Peter Huber Kältemaschinenbau Unichiller 700Tw
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 700Tw

Peter Huber Kältemaschinenbau Unichiller 700Tw — Recirculating chillers.

The Unichiller 700Tw is a water-cooled recirculating chiller in the Unichiller series, rated for a -20…40 °C working range and requiring 400 V 3~ 50 Hz supply at up to 45 A. Its G1 1/4 cooling-water connections and 3780 l/h consumption at 15 °C distinguish this larger modification from the 110T/110Tw siblings. It serves externally closed process loops where heat is rejected to a site cooling-water circuit.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Pump typeSafety classTemperature range, °CPower supplyExpansion volume, m³Minimum fill volume, m³
Unichiller 700Tw Current D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 110T C3I / NFL-10–40400V 3~ 50Hz0.007—
Unichiller 110T-H C3III / FL-10–100400V 3~ 50Hz0.007—
Unichiller 110Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 130T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 130T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 130Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 160T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 160T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 160Tw C3I / NFL-20–40400V 3~ 50Hz0.01—
Unichiller 180-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 180T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 180T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 180Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 180Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 180w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 180w-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 200T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 200Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 210T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 210T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 210Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 230-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 230w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 230w-H E1III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller 250T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 250T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 250Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 260T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 260T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 260Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 260Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 300T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 300T-H D3III / FL-20–100460V 3~ 60Hz0.0390.014
Unichiller 300Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 300Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 350T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 350Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 500Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw-H D3III / FL-20–100400V 3~ 50Hz0.007—
Unichiller 800Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller GL 1000w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.05—
Unichiller GL 200w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 250w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 300w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 400w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 750w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.05—
Unichiller P180 E2I / NFL-20–40—0.0480.018
Unichiller P180-H E2III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller P180w E2I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller P180w-H E2III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller P230 E2I / NFL-20–40460V 3~ 60Hz0.0480.018
Unichiller P230-H E2III / FL-20–100460V 3~ 60Hz0.0480.018

Full specifications

Core Performance & Functional Specifications
Expansion volume 7 l
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type D3
External sensor connection Pt100
Temperature range -20...40 °C
Dimensions, Weight & Mechanical Design
Weight 600 kg
Electrical, Power & Drive Specifications
Current consumption 45 A (max)
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G1 1/4 male
Cooling water consumption 1980 л/час (at 15°C, flow -10°C)
at 15°C, flow 0°C: 2940 l/h · at 15°C, flow 15°C: 3780 l/h
Cooling Water Pressure 6 bar (max)
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Behavior and process limits

Control, connection and operation

Integration & Operating Notes

Cooling & Media
Cooling-water inlet must stay between 5 and 20 °C

The unit is designed for cooling-water intake of 5…20 °C. If the water temperature falls below the condensation point, the cooling-water pipes inside the unit must be insulated to prevent condensation and electrical hazard.

Unichiller 700Tw Technical Data, page 2
Cooling & Media
Site water loop must deliver ≥1.5 bar differential and ≤6 bar

The minimum cooling-water differential pressure is 1.5 bar and the maximum cooling-water pressure is 6 bar. The site supply must fall within these limits; rated capacity is quoted at 1.5 bar differential, so lower differential pressure degrades performance.

Unichiller 700Tw Technical Data, page 1
Cooling & Media
Shut off cooling water even for overnight downtime

The cooling-water supply must be shut off during idle periods, including short downtimes such as overnight, to prevent water damage and corrosion.

Unichiller Operation Manual, page 28
Mounting
Allow 50–200 cm wall clearance per side for maintenance

Free-standing models require a wall clearance of 50 to 200 cm on either side for maintenance access. The 600 kg weight and 1000x1100x1635 mm footprint must be accommodated with adequate floor loading and doorway clearance.

Unichiller Operation Manual, page 25; Unichiller 700Tw Technical Data, page 2
Mounting
Indoor installation only, ≥300 lx, below 2000 m altitude

The unit may only be used indoors with illuminance of at least 300 lx and at altitudes up to 2000 m. IP20 protection means it must be kept dry and protected from water ingress.

