Peter Huber Kältemaschinenbau Unichiller 230w-H
Peter Huber Kältemaschinenbau Unichiller 230w-H — Recirculating chillers.
The Unichiller 230w-H is a water-cooled recirculating chiller with a 48 l expansion volume and 18 l minimum fill, operating from -20 to 100 °C with a 2 kW heater. It is distinguished within the series by its 460 V 3~ 60 Hz supply and G3/4 male cooling-water connection. It serves externally closed process loops requiring precise temperature control via the Pilot ONE controller.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Pump type | Safety class | Temperature range, °C | Power supply | Expansion volume, m³ | Minimum fill volume, m³ |
|---|---|---|---|---|---|---|
| Unichiller 230w-H Current | E1 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller 110T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 130T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 160T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.01 | — |
| Unichiller 180-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 180Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 180w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180w-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 200T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 200Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 210T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 230-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 250T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 260T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 260Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 300T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 300T-H | D3 | III / FL | -20–100 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 300Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 300Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 350T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 350Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 500Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 700Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 800Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller GL 1000w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.05 | — |
| Unichiller GL 200w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 250w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 300w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 400w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 750w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.05 | — |
| Unichiller P180 | E2 | I / NFL | -20–40 | — | 0.048 | 0.018 |
| Unichiller P180-H | E2 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w | E2 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230 | E2 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
Full specifications
| Expansion volume | 48 l |
| Heating capacity | 2 kW |
| Minimum fill volume | 18 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | E1 |
| External sensor connection | Pt100 |
| Temperature range | -20...100 °C |
| Power supply | 460V 3~ 60Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G3/4 male |
| Cooling water consumption | 324 l/h (cooling water 15°C, flow -20°C) cooling water 15°C, flow -10°C: 414 l/h · cooling water 15°C, flow 0°C: 540 l/h |
| Cooling water differential pressure | 1 bar |
| Cooling Water Pressure | 6 bar |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and Series Positioning
The Unichiller 230w-H is a water-cooled recirculating chiller in the Unichiller series, using the Pilot ONE controller and an E1 pressure pump with fixed speed. Unlike sibling models such as the Unichiller 110T variants, this model is configured for a 460 V 3~ 60 Hz power supply and has a G3/4 male cooling-water connection. The cooling-water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, which constrains water quality. The unit is rated IP20 and safety class III/FL, and is intended for indoor installation only.
Behavior Under Load and Media
Cooling-water consumption depends on the flow temperature: 540 l/h at 0 °C, 414 l/h at -10 °C, and 324 l/h at -20 °C, all with cooling water at 15 °C. A minimum cooling-water differential pressure of 1 bar is required, and the maximum cooling-water pressure is 6 bar. The cooling water inlet temperature must be between 5 °C and 20 °C. As cooling water temperature rises, cooling power drops and flow rate may need to increase. The unit is designed for externally closed applications only; models with 'P' in the model name are suited to high pressure drop, but this model does not carry that designation.
Installation, Control, and Operation
The Pilot ONE controller provides Ethernet, USB (Host and Device), and RS232 interfaces, and supports a Pt100 external sensor connection. Power-failure response is configurable as OFF/Standby, ON, or Power Failure Auto. Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached, rather than switching off all poles. The unit requires a three-phase 460 V 60 Hz supply with ±5% voltage tolerance and ±2% frequency tolerance; external branch circuit protection per UL 489 must be provided by the installer. Three-phase devices under 63 A are supplied with cable but no plug. A wall clearance of 50 to 200 cm per side is required for maintenance, and the unit must be installed indoors at an illuminance of at least 300 lx and up to 2000 m altitude. Leveling feet or parking brakes must be engaged before operation. Cooling water supply must be shut off even for short downtimes.
Integration & Operating Notes
The chiller requires a three-phase 460 V 60 Hz supply. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed. Verify site power quality before installation to avoid warranty and operational issues.
External branch circuit protection according to UL 489 is required and must be provided by the installer. Three-phase devices with current consumption less than 63 A are supplied with cable but without a plug, so a suitable plug must be sourced separately.
The unit is designed to operate with cooling water intake temperature between 5 °C and 20 °C. Pipes must be insulated if below the condensation point. Cooling water pressure must not exceed 6 bar, and a minimum differential pressure of 1 bar is required for proper operation.
A wall clearance of 50 to 200 cm is required on either side for maintenance on free-standing models. The unit must be installed indoors at an illuminance of at least 300 lx and up to 2000 m altitude. It must not be installed or started up inside an ATEX zone.
The parking brakes must be activated at the casters (if any) and/or the leveling feet must be unscrewed/activated before the temperature control unit is put into operation. This prevents movement and crushing injuries during operation.
This temperature control unit is designed for externally closed applications. Models with 'P' in the model name are particularly suitable for applications requiring high pressure drops; this model does not carry that designation, so verify the pressure drop of your external circuit.
The power-failure response can be configured as OFF/Standby, ON, or Power Failure Auto via the Pilot ONE. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger value is reached instead of switching off all poles.
Work on the coolant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The refrigerant R-449A has a GHS hazard H280 (pressurized gas) and a GWP of 1397. Observe the amount of refrigerant and room size to avoid exceeding the refrigerant limit per m³ of ambient air.
Shut off the cooling water supply to the temperature control unit even for shorter downtimes (e.g., overnight). Electrical lines directly below a water-cooled unit must be protected against liquid ingress from condensation.
Selection & Integration Q&A
Choose the 230w-H when you need a 460 V 3~ 60 Hz supply and a water-cooled unit with a G3/4 cooling-water connection. The 110T and 110Tw siblings are air-cooled (noise levels 74 dB(A) and 65 dB(A) respectively) and likely differ in voltage; select them if water cooling is unavailable or lower noise is required.
Cooling water must be 5–20 °C inlet, max 6 bar, min 1 bar differential pressure, with consumption up to 540 l/h at 15 °C. The cooling-water connection is G3/4 male. The process loop connects via G1 1/4 AG male pump connections; ensure the external circuit is closed and compatible with the wetted materials (copper, stainless steel 1.4401, MS, PA, PPE, PTFE, EPDM).
The base delivery includes a cable but no plug for the 460 V three-phase supply; a suitable plug must be sourced. External branch circuit protection per UL 489 is installer-supplied. Refrigerant circuit work must be by approved contractors. No other accessories or consumables are specified in the provided documents.