Peter Huber Kältemaschinenbau Unichiller 110T-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 110T-H

Peter Huber Kältemaschinenbau Unichiller 110T-H — Recirculating chillers with Noise level 74 dB.

The Unichiller 110T-H is a recirculating chiller with a C3 pump and Pilot ONE controller, rated for -10 to 100 °C in externally closed circuits. Its 2 kW heating and staged cooling (11 kW at 15 °C, 6 kW at 0 °C, 2.7 kW at -10 °C) distinguish it from the quieter 110Tw variants. It serves as a temperature-control source for industrial processes requiring a 400 V three-phase supply.

Noise level
74 dB

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Pump typeSafety classTemperature range, °CPower supplyExpansion volume, m³Minimum fill volume, m³
Unichiller 110T-H Current C3III / FL-10–100400V 3~ 50Hz0.007—
Unichiller 110T C3I / NFL-10–40400V 3~ 50Hz0.007—
Unichiller 110Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 130T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 130T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 130Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 160T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 160T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 160Tw C3I / NFL-20–40400V 3~ 50Hz0.01—
Unichiller 180-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 180T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 180T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 180Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 180Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 180w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 180w-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 200T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 200Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 210T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 210T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 210Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 230-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 230w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 230w-H E1III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller 250T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 250T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 250Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 260T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 260T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 260Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 260Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 300T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 300T-H D3III / FL-20–100460V 3~ 60Hz0.0390.014
Unichiller 300Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 300Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 350T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 350Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 500Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw-H D3III / FL-20–100400V 3~ 50Hz0.007—
Unichiller 700Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 800Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller GL 1000w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.05—
Unichiller GL 200w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 250w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 300w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 400w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 750w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.05—
Unichiller P180 E2I / NFL-20–40—0.0480.018
Unichiller P180-H E2III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller P180w E2I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller P180w-H E2III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller P230 E2I / NFL-20–40460V 3~ 60Hz0.0480.018
Unichiller P230-H E2III / FL-20–100460V 3~ 60Hz0.0480.018

Full specifications

Core Performance & Functional Specifications
Noise level 74 dB(A)
Expansion volume 7 l
Heating capacity 2 kW
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type C3
External sensor connection Pt100
Temperature range -10...100 °C
Dimensions, Weight & Mechanical Design
Weight 232 kg
Electrical, Power & Drive Specifications
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Mounting
Maintain 50–200 cm side clearance for maintenance access

Free-standing installation requires a wall clearance of 50 to 200 cm on either side to allow service access to the refrigerant circuit and pump. Planning the footprint without this clearance will obstruct maintenance and may violate the manual's installation requirements.

Unichiller Operation Manual, Section on Installation, p. 25
Electrical
Verify supply tolerance pairing before connecting

The datasheet permits ±5% voltage only when frequency deviation is within ±2%, and explicitly forbids opposite-sign deviations (e.g., -5% voltage with +2% frequency). Site power quality must be checked against this combined envelope, not each parameter independently.

Unichiller 110T-H Technical Data, p. 2
Electrical
Three-phase cable supplied without plug

Devices below 63 A are delivered with a cable but no plug. The installer must procure and fit a suitable mating plug for the 400 V 3~ 50 Hz supply, and account for this in the electrical commissioning schedule.

Unichiller 110T-H Technical Data, p. 2
Process Limits
Externally closed circuit only

The unit is designed exclusively for externally closed applications. Using it with an open tank or unsealed loop will cause evaporation, contamination and possible pump damage, and is outside the manual's intended use.

Unichiller Operation Manual, p. 34
Process Limits
Size cooling capacity at the actual set point

Cooling capacity falls from 11 kW at 15 °C to 2.7 kW at -10 °C, referenced to 20 °C room temperature. Selecting the unit on its nominal maximum will undersize the system for low-temperature operation, and rising ambient temperature further reduces available capacity.

Unichiller 110T-H Technical Data, p. 1–2
Cooling & Media
Shut off cooling water during overnight downtime

The cooling water supply must be shut off even for short downtimes such as overnight to prevent water damage and corrosion. This should be included in the site's daily shutdown procedure, not only in long-term maintenance planning.

Unichiller Operation Manual, p. 28
Maintenance
Refrigerant circuit work requires certified contractor

Any work on the refrigerant circuit must be performed by approved refrigeration/air-conditioning system contractors. The refrigerant is R-449A (GHS H280, GWP 1397), so leak response and handling must follow the corresponding safety rules and cannot be delegated to general maintenance staff.

Unichiller Operation Manual, p. 17
Control & I/O
Configure power-failure response for process safety

The Pilot ONE allows the power-failure response to be set to OFF/Standby, ON, or Power Failure Auto. For exothermic processes, the wrong choice can cause either uncontrolled restart or loss of cooling; the response must be selected deliberately during commissioning.

Unichiller Operation Manual, p. 19
Safety
Process Safety mode releases cooling on OT trigger

In Process Safety mode, maximum cooling capacity is released when the overtemperature protection trigger value is reached, instead of switching off all poles. This behavior must be matched to the process risk: it protects against runaway exotherms but is not a substitute for a hardwired emergency stop.

Unichiller Operation Manual, p. 18

Selection & Integration Q&A

When should I choose the 110T-H over the 110Tw-H or the base 110T?

Choose the 110T-H when the process needs heating up to 100 °C and a 74 dB(A) noise level is acceptable. The 110Tw-H is the low-noise alternative (65 dB(A)) for noise-sensitive rooms. The base 110T lacks the 2 kW heating, so it cannot cover the upper temperature range.

What hydraulic and electrical infrastructure must be in place before installing the 110T-H?

Provide a 400 V 3~ 50 Hz supply with a customer-supplied plug (cable delivered without plug), and G1 1/4 male mating fittings for the pump connections. The external circuit must be closed and its pressure drop checked against the pump curve (96 l/min max, 29 l/min at 5.0 bar).

What are the site and duty-cycle limits for installing this chiller?

Install indoors at 5–40 °C ambient, at least 300 lx illuminance, up to 2000 m altitude, with 50–200 cm side clearance for maintenance. IP20 requires a dry location. The unit is not ATEX-rated and must not be placed in a hazardous zone. Cooling water must be shut off overnight.

What maintenance and consumables are required, and what is not included in delivery?

Refrigerant circuit work must be done by approved refrigeration contractors; the R-449A charge (GWP 1397) requires leak checks. The atmospheric expansion tank must be kept covered and level-checked. The mating electrical plug is not included, and no interface cables are listed in the delivery.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF
PDF
Unichiller 110T-H Technical Data
Datasheet ·165,3 КБ ·2 pp.
View PDF