Unichiller Operation Manual, page 25; Unichiller 700Tw Technical Data, page 2
Mounting
Do not install in an ATEX zone

The unit is not explosion-protected and must not be installed or started up inside an ATEX zone. Refrigerant charge and room size must be checked at installation to avoid exceeding the refrigerant limit per m³ of ambient air.

Unichiller Operation Manual, pages 13 and 15
Electrical
Cable supplied without plug below 63 A

Three-phase devices with current consumption less than 63 A are supplied with cable but without a plug; the installer must provide a suitable plug or hard-wired connection. The 700Tw draws up to 45 A at 400 V 3~ 50 Hz.

Unichiller 700Tw Technical Data, page 2
Electrical
Voltage and frequency tolerances cannot be combined arbitrarily

Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, but combinations such as -5% voltage with +2% frequency are not allowed. Out-of-tolerance supply may cause malfunction.

Unichiller 700Tw Technical Data, page 2
Electrical
Protect electrical lines below the unit from condensate

Electrical lines directly below a water-cooled unit must be protected against liquid ingress from condensation.

Unichiller Operation Manual, page 28
Control & I/O
Configure power-failure response for the process

The Pilot ONE allows the power-failure response to be set to OFF/Standby, ON or Power Failure Auto. The choice determines whether the process restarts automatically after a power outage.

Unichiller Operation Manual, page 19
Control & I/O
Process Safety mode applies maximum cooling at OT trigger

In Process Safety mode, maximum cooling capacity is released when the overtemperature protection trigger value is reached, instead of switching off all poles. This is relevant for exothermic processes where cutting cooling would cause runaway temperatures.

Unichiller Operation Manual, page 18
Maintenance
Refrigerant circuit work only by approved contractors

Work on the refrigerant circuit must be carried out only by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A (A1, H280; GWP 1397), so leak detection and ventilation requirements apply.

Unichiller Operation Manual, page 17; Unichiller 700Tw Technical Data, page 1
Maintenance
Activate leveling feet and parking brakes before start-up

Before the unit is put into operation, parking brakes must be activated at the casters (if any) and/or leveling feet unscrewed/activated to prevent movement and crushing injuries.

Unichiller Operation Manual, page 31

Selection & Integration Q&A

When should I choose the Unichiller 700Tw rather than a smaller sibling such as the 110Tw?

Choose the 700Tw when the process requires the larger cooling capacity implied by its 3780 l/h cooling-water consumption at 15 °C flow and its -20…40 °C range. The 110Tw is a smaller unit (listed at 65 dB(A)); select it only when its capacity matches the load. The 700Tw is water-cooled and needs a site water circuit delivering ≥1.5 bar differential.

What site services and adjacent equipment must be ready before installing the 700Tw?

A 400 V 3~ 50 Hz supply capable of 45 A (cable supplied without plug below 63 A), a cooling-water circuit with G1 1/4 connections delivering 1.5–6 bar differential and up to 3780 l/h at 15 °C, and a dry indoor location with ≥300 lx and 50–200 cm side clearance. The process loop must be externally closed.

What mounting and duty-cycle limits apply to the 700Tw?

Install indoors only, not in an ATEX zone, at 5…40 °C ambient and below 2000 m altitude. Allow 50–200 cm wall clearance per side, verify floor loading for 600 kg, and activate leveling feet/parking brakes before start-up. Shut off cooling water even for overnight downtime.

What maintenance and accessories are required beyond the base delivery?

The base delivery includes cable but no plug for three-phase units below 63 A, so a plug or hard-wired connection must be provided. Refrigerant circuit work requires approved refrigeration contractors. Cooling-water pipes may need insulation if water temperature falls below the condensation point. No consumables or spare parts are listed in the supplied documents.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller 700Tw Technical Data
Datasheet ·94,1 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF