Peter Huber Kältemaschinenbau Unichiller P230
Peter Huber Kältemaschinenbau Unichiller P230 — Recirculating chillers.
The Unichiller P230 is a recirculating chiller with a pressure pump (E2, non-variable speed) for externally closed circuits with high pressure drop, rated -20 to 40 °C and 23 kW cooling at 20 °C. It is the 'P' modification of the Unichiller series, distinguished by its high-pressure pump rather than by capacity class. It serves as a central cooling source for industrial processes requiring stable temperature control under significant hydraulic resistance.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Pump type | Safety class | Temperature range, °C | Power supply | Expansion volume, m³ | Minimum fill volume, m³ |
|---|---|---|---|---|---|---|
| Unichiller P230 Current | E2 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller 110T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 130T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 160T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.01 | — |
| Unichiller 180-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 180Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 180w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180w-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 200T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 200Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 210T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 230-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w-H | E1 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller 250T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 260T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 260Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 300T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 300T-H | D3 | III / FL | -20–100 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 300Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 300Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 350T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 350Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 500Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 700Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 800Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller GL 1000w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.05 | — |
| Unichiller GL 200w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 250w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 300w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 400w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 750w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.05 | — |
| Unichiller P180 | E2 | I / NFL | -20–40 | — | 0.048 | 0.018 |
| Unichiller P180-H | E2 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w | E2 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
Full specifications
| Expansion volume | 48 l |
| Minimum fill volume | 18 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | E2 |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Power supply | 460V 3~ 60Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Cooling capacity | 23 kW (at 20 °C) at -10 °C: 9 kW |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and positioning
- The P230 is a free-standing recirculating chiller with overall dimensions 938×1288×2003 mm (W×D×H) and IP20 protection, intended for indoor installation only.
- Its defining feature within the Unichiller series is the 'P' designation: the manual states that models with 'P' in the model name are particularly suitable for applications requiring high pressure drops. The pump is type E2 with a maximum delivery of 140 l/min and maximum delivery pressure of 5.3 bar; flow falls to 43 l/min at 5.0 bar, so the external circuit must be checked against this curve.
- The pump speed is not adjustable. The pump connection is G1 1/4 male.
- Sibling models in the series (Unichiller 110T, 110T-H, 110Tw, 110Tw-H) are distinguished by noise level (74 dB(A) for 110T/110T-H, 65 dB(A) for 110Tw/110Tw-H); the P230's noise level is not stated in the verified facts.
Behavior under load and media
- Cooling capacity is strongly temperature-dependent: 23 kW at 20 °C, 13.5 kW at 0 °C, 9 kW at -10 °C, and 5.5 kW at -20 °C. Sizing must use the capacity at the actual operating point, not the nominal 23 kW.
- The operating temperature range is -20 to 40 °C. The unit is designed for externally closed applications only.
- The expansion tank volume is 48 l and the minimum filling capacity is 18 l; the external loop volume and fluid charge must be planned accordingly.
- The refrigerant is R-449A (GWP 1397, charge 1.49 kg, CO2 equivalent 2.1 t). Room size and charge must be checked at installation to avoid exceeding the refrigerant limit per m³ of ambient air.
- Cooling capacity data is valid at 20 °C room temperature; capacity may drop at higher ambient. The permissible ambient temperature range is 5 to 40 °C.
Installation, control and operation
- Electrical supply is 460 V three-phase 60 Hz. Voltage tolerance is ±5% and frequency tolerance ±2%, but these cannot be combined in the unfavorable direction. External branch circuit protection according to UL 489 is required. Three-phase devices below 63 A are delivered with cable but without plug.
- The controller is Pilot ONE with interfaces Ethernet, USB (Host and Device), and RS232. An external Pt100 sensor connection is available. The power-failure response is configurable as OFF/Standby, ON, or Power Failure Auto.
- Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached, instead of switching off all poles.
- The unit is EMC class A group 1 (EN 55011), intended for industrial use; it may cause radio interference in residential areas.
- Installation requires a wall clearance of 50 to 200 cm per side for maintenance, indoor use at illuminance of at least 300 lx, and altitude up to 2000 m. Leveling feet must be activated and parking brakes applied before startup. Cooling water supply must be shut off even for short downtimes. Electrical lines directly below a water-cooled unit must be protected against liquid ingress.
Integration & Operating Notes
The equipment is classified to EN 55011 as Class A, Group 1, so it may cause radio interference in residential areas. It is intended for industrial use and should not be installed in residential environments without additional filtering.
Selection & Integration Q&A
Choose the P230 when the external circuit has high pressure drop and requires up to 5.3 bar pump pressure; the 'P' models are specifically suited to such applications. The 110T/110Tw siblings differ in noise level (74 vs 65 dB(A)) and are not designated for high pressure drop. The P230 also covers -20 to 40 °C with 23 kW at 20 °C.
The P230 requires a 460 V three-phase 60 Hz supply with voltage tolerance ±5% and frequency tolerance ±2%, not combined unfavorably. External branch circuit protection according to UL 489 is mandatory. The unit is delivered with cable but without plug (three-phase below 63 A), so a suitable connection must be provided on site.
Refrigerant circuit work must be performed by approved refrigeration contractors. Check refrigerant charge (1.49 kg R-449A) against room volume at installation. Cooling water supply must be shut off during downtimes. The base delivery includes cable but no plug; hoses and fittings for the G1 1/4 male pump connection are not included and must be ordered separately.