Peter Huber Kältemaschinenbau Unichiller 260Tw
Peter Huber Kältemaschinenbau Unichiller 260Tw — Recirculating chillers.
The Unichiller 260Tw is a water-cooled recirculating chiller with a 210 l/min pump and a -20 to 40 °C working range, distinguished from the air-cooled 110T siblings by its water-cooled condenser and higher-capacity pump. It serves externally closed process loops requiring up to 4.7 bar delivery pressure.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Pump type | Safety class | Temperature range, °C | Power supply | Expansion volume, m³ | Minimum fill volume, m³ |
|---|---|---|---|---|---|---|
| Unichiller 260Tw Current | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 110T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 130T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 160T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.01 | — |
| Unichiller 180-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 180Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 180w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180w-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 200T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 200Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 210T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 230-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w-H | E1 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller 250T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 260T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 260Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 300T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 300T-H | D3 | III / FL | -20–100 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 300Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 300Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 350T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 350Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 500Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 700Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 800Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller GL 1000w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.05 | — |
| Unichiller GL 200w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 250w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 300w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 400w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 750w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.05 | — |
| Unichiller P180 | E2 | I / NFL | -20–40 | — | 0.048 | 0.018 |
| Unichiller P180-H | E2 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w | E2 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230 | E2 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
Full specifications
| Expansion volume | 22 l |
| Minimum fill volume | 15 l |
| Pump connection | G1 1/4 AG male |
| Pump speed adjustable | no |
| Pump type | D3 |
| External sensor connection | Pt100 |
| Temperature range | -20...40 °C |
| Weight | 375 kg |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Refrigerant | R-449A (A1, H280) (1st stage) |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G3/4 male |
| Cooling water differential pressure | 1 bar (min) |
| Cooling Water Pressure | 6 bar (max) |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- Water-cooled condenser using R-449A (2.55 kg, 3.6 t CO2e); the 110T/110T-H siblings are air-cooled and rated at 74 dB(A), while the 110Tw/110Tw-H are water-cooled at 65 dB(A).
- Pump type D3, non-adjustable speed, G1 1/4 male pump connections; cooling water connections G3/4 male.
- 15 l minimum fill, 22 l expansion volume; 375 kg; IP20; Pilot ONE controller.
Hydraulic and thermal behavior
- Temperature range -20...40 °C. Pump delivers 210 l/min maximum and 4.7 bar maximum pressure; at 4.5 bar the flow falls to 31 l/min, so external circuit pressure drop must be matched to the pump curve.
- Cooling power ratings are valid only at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure.
- Intended for externally closed applications only; models with 'P' in the name suit high-pressure-drop loops, which this model is not.
Installation, control and operation
- 400 V 3~ 50 Hz supply, max current 27.5 A, 3x32 A fuse; delivered with cable but without plug.
- Pilot ONE controller with Ethernet, USB (host and device) and RS232; external Pt100 sensor connection.
- Power-failure response configurable as OFF/Standby, ON or Power Failure Auto; Process Safety mode releases maximum cooling at the OT trigger instead of switching off.
- Cooling water 5...20 °C inlet, 1 bar min differential, 6 bar max; insulate cooling water pipes if below condensation point.
Integration & Operating Notes
Below 5 °C or above 20 °C inlet the rated cooling capacity is not valid; below the condensation point the cooling water pipes must be insulated to prevent condensate. Differential pressure below 1 bar starves the condenser, above 6 bar risks connection damage.
Voltage tolerance ±5% and frequency tolerance ±2% apply simultaneously; a -5% voltage with +2% frequency is explicitly not allowed. Plan the 3x32 A fuse and 27.5 A max current, and provide a suitable plug since the cable is supplied without one.
Free-standing installation requires this wall clearance on either side. Indoors only, illuminance at least 300 lx, altitude up to 2000 m, ambient 5–40 °C. Check refrigerant charge against room volume to avoid exceeding the limit per m³.
Because the condenser is water-cooled, electrical lines routed directly below the unit must be protected against liquid ingress from condensation. Also secure the unit: activate parking brakes and/or unscrew leveling feet before switching on.
The unit is designed for externally closed applications and is not explosion-protected, so it must not be installed or started inside an ATEX zone. For high-pressure-drop loops, a 'P' model is the correct choice instead of this unit.
The Pilot ONE allows OFF/Standby, ON or Power Failure Auto after mains loss. For exothermic processes, Process Safety mode releases maximum cooling at the OT trigger rather than switching off all poles, preventing runaway temperatures.
Any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. Shut off the cooling water supply even for short downtimes such as overnight to prevent water damage and corrosion.
Selection & Integration Q&A
Pick the 260Tw when you need the higher 210 l/min pump and water-cooled condenser for a large externally closed loop. The 110T is air-cooled (74 dB(A)); the 110Tw is water-cooled at 65 dB(A) but with lower pump capacity. Choose a 'P' model instead for high-pressure-drop circuits.
Pump connections are G1 1/4 male; size the loop so pressure drop matches the pump curve (210 l/min max, 4.7 bar max, 31 l/min at 4.5 bar). Cooling water: G3/4 male, 5–20 °C, 1–6 bar differential. Electrical: 400 V 3~ 50 Hz, 27.5 A max, 3x32 A fuse, plug not included.
Indoors only, 5–40 °C ambient, at least 300 lx illuminance, up to 2000 m altitude, IP20. Allow 50–200 cm wall clearance per side for maintenance. Not permitted in ATEX zones. Protect cables below the unit from condensate and check refrigerant charge against room volume.
The unit ships with a cable but no plug, so the customer supplies a suitable 3-phase plug. Refrigerant circuit service is restricted to approved contractors. Shut off cooling water during downtimes. Insulate cooling water pipes if inlet temperature falls below the condensation point.