Peter Huber Kältemaschinenbau Unichiller P230
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller P230

Peter Huber Kältemaschinenbau Unichiller P230 — Recirculating chillers.

The Unichiller P230 is a recirculating chiller with a pressure pump (E2, non-variable speed) for externally closed circuits with high pressure drop, rated -20 to 40 °C and 23 kW cooling at 20 °C. It is the 'P' modification of the Unichiller series, distinguished by its high-pressure pump rather than by capacity class. It serves as a central cooling source for industrial processes requiring stable temperature control under significant hydraulic resistance.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Pump typeSafety classTemperature range, °CPower supplyExpansion volume, m³Minimum fill volume, m³
Unichiller P230 Current E2I / NFL-20–40460V 3~ 60Hz0.0480.018
Unichiller 110T C3I / NFL-10–40400V 3~ 50Hz0.007—
Unichiller 110T-H C3III / FL-10–100400V 3~ 50Hz0.007—
Unichiller 110Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 130T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 130T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 130Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 160T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 160T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 160Tw C3I / NFL-20–40400V 3~ 50Hz0.01—
Unichiller 180-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 180T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 180T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 180Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 180Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 180w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 180w-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 200T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 200Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 210T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 210T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 210Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 230-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 230w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 230w-H E1III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller 250T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 250T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 250Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 260T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 260T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 260Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 260Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 300T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 300T-H D3III / FL-20–100460V 3~ 60Hz0.0390.014
Unichiller 300Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 300Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 350T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 350Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 500Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw-H D3III / FL-20–100400V 3~ 50Hz0.007—
Unichiller 700Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 800Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller GL 1000w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.05—
Unichiller GL 200w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 250w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 300w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 400w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 750w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.05—
Unichiller P180 E2I / NFL-20–40—0.0480.018
Unichiller P180-H E2III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller P180w E2I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller P180w-H E2III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller P230-H E2III / FL-20–100460V 3~ 60Hz0.0480.018

Full specifications

Core Performance & Functional Specifications
Expansion volume 48 l
Minimum fill volume 18 l
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type E2
External sensor connection Pt100
Temperature range -20...40 °C
Electrical, Power & Drive Specifications
Power supply 460V 3~ 60Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling capacity 23 kW (at 20 °C)
at -10 °C: 9 kW
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Environment
EMC class A group 1 — industrial use only

The equipment is classified to EN 55011 as Class A, Group 1, so it may cause radio interference in residential areas. It is intended for industrial use and should not be installed in residential environments without additional filtering.

Datasheet, Specifications

Selection & Integration Q&A

When should I choose the Unichiller P230 over the 110T or 110Tw siblings?

Choose the P230 when the external circuit has high pressure drop and requires up to 5.3 bar pump pressure; the 'P' models are specifically suited to such applications. The 110T/110Tw siblings differ in noise level (74 vs 65 dB(A)) and are not designated for high pressure drop. The P230 also covers -20 to 40 °C with 23 kW at 20 °C.

What are the requirements for the electrical supply and branch protection?

The P230 requires a 460 V three-phase 60 Hz supply with voltage tolerance ±5% and frequency tolerance ±2%, not combined unfavorably. External branch circuit protection according to UL 489 is mandatory. The unit is delivered with cable but without plug (three-phase below 63 A), so a suitable connection must be provided on site.

What maintenance and service items are required, and what is not included in base delivery?

Refrigerant circuit work must be performed by approved refrigeration contractors. Check refrigerant charge (1.49 kg R-449A) against room volume at installation. Cooling water supply must be shut off during downtimes. The base delivery includes cable but no plug; hoses and fittings for the G1 1/4 male pump connection are not included and must be ordered separately.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller P230
Datasheet ·200,0 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF