Peter Huber Kältemaschinenbau Unichiller 180Tw-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 180Tw-H

Peter Huber Kältemaschinenbau Unichiller 180Tw-H — Recirculating chillers with Noise level 59 dB.

The Unichiller 180Tw-H is a water-cooled recirculating chiller with a 400 V 3-phase supply, delivering 18 kW at 0 °C and 6 kW at -20 °C over a -20…100 °C range. Its D3 pump provides up to 210 l/min, distinguishing it from lower-capacity siblings. It serves externally closed process loops requiring precise temperature control.

Noise level
59 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Pump typeSafety classTemperature range, °CPower supplyExpansion volume, m³Minimum fill volume, m³
Unichiller 180Tw-H Current D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 110T C3I / NFL-10–40400V 3~ 50Hz0.007—
Unichiller 110T-H C3III / FL-10–100400V 3~ 50Hz0.007—
Unichiller 110Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 130T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 130T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 130Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 160T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 160T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 160Tw C3I / NFL-20–40400V 3~ 50Hz0.01—
Unichiller 180-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 180T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 180T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 180Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 180w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 180w-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 200T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 200Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 210T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 210T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 210Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 230-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 230w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 230w-H E1III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller 250T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 250T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 250Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 260T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 260T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 260Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 260Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 300T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 300T-H D3III / FL-20–100460V 3~ 60Hz0.0390.014
Unichiller 300Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 300Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 350T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 350Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 500Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw-H D3III / FL-20–100400V 3~ 50Hz0.007—
Unichiller 700Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 800Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller GL 1000w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.05—
Unichiller GL 200w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 250w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 300w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 400w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 750w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.05—
Unichiller P180 E2I / NFL-20–40—0.0480.018
Unichiller P180-H E2III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller P180w E2I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller P180w-H E2III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller P230 E2I / NFL-20–40460V 3~ 60Hz0.0480.018
Unichiller P230-H E2III / FL-20–100460V 3~ 60Hz0.0480.018

Full specifications

Core Performance & Functional Specifications
Noise level 59 dB(A)
Expansion volume 22 l
Heating capacity 2 kW
Minimum fill volume 15 l
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type D3
External sensor connection Pt100
Temperature range -20...100 °C
Dimensions, Weight & Mechanical Design
Weight 401 kg
Electrical, Power & Drive Specifications
Current consumption 24 A (max.)
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling capacity 15 kW (at 15 °C)
at 0 °C: 18 kW · at -10 °C: 13 kW · at -20 °C: 6 kW
Cooling water connection G3/4 male
Cooling water consumption 427 л/час (at 15°C, flow -20°C)
at 15°C, flow -10°C: 553 л/час · at 15°C, flow 0°C: 666 l/h
Cooling water differential pressure 1 bar (min.)
Cooling Water Pressure 6 bar (max.)
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and positioning

Behavior under load

Installation and operation

Integration & Operating Notes

Process Limits
Cooling water pressure must stay within 1–6 bar

Supply pressure below 1 bar differential prevents safe commissioning; above 6 bar may damage the unit. Size the building water system and any pressure-reducing valve to maintain this window under all flow conditions.

Technical Datasheet, page 2
Mounting
Maintain 50–200 cm wall clearance per side for maintenance access

Free-standing models require this clearance on either side to allow service access. Plan the installation footprint accordingly, considering the unit dimensions of 760×800×1615 mm and weight of 401 kg.

Operation Manual, page 25
Process Limits
External loop volume must be between 15 l and 22 l

Minimum filling capacity is 15 l; expansion volume is 22 l. Too small a volume causes poor temperature stability, while exceeding 22 l may overflow the expansion tank. Calculate the total volume of the unit plus external circuit.

Technical Datasheet, page 2
Maintenance
Shut off cooling water supply even for short downtimes

Leaving the cooling water supply on during overnight or short downtimes can cause water damage and corrosion. Install a shut-off valve in the cooling water supply line and close it whenever the unit is not in use.

Operation Manual, page 28
Electrical
Unit is delivered with cable but without a plug

Three-phase devices below 63 A are supplied with a cable but no plug. The customer must provide and fit a suitable plug (3×25 A fuse required) before commissioning. Plan for this in the installation schedule.

Technical Datasheet, page 2

Selection & Integration Q&A

When should I choose the Unichiller 180Tw-H over the Unichiller 110T or 110Tw models?

Choose the 180Tw-H for higher cooling capacity (18 kW at 0 °C vs lower in 110 series) and lower noise (59 dB(A) vs 74 dB(A) for 110T). The 110Tw offers 65 dB(A) but less capacity. Select the 180Tw-H when process loads exceed 13 kW at -10 °C or when acoustic limits are tight.

What are the requirements for the cooling water supply and electrical connection when integrating this chiller?

Cooling water: G3/4 male connections, supply pressure 1–6 bar differential, inlet temperature 5–20 °C, flow up to 666 l/h at 0 °C process. Electrical: 400 V 3~ 50 Hz, 24 A max, 3×25 A fuse, cable provided but no plug. Ensure voltage/frequency tolerances (±5%/±2%) are not combined oppositely.

What installation environment and duty-cycle limits apply to the Unichiller 180Tw-H?

Install indoors only, ambient 5–40 °C, IP20, illuminance ≥300 lx, altitude ≤2000 m. Maintain 50–200 cm wall clearance per side. Engage leveling feet or parking brakes before operation. Not for ATEX zones. Shut off cooling water during downtimes. External loop volume must be 15–22 l.

What maintenance and service items are required, and what is not included in the base delivery?

Refrigerant circuit work only by certified contractors; F-gas records required (R-449A, 2.6 kg, 3.6 t CO2e). Cooling water circuit materials (copper, stainless steel, etc.) require compatible water treatment. Base delivery excludes plug (customer must provide) and external hoses/fittings. Regular maintenance includes checking cooling water quality and pipe insulation.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller 180Tw-H Technical Datasheet
Datasheet ·18,4 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF