected from water and dust. The manual additionally requires illuminance of at least 300 lx and a site no higher than 2000 m altitude; the ambient temperature must stay within 5…40 °C.
Selection & Integration Q&A
Pick the 350T when the process heat load needs the larger capacity (23 kW at 0 °C, 8 kW at -20 °C). The 110-class siblings are smaller machines; the Tw versions are the quieter 65 dB(A) build versus 74 dB(A) on the 110T, so choose those when acoustic limits dominate.
A 460 V 3~ 60 Hz supply with 27 A consumption and 3×32 A fusing, plus external branch protection to UL 489. The unit ships with a cable but no plug (below 63 A), so the final connection is site-supplied; verify ±5 % voltage and ±2 % frequency are not combined unfavorably.
Install indoors only (IP20), at 5…40 °C ambient and at least 300 lx lighting, below 2000 m altitude, never in an ATEX zone. Keep 50–200 cm clearance per side for service, ensure airflow for the air-cooled condenser, and secure leveling feet/parking brakes before startup.
The R-449A charge has a CO2 equivalent of 11.2 t, triggering F-gas record-keeping and leak checks; refrigerant work is restricted to approved contractors. The base delivery excludes the final plug and UL 489 breaker, and the external loop must suit the 14 l minimum fill and 39 l expansion volume